4.0 MECHANICAL INSTALLATION

Installation must be completed by competent persons, in accordance 
with good industry practice and should conform to all governing and 
statutory bodies i.e. IEE, CIBSE, etc.

The units are supplied for installation into In-line ductwork (internal) 
applications only. All ductwork connections must be airtight to prevent 
loss of performance. 

The unit has an external case side mounted control module / terminal 
box and is supplied ready for connection into the electrical supply. 
Typically the control is mounted on the side of the unit as standard 
(AVS2-9).

The method of mounting used is the responsibility of the installer. 

The 

units can be mounted in any attitude

 enabling alternative control 

positions. Access to the blower for maintenance can still be achieved 
for annual maintenance once orientation is changed, however if the 
motor requires replacing, the unit will have to be lowered to ground 
level if installed in non-standard configuration.

4.1 Umbilical Cord Kits (AVS1-8 Only)

As an option, an umbilical cord can be purchased for remote mounting 
up to 1m away (Figure 5). 

1m Umbilical Cord Kit Code: AVT-CK.

4.2 Surface Mounting Control Module (AVS1 Only)

The fan unit control module/terminal box is supplied loose for 
mounting up to 1 metre away from main unit (Figure 4). The unit must 
be mounted on a secure, vibration free vertical surface away from direct 
heat sources or water spray.

 
 
 
 

 
 

AVS1 Control Module

4.3 Surface Mounted Units

Utilising four matching anti-vibration (AV) mounting feet (Figure 1). 

AV 

mounts isolate the fan only, silencers / back draught dampers and 
other "significant mass" accessories should form part of the fixed 
ductwork after the flexible connection.

4.4 Units Suspended With Drop Rods

From the ceiling or in the ceiling void using four AV mounting feet 
supplied, with access panel positioned for underside access (Figure 2 & 
3).

4.5 Vertically Wall Mounted (Rigid) Units

Utilising the Aire-Volve Vertical Hanging Bracket kit that includes 
wall hanging brackets and hinges (Figures 5 and 6). The unit case has 
captive M8 nuts which can be used after removing the M8 ‘plugging’ 
screws. Units should always be positioned with sufficient space to allow 
the access panel to extend forward. 

Only suitable for topside and 

underside detachable access panel units mounted indoors.

 

Aire-Volve Unit Size

Aire-Volve Vertical Hanging Bracket Kit

1

AVT1-VK

2

AVT2-VK

3

AVT3-VK

4

AVT4-VK

Aire-Volve Unit Size

Aire-Volve Vertical Hanging Bracket Kit

4L

AVT4L-VK

5

AVT5-VK

6

AVT6-VK

Typical Installation Of Vertically Wall Mounted 
AVS-A(1-6) Unit Using Vertical Hanging Bracket Kit

Front Access Of Vertically Wall Mounted AVS-A(1-6) 
Unit Using Vertical Hanging Bracket kit

 

 

4.6 Anti-Vibration (AV) Mounts

AV mounts should not be fitted to a fan/silencer assembly unless there 
are flexible connectors fitted between the assembly and associated 
duct work. AV mounts should be installed with the matched mounting 
feet and positioned such that they carry an equal proportion of the 
assembly weight. This is particularly important where fans and silencers 
are installed on suspension rods. Suspension rods and fixing screws are 
not supplied.

Resilient rubber anti-vibration mounting kits (NAV) are available, 
the correct selection and type employed will depend on the accurate 
calculation of the weight of the assembly to be supported.

The large round washers included with the NAV(2-5) are for fitting 
above or below the resilient mounting as required to safeguard 
the installation against break-up of, or damage to, a mounting. In 
the event of a resilient mounting failure, the washer will support 
the weight of the unit. Fans using size NAV 6 upwards require 
supporting steelwork to be designed (by others) for suspended 
applications.

AV mounts must only be subjected to compressional forces and 
MUST NOT be used in a configuration that places these parts under 
tension or shear force.

Summary of Contents for AV55-MSS

Page 1: ...l not play with the appliance Cleaning and user maintenance shall not be carried out by children 1 1 Symbols GENERAL WARNING Signifies a general warning regarding hazard specified by supplementary information ELECTRIC SHOCK This unit must be completely electrically isolated before any panels are removed Check mains supply and control connections ROTATING PARTS This unit contains fast moving rotati...

