2
2. Using the terminal connected to the ENVIROMUX, start the terminal program (e.g. Windows HyperTerminal) and configure it
as follows:
direct connection (using the appropriate CPU local serial Com port)
115200
bps
8
bits
no
parity
1 stop bit
no flow control
VT100 terminal mode.
3. Power ON the ENVIROMUX and as the ENVIROMUX begins to boot, press and hold the <
Tab
> key. (If you fail to press this
key in time the system will continue booting and you will have to power OFF the ENVIROMUX and start over.)
Erase the configuration of the ENVIROMUX
4. At the “SEMS-16>” prompt, type;
SEMS-16>
nand erase config
5. Press <
Enter
> key.
The ENVIROMUX will erase all configuration settings and restore the ENVIROMUX to factory default settings. ALL USER
CONFIGURATION AND SENSOR CONFIGURATION SETTINGS WILL BE LOST.
When finished, the “SEMS-16>” prompt will return.
6. At the prompt, type
reset
and press <
Enter
>. The ENVIROMUX will restart.
Type
nand erase config
Type
reset