background image

Timer NT240 

NOVUS AUTOMATION 

2/5

 

Connections of the input signals 
The type of signal to be applied to the inputs is determined by the 

user in the 

PnP

 parameter of the timer. The signal type must be the 

same for the three inputs (Start, Hold and Reset). 

Sensors with NPN/PNP open collector output: 
Common to most proximity sensors, must be connected as indicated 

in Figure 02. The 

PnP

 parameter must be set to 0 for NPN sensor 

output and to 1 for PNP. 

 

Figure 02 – Connecting PNP/NPN type sensor

 

- Signal from relay or switch (dry contact): 
Wire  dry contacts as shown on Figure 03. For this type of input, 

configure 

PNP

 = 0

 

Figura 03 - Conectando contato seco (relé, interruptor)

 

Voltage input signal 
Refer to the “Specifications” section for the input voltage levels 

compatible with the timer. Figure 04 shows the wiring scheme. 
When 

PNP

 = 1, the timer recognizes the rising edge of the pulse  

For the recognition of the falling edge, set  

PnP

 = 0. 

 

Figure 04 - Connection for pulse input.

 

OPERATION 

Following power-on, the timer shows the main screen (Time) and will 

remain in this screen in normal operation. 
For configuring the timer, it is necessary to set proper values to the 

various internal parameters.  
The parameters are organized in three levels. To enter these levels, 

one must press the 

P

 

key for defined intervals of time, as shown 

below.  

Levels structure: 

Indication of elapsed time 

    Shown on power-up;  

2   Setpoint level (temporization setpoints) 

     To enter, press 

P

 for 4 seconds;  

3   Configuration level. 

     Press  

P

  

for 8 seconds;  

4   Custom Operating mode level.  

     Press  

P

 

for 12 seconds;  

 

To enter into deeper levels, press the 

P

 

for the time required by 

the level and when the timer shows the first parameter of that level, 

simply release the 

P

 

key to stay in that level. Other parameters in 

that level are accessed by pressing the 

P

 key. 

To modify the value of a parameter use the    and    keys for 

incrementing or decrementing the value, respectively.  After the last 

parameter of the cycle