AMBIENT
TEMPERATURE
(DEGREES C)
110S TEMPERATURE
PROBE SIGNAL OUTPUT
(VOLTS)
-5
1.46
-4
1.48
-3
1.50
-2
1.52
-1
1.54
0
1.55
1
1.57
2
1.59
3
1.61
4
1.63
5
1.65
6
1.66
7
1.68
8
1.70
9
1.72
10
1.74
Press SEL.
Use the left / right and up / down arrows to make your selection. Once you are on the setting
you wish to modify, press SEL. Use the up/down arrows to adjust the value for that setting.
Press OK to save your selection.
6.6.4 Temperature Threshold for Switching off the Heater
Press ESC. You should see the PLC home screen “NRG Systems”, press the up arrow three times to enter
the Temperature Threshold menu. The threshold values are in the units of Volts. Use the table found in
the section above to determine the voltage for the desired switch-off temperature.