Nu-Air Ventilation Systems Inc. - HRV Operating & Installation Manual
Rev. 2.3 Aug. 19, 2014
- 3 -
VENTILATION PERFORMANCE
ENERGY PERFORMANCE
EXT.
STATIC
NET SUPPLY
GROSS AIR FLOW
SUPPLY
NET
POWER
SENSIBLE
APPARENT
PRESSURE
AIR FLOW
SUPPLY
EXHAUST
TEMP.
AIR FLOW
CONSUMED
RECOVERY
SENSIBLE
in wg (Pa)
cfm (l/s)
cfm (l/s)
cfm (l/s)
ºF (ºC)
cfm (l/s)
Watts
EFFICIENCY
EFFECTIVENESS
0.1 (25)
173 (81)
180 (84)
193 (91)
+32 (0)
61 (29)
54
63
75
0.2 (50)
159 (75)
165 (78)
175 (82)
+32 (0)
85 (40)
66
62
72
0.3 (75)
146 (68)
151 (71)
159 (75)
+32 (0)
114 (54)
94
61
70
0.4 (100)
132 (62)
137 (65)
144 (68)
0.5 (125)
119 (56)
123 (58)
130 (61)
13 (-25)
62 (29)
58
65
78
0.6 (150)
105 (49)
109 (51)
116 (55)
0.7 (175)
90 (42)
94 (44)
103 (48)
1.
PERFORMANCE RATINGS & PHYSICAL DATA
Model: NU165
ELECTRICAL: 120V/1/60 Hz. 128W, 1.1A