NTC HC10B Installation & User Manual Download Page 1

 

INSTALLATION & USER GUIDE 

 

 

 

UK          0200008-2.3 

Thermostat: HC10B 

 

 

Fig. 1 Connections 

  

L / N: Line and Neutral 
Mains 230-240 VAC connection 
OUT / N: Heating cable connection 
Sensor: Floor sensor connection 
Earth connected separately 
 
 
 

User instructions - General information.

 

A)  What HC10B does 

 

HC10B is a digital thermostat for precise control of electric underfloor heating. 

 

HC10B starts automatically in Quickstart = Manual mode and floor sensor 

 

HC10B can also perform night and day setback in three different ways 

 
B)  IMPORTANT! 

Important information before connecting the underfloor heating 

 

To ensure optimum service life of the underfloor heating, the material in which the heating system is laid must be allowed to 
dry for a minimum of 28 days before switching on the heat. 

 

A new installation of HC10B and underfloor heating must be carried out by an authorised electrician. 

 

Exchanging an HC10B, is allowed to do by the end-user in most countries. 

 

HC10B must not be covered 

C)  Programs in HC10B 

 

C1) Quickstart 

 

Switch on and the underfloor heating will start up. 

 

The temperature is set to 21

 O

 

The temperature can be altered with [▼] and [▲] 

  The display shows the set temperature 

 

The floor sensor will automatically start operation 

 

C2) Night and day setback programs 

 

HC10B holds three different night and day setback programmes. 

 

They each control the temperatures and time settings. i.e. low temperature at night and during working hours, higher 
temperature at morning and evening. 

 

For each program the starting time and temperature are determined. Start times and temperatures are set at the factory, but 
can be changed as required. The factory setting is shown in Table 1. 

 

Night and day setback ensures minimum power consumption. With optimum adjustment of the underfloor heating the average 
temperature can be dropped by up to 3 

o

C, giving potential power savings of up to 15%. The savings will naturally depend on 

the circumstances and on what you want from the underfloor heating. 

 

Max. and min. limits are in all programs Max: 27 

o

C Min.: 15 

o

C.  

 

Program 1: Settings for Monday to Friday, and settings for Saturday and Sunday. 
Program 2: Settings for All Weekdays. 
Program 3: Settings for Each Day of the Week separately. 

 
 
Table 1: Factory setting for night and day setback. 

Times and temperatures can be changed as required. See section 3.4) and 3.5). 

 

 

Technical data: 

Voltage: 

230-240 VAC 

Frequency: 

50-60 Hz 

Resistive load: 

1 6 A (3600 W-230 VAC) 

Inductive load: 

1 A 

Ingress protection:  IP30 
Temperature range: 5 °C - 40 °C 
Tolerance sensor:  ±1.5 °C @ 10-30 °C 
Signal sensors: 

Room, Floor, Combined 

Sensor type: 

NTC 10 kΩ @ 25 °C Double 
insulated 

Terminals: 

1.5 mm

²

 

– 4.0 mm

²

 

Apply: 

 LVD 2014/35/EU 

 EN60730-2-9 

 EN 50081-1 

 EN 50082-1 

 RoHS 

 