INTRODUCTION
This manual has been produced to enable users to install, commission and use the MDFL burners
safely and efficiently. At each stage the conditions that should be met and the adjustments and other
actions that should be carried out are detailed and the locations of the various components and
adjustment mechanisms are identified. Where appropriate, this information is supported by tables
and graphs.
FEATURES
Developed through extensive field experience in the UK and overseas markets, the MDFL series of
dual fuel burners meets all current test authority requirements in these markets and sets new
standards in efficient and reliable operation.
MDFL burners are designed for flange mounting to the appliance frontplate and they are delivered
ready to install with a pre-wired packaged control system and plug-in gas train.
Burner Capacity
The figures quoted are nominal burner
Burner Model
Capacity kW
outputs based on the nett calorific value.
MDFL 3300
1550-3367
MDFL
4000
1350-4095
Please refer to the Appendix of this handbook for detailed burner performance data.
Fuel
MDFL burners are suitable for light distillate oil (Class D) and Natural Gas
Air Fan Size
To match MDFL burners with the appliance, with
respect to both burner output and appliance
resistance, a number of combustion air fan sizes
are available for each model, as detailed in the
table opposite.
The fan size quoted is the diameter of the fan impellor (measured in cm) and appears as a suffix to
the model number. For example, a burner designated MDFL 3300-36 is a model 3300 with a 36cm
diameter combustion air fan impellor.
Controls and Safety Systems
MDFL burners are fitted with a combustion airflow control and an air/fuel ratio control system which
together ensure smooth starting and optimum operating efficiency.
An air pressure switch provides safe burner shutdown if the combustion air supply becomes
insufficient for complete combustion. The burners additional safety systems include for gas pressure
monitoring (low and high) whilst gas firing. Continuous flame supervision is provided by an ultraviolet
(UV) cell and automatic programming control unit.
Operating Mode
The MDFL 3300 and 4000 burners operate in fully modulating mode when firing on gas, and 2 stage
(high/low) mode when firing on oil.
Oil Firing – 2 stage Operation
MDFL 3300 and 4000 burners are supplied with a system designated ‘Sliding High/Low’ which uses a
single spillback oil nozzle (similar to that employed in the fully modulating mode) which is constrained
to operate at either of two fixed oil flows corresponding to the high and low fire rates. If the burner
has been correctly matched to the appliance, a turndown ratio of up to 3.0:1 may be achieved.
Gas Firing – all Models
When gas firing, the fuel gas flow is controlled by an automatic valve which, following commissioning,
precisely matches the fuel flow to the air flow to achieve the required fuel/air ratio at any point in the
full turndown range. If the burner has been correctly matched to the appliance, a turndown ratio
between 2.0 and 2.5:1 may be achieved.
MDFL 3300 & MDFL 4000 Issue 2 08/08
Page 5
Burner Model
Available Fan Sizes
MDFL 3300
36, 41
MDFL 4000
36, 41, 44
Summary of Contents for MDFL 3300
Page 16: ...MDFL 3300 MDFL 4000 Issue 2 08 08 Page 15 VALVE PROVING SYSTEM LDU 11 Standard fitting...
Page 30: ...MDFL 3300 MDFL 4000 Issue 2 08 08 Page 29 MODULATING CAM BOX...
Page 43: ...Electrode Setting Details MDFL 3300 MDFL 4000 Issue 2 08 08 Page 42 All dimensions in mm...
Page 48: ...NOTES MDFL 3300 MDFL 4000 Issue 2 08 08 Page 47...