Page 2: ...sembly positioned in series for optimum performance Units incorporate fully detachable top or bottom panels for maintenance and inspection purposes AVS 1 units have a loose control module for surface mounting up to 1 metre away from main unit AVS 8 and 9 units incorporate split access panels 2 1 Code Description 1 2 3 4 AV S CP 1 1 Range Aire Volve 2 Fan Type S Single Fan 3 Constant Pressure CP Co...

Page 3: ...mounting feet supplied with access panel positioned for underside access Figure 2 3 4 5 Vertically Wall Mounted Rigid Units Utilising the Aire Volve Vertical Hanging Bracket kit that includes wall hanging brackets and hinges Figures 5 and 6 The unit case has captive M8 nuts which can be used after removing the M8 plugging screws Units should always be positioned with sufficient space to allow the ...

Page 4: ...talled NAV 2 5 Floor Mounted Application 4 7 Dimensions mm Weights kg 4 7 1 AVS Units 12 AVS Dimensions A C D B B1 A1 Unit Code A A1 Bracket Centre Points B B1 Bracket Centre Points C D Weight kg AVS1 580 344 535 576 246 200 27 AVS2 615 380 535 646 281 200 24 AVS3 745 510 672 713 329 250 43 AVS4 788 553 672 713 373 315 47 AVS4L 914 678 818 860 391 315 67 AVS5 914 678 818 860 428 315 66 AVS6 1087 8...

Page 5: ...3 AVS7 MSS Standard 1000 1013 575 41 AVS7 MSL Large 1500 1013 575 98 AVS8 AVS8 MSM Mini 500 1237 615 51 AVS8 MSS Standard 1000 1237 615 83 AVS8 MSL Large 1500 1237 615 114 AVS9 AVS9 MSM Mini 500 1237 615 51 AVS9 MSS Standard 1000 1237 615 92 AVS9 MSL Large 1500 1237 615 125 4 8 Unit Access Unit can be installed inverted for ease of access to control e g control opposite side If inverted it will re...

Page 6: ...ncer Floor Mounted Unit And Inlet Silencer 17 Silencer Alignment Brackets 18 Installed AVS Silencer 4 10 AVSCP Constant Pressure Range Ecosmart constant pressure extract fans are supplied to control the static pressure at the fan inlet This set up is suitable for the majority of applications However when ancillaries with high pressure losses are fitted to the fan s inlet side the low pressure tapp...

Page 7: ... Ecosmart devices Min Max SL run on Trickle 0 1 Link wire see note Test Connection ES CO2 BMS Input Signal 0V 0 10V Ecosmart Pwr Standby Fan 1 Heating Fan 2 Cooling Fault TX RX Frost N L SL DP CL N RET Heat Demand Run Fault N L1 L3 L2 L3 L2 L1 N 400V 3ph 50Hz Supply Local isolator by others E 21 AVS9 Wiring Diagram 5 1 3 Control Module Volt Free Contact RUN signal 0 5A inductive 5A resistive Volt ...

Page 8: ... minute before starting If a damper is not fitted connect a link wire from OP to RET This will cancel the delay 25 Drive Open Drive Close Damper Connection All wiring is 1PH 230V 50Hz A fan starting delay of 1 minute is imposed to the enable the damper to open To override the delay fit a link here 230V motor OP CL N RET 2 S4 S6 1 26 Drive Open Spring Close Damper Connection All wiring is 1PH 230V ...

Page 9: ...cosmart products and will have indicators for functions that are not available in this particular fan However these indicators will not be illuminated A Commissioning Procedure document Document No 671153 is available on request from Nuaire 29 Commissioning Panel Details LED indicators Max Min Trickle Test 1 0 Pwr Standby Fan 1 Fan 2 Heating Cooling Fault Frost Tx Rx MIN Minimum speed adjustment M...

Page 10: ...Annually Thoroughly inspect the unit and its components for corrosion acting immediately to treat restore any damaged areas All electrical terminals within the unit should be tightened Check all earth connections Check control dampers blades Check operation of damper actuators and linkages and adjust as necessary 8 0 WARRANTY The 5 year warranty starts from the day of delivery and includes parts a...

Page 11: ...11 24 02 22 Document Number 671572 Nuaire Western Industrial Estate Caerphilly CF83 1NA nuaire co uk AVS Installation Manual NOTES ...

Page 12: ...12 24 02 22 Document Number 671572 Nuaire Western Industrial Estate Caerphilly CF83 1NA nuaire co uk AVS Installation Manual NOTES ...

Reviews: