INTRODUCTION 

This manual has been produced to enable users to install, commission and use the MDFL burners 
safely and efficiently.  At each stage the conditions that should be met and the adjustments and other 
actions that should be carried out are detailed and the locations of the various components and 
adjustment mechanisms are identified.  Where appropriate, this information is supported by tables 
and graphs. 
 

FEATURES 

Developed through extensive field experience in the UK and overseas markets, the MDFL series of 
dual fuel burners meets all current test authority requirements in these markets and sets new 
standards in efficient and reliable operation. 

 

MDFL burners are designed for flange mounting to the appliance frontplate and they are delivered 
ready to install with a pre-wired packaged control system and plug-in gas train. 
 

Burner Capacity 

The figures quoted are nominal burner  

 

 

Burner Model  

Capacity kW 

outputs based on the nett calorific value. 

 

 

  MDFL 3300   

  1550-3367 

         

 

MDFL 

4000 

  

 

1350-4095 

 
Please refer to the Appendix of this handbook for detailed burner performance data. 

 

Fuel

 

MDFL burners are suitable for light distillate oil (Class D) and Natural Gas 
 

Air Fan Size

 

To match MDFL burners with the appliance, with 
respect to both burner output and appliance 
resistance, a number of combustion air fan sizes 
are available for each model, as detailed in the 
table opposite. 

 

The fan size quoted is the diameter of the fan impellor (measured in cm) and appears as a suffix to 
the model number.  For example, a burner designated MDFL 3300-36 is a model 3300 with a 36cm 
diameter combustion air fan impellor. 

 

Controls and Safety Systems

 

MDFL burners are fitted with a combustion airflow control and an air/fuel ratio control system which 
together ensure smooth starting and optimum operating efficiency. 

 

An air pressure switch provides safe burner shutdown if the combustion air supply becomes 
insufficient for complete combustion.  The burners additional safety systems include for gas pressure 
monitoring (low and high) whilst gas firing.  Continuous flame supervision is provided by an ultraviolet 
(UV) cell and automatic programming control unit. 

 

Operating Mode

 

The MDFL 3300 and 4000 burners operate in fully modulating mode when firing on gas, and 2 stage 
(high/low) mode when firing on oil. 

 

Oil Firing – 2 stage Operation

 

MDFL 3300 and 4000 burners are supplied with a system designated ‘Sliding High/Low’ which uses a 
single spillback oil nozzle (similar to that employed in the fully modulating mode) which is constrained 
to operate at either of two fixed oil flows corresponding to the high and low fire rates.  If the burner 
has been correctly matched to the appliance, a turndown ratio of up to 3.0:1 may be achieved. 

 

Gas Firing – all Models

 

When gas firing, the fuel gas flow is controlled by an automatic valve which, following commissioning, 
precisely matches the fuel flow to the air flow to achieve the required fuel/air ratio at any point in the 
full turndown range.  If the burner has been correctly matched to the appliance, a turndown ratio 
between 2.0 and 2.5:1 may be achieved. 
 
 

MDFL 3300 & MDFL 4000  Issue 2  08/08 

 

 

 

 

 

  

 

             Page 5 

Burner Model 

Available Fan Sizes 

MDFL 3300 

36, 41 

MDFL 4000 

36, 41, 44 

Summary of Contents for MDFL 3300

Page 1: ...Installation Maintenance Manual MDFL 3300 MDFL 4000 Dual Fuel Burner 11 12 Tel 44 0 1905 794331 Fax 44 0 1905 794017 Email info nu way co uk Web www nu way co uk...

Page 2: ...r 11 Gas train 12 Oil Controls Single Spill Back Nozzle 16 Control Panel 20 Burner Controller 20 Modulating Controller 20 BURNER OPERATING SEQUENCE 22 MODULATING CONTROLS 23 Controller 23 Commissionin...

Page 3: ...is essential that the following instructions and adjustments are carried out by qualified engineers that are experienced in forced draught gas and pressure jet oil burner commissioning In the UK it i...

Page 4: ...Pressure Switch 7 Burner Terminal Panel 19 Flexible Oil Pipe 8 Casing Access Lid 20 Quick Release Oil Couplings 9 High Gas Pressure Switch 21 Pressure Gauges 10 Valve Body 22 Oil Manifold 11 Control V...

Page 5: ...MGN 3300 MGN 4000 Page 4 BURNER MOUNTING ARRANGEMENT MDFL 3300 MDFL 4000 Issue 2 08 08 Page 4 BURNER MOUNTING ARRANGEMENT MODELS MDFL 3300 4000 Hole Diameter 350mm...

Page 6: ...er For example a burner designated MDFL 3300 36 is a model 3300 with a 36cm diameter combustion air fan impellor Controls and Safety Systems MDFL burners are fitted with a combustion airflow control a...

Page 7: ...riately rated for the maximum gas flow rate anticipated It is essential that a 90 manual isolation valve is fitted upstream of the gas control train to allow the burner to be isolated for maintenance...

Page 8: ...priately rated for the maximum oil flow rate anticipated Galvanised steel pipe should not be used The supply pipework should include an appropriate filter The final connection to the oil pump inlet po...

Page 9: ...be maintained and all exposed pipework must be lagged 3 If a shut off valve is fitted in the supply line to the burner oil pump inlet then a pressure relief valve MUST also be fitted to prevent damage...

Page 10: ...that lifting gear should be employed if necessary INSTALLATION General Ensure that the appliance is suitable for the heat input of the burner If there is any doubt in this area reference should be ma...

Page 11: ...as pressure switch is fitted at the outlet of the gas train to ensure that any increase in gas supply pressure above the level needed to maintain the set conditions results in a safe burner shutdown I...

Page 12: ...ts mounted on a common shaft within the Modulating Cam Box 2 The operation and adjustment of the Modulating Cam Box arrangement should be fully understood before attempting to adjust the motor setting...

Page 13: ...Page 12 TYPICAL GAS TRAIN Item Description Item Description 1 Manual Gas Interlock Valve 5 Control Valve 2 Low Gas Pressure Switch 6 Pilot Solenoid Valve 3 Main Valve 7 Pilot Governor 4 Valve Proving...

Page 14: ...n continuously operating flue gas damper or the combustion chamber pressure changes from negative to positive whilst moving from Low to High flame then a compensating circuit is required This means th...

Page 15: ...on of the burner control circuit prior to burner start up The proving test is based upon the 2 stage pressure proving principal First the main safety valve V1 on the upstream side of the gas circuit i...

Page 16: ...MDFL 3300 MDFL 4000 Issue 2 08 08 Page 15 VALVE PROVING SYSTEM LDU 11 Standard fitting...

Page 17: ...imum performance under the specified operating conditions Any queries regarding the size of the nozzle should be referred to Nu way The nozzle is held in position by the inner assembly lance through w...

Page 18: ...OIL PUMPING SET FOR DISTILLATE FUELS Connection Sizes Item Description Size inches 1 Main Inlet Connection 1 2 Main Return Connection Optional 1 3 Burner Feed 4 Burner Return Mounting Dimensions Burn...

Page 19: ...il Pump with TV Pressure Regulator Connection Sizes Item Description Size P Pressure port R Return port S Suction port Pn Vacuum gauge i t l b l Ps Pressure gauge 1 Regulator cap nut 2 Washer 3 Regula...

Page 20: ...All interconnecting pipework must have a minimum bore of 19mm and must be pressure rated for 42 kg cm2 2 Solenoid valves are shown as either NO normally open or NC normally closed 3 Pipework connecti...

Page 21: ...PERATURE PRESSURE in the appliance Also located on this enclosure are the fuel selector switch and two additional neon lights The amber light is illuminated when OIL is the chosen fuel and the red lig...

Page 22: ...to drive to open position proved by servo motor limit switch P Yes Lockout caused by the failure of the air pressure switch to changeover from the no air position shortly after the start of the pre pu...

Page 23: ...ed by the pressure and or temperature requirements of the appliance Time seconds LFL 1 333 Description T1 40 Pre purge T2 6 Pre ignition T3 3 Safety lockout time T4 Not applicable to two stage or full...

Page 24: ...sition between low and high flame Commissioning Controls Two switches Hand Auto and Inching are included in the burner panel In auto mode the burner will respond to the demand of the boiler via the RW...

Page 25: ...hat the electrical wiring is complete and complies with all applicable Codes and Standards 2 Ensure that the fuses are fitted and of the correct ratings 3 Check electrical earthing 4 Verify that the g...

Page 26: ...n scale 1 to 0 8 by adjusting screw 1 anti clockwise to increase clockwise to decrease Set the ratio on the remaining scale to half a division on the positive side of 0 by adjusting screw 2 in the sam...

Page 27: ...n the burner at the control panel The modulating unit cam shaft should now rotate to the high flame setting and the combustion fan motor will start the air pre purge phase 11 Allow the fan motor to ru...

Page 28: ...that it gives approximately 1 5mm throw 3mm stroke and lock in position 2 Check to ensure that the spill valve push rod bears slightly against the oil cam refer to page 29 3 Rotate the air cam adjust...

Page 29: ...satisfactory flame is achieved again check the line and spill pressures 11 Inch the camshaft back to the low flame position The oil consumption rate should now be between 40 and 50 of the rated maximu...

Page 30: ...MDFL 3300 MDFL 4000 Issue 2 08 08 Page 29 MODULATING CAM BOX...

Page 31: ...al Premises 4 Open the control panel cover and set the burner for low flame hold On modulating burners not fitted with a low flame hold switch set the Hand Auto switch to the Hand position 5 If a gas...

Page 32: ...at required for the maximum required continuous output from the burner and not more than 200 mbar Before proceeding with commissioning 1 Fit a manometer or other approved pressure measuring instrument...

Page 33: ...o the diagram on page 13 until an acceptable figure is achieved In extreme cases the adjustment on screw 2 may be exhausted without achieving an acceptable CO level In this event reset the high fire a...

Page 34: ...burner Allow the burner to light and establish the start gas flame 4 Check the gas flow rate The appropriate setting is usually found between 25 and 30 of the main flame gas rate The start gas rate mu...

Page 35: ...other approved pressure measuring instrument to the pressure switch to enable a comparison to be made between the pressure switch indicator and the measured pressure if required 3 Remove the control p...

Page 36: ...made in small increments with time given to see how the burner is reacting to the changed parameter Press and hold the PGM button down until the green set point figure changes to an AL the larger upp...

Page 37: ...eer shall prepare a report which shall contain the following 1 Details of any modifications made to the system together with revised drawings if necessary 2 Customer and plant details including any se...

Page 38: ...on oil for a prolonged period it may be necessary to purge the gas line of air 6 If the burner is to be operated with gas for a prolonged period it may be desirable to remove the oil pump couplings RO...

Page 39: ...ct the ignition leads Remove the two screws which secure the oil manifold within the hinged extension Remove the four bolts which locate the inner assembly and withdraw the assembly taking care not to...

Page 40: ...al Landis Staefa LFL 1 333 Terminals 13 and 14 4 If the air pressure switch is not in the start position turn the setting dial clockwise fully to the maximum setting Check again for continuity between...

Page 41: ...e followed 1 Switch off the burner and the electrical power supply to the burner 2 Disconnect the multi pin plug from the socket on the control system 3 Remove the screw which holds the control system...

Page 42: ...fully modulating burners additional data at intermediate positions in the operating range between high and low fire are required A copy of the completed sheet must be sent to the appliance manufactur...

Page 43: ...Electrode Setting Details MDFL 3300 MDFL 4000 Issue 2 08 08 Page 42 All dimensions in mm...

Page 44: ...MDFL 3300 MDFL 4000 Issue 2 08 08 Page 43 Performance Envelopes MDFL 3300 and MDFL 4000 MDFL 3300 MDFL 4000...

Page 45: ...Guarantee Expiry Date Fuel Oil Type Oil pressure upstream of pump Standing bar or psi Running bar or psi Firing Rate High Fire Intermediate Positions Low Fire Units 1 Oil bar or psi Pressure at burner...

Page 46: ...piry Date Fuel Oil Type Gas pressure upstream of main governor Standing mbar or ins wg Running mbar or ins wg Firing Rate High Fire Intermediate Positions Low Fire Units 1 Gas mbar or ins wg Pressure...

Page 47: ...CORD The details below are to be completed by the Servicing Engineer This sheet to be completed and signed following each service adjustment Date Details of Service Signature MDFL 3300 MDFL 4000 Issue...

Page 48: ...NOTES MDFL 3300 MDFL 4000 Issue 2 08 08 Page 47...

Page 49: ...Enertech Limited P O Box 1 Vines Lane Droitwich Worcestershire WR9 8NA Tel 44 0 1905 794331 Fax 44 0 1905 794017 Email info nu way co uk Web www nu way co uk...