Nuaire Group MRXBOX95B-LP1EH Installation And Maintenance Manual Download Page 6

6

05. 09. 13. Leaflet Number 671632

Installation and Maintenance

MRXBOX95B-LP1EH Mechanical Ventilation with Heat Recovery & Summer Bypass

The filters fitted inside the unit are protected with a 

plastic film. Prior to commissioning remove the covers

(fig 13), take off the film and replace.

Access to second filter

Filter cover and 
filter being removed

Control module

Figure 11. Remove the two filter covers on the underside panel of the
unit, and the filters can be pulled out of the unit using the tab on
the lower edge of the filter. 

Isolation - Before commencing work make sure that the unit,

switched live and Nuaire control are electrically isolated

from the mains supply and switched live supply. 

Figure 10. PCB inside enclosure.   

Access to Humidistat 
adjustment pot

Control module

7.0 Commissioning

1. For the required air flow rates please refer to the design 

specification for the property, follow 2.4, or refer to building 

regulations ADF 2006/2010.

2. The unit is supplied with independent control for both normal 

and boost airflows. (see fig. 10). 

3. Correct commissioning is essential to ensure the ventilation 

air flowrates are met. It also ensures the unit is not over 

ventilating and causing excessive power consumption. 

4. Commissioning should be carried out in accordance with 

building regulations document “Domestic ventilation 

compliance guide”. A calibrated moving vane anemometer 

and hood will be required to carry out commissioning.

5. Adjustment valves should be locked in place to prevent 

further adjustment. 

6. Once commissioned the home owner / tenant should be 

informed that the unit should not be adjusted as it will have 

a detrimental effect on the indoor air quality and could result 

in condensation and mould growth. The label covering the 

control has an adhesive panel which should be removed post 

commissioning to prevent tampering.

7.1 Summertime boost facility

The unit has to ability to override both the trickle and boost

speeds to operate the fan to maximum airflow. See wiring 

diagram for details of operating this facility.

7.2 Humidity adjustment

This product contains an internal humidity sensor fitted into the

airflow extracting from the wet rooms. When the unit senses

that the humidity exceeds the set point the unit will boost to

that set by the commissioned boost speed. The set point can be

found on the bottom of the unit (see fig 10) and is at its least 

sensitive when turned fully clockwise. Note that the sensor is

measuring humidity from all the wet rooms at the same time

and should not be relied on to solely boost the unit. 

Additional switch should be used local to the wet rooms (see

wiring diagrams).

8.0 Maintenance/Cleaning

We recommend that the two G3 fiters are inspected after 

6 months, and replaced every 12 to 18 months.

The filters can be removed from the unit by removing the two

filter covers on the bottom panel of the unit. Take hold of the

two circular tabs either end of the filter covers and pull to

remove. (see fig. 11). 

The filter can now be extracted by pulling the removal loop on

the edge of the filter. Once the filters have been inspected

return or replace them as necessary.

Inspect the heat exchanger every 5 years. Generally check 

for damage and security of components. Refit cover.

9.0 Replacement of Parts

Should any component need replacing Nuaire keep extensive

stocks for quick delivery. Ensure that the unit is electrically 

isolated, before carrying out any work.

Note: The supply cable must be replaced by an electrically 

competent person. 

When ordering spare parts, please quote the serial number 

of the unit and the ARC number of the purchase if possible.

(This information will be available on the fan label).

10.0 Warranty

The 5 year warranty starts from the day of delivery and

includes parts and labour for the first year and parts only for

the remaining 4 years. This warranty is conditional on planned

maintenance being undertaken

.

10.0 Service Enquiries

Nuaire can assist you in all aspects of service. Our Technical

Support department will be happy to provide any assistance

required.

Technical Support 

029 2085 8400

Summary of Contents for MRXBOX95B-LP1EH

Page 1: ...mains wiring must be in accordance with the current I E E Regulations or the appropriate standards Ensure that the mains supply Voltage Frequency and Phase complies with the rating label Please note...

Page 2: ...d be adjustable valve types not supplied External grilles to have a minimum free area of 12 250 sq mm 2 3 Ducting Before commencing ducting installation reference should be made to building regulation...

Page 3: ...um high rate from Table 1 For sanitary accommmodation only as an alternative the purge ventilation provisions given in ADF 2010 can be used where security is not an issue In this case minimum high ext...

Page 4: ...in ceilings Exhaust air from kitchen bathroom to outside via air brick Part no PVC505NS Supply and extract ducts from external air bricks to the unit needs to be insulated Minimum 300mm Top of ceilin...

Page 5: ...erving kitchen and bathroom Unit serving kitchen and two bathrooms Figure 8 Figure 9 For good EMC engineering practice any sensor cables or switched live cables should not be placed within 50mm of oth...

Page 6: ...eds to operate the fan to maximum airflow See wiring diagram for details of operating this facility 7 2 Humidity adjustment This product contains an internal humidity sensor fitted into the airflow ex...

Page 7: ...ffected 3 2 When handling the equipment care should be taken with corners and edges and that the weight distribution within the unit is considered Lifting gear such as slings or ropes must be arranged...

Page 8: ...8 05 09 13 Leaflet Number 671632 Western Industrial Estate Caerphilly United Kingdom CF83 1NA T 029 2085 8400 F 029 2085 8444 E info nuaire co uk W www nuaire co uk...

Reviews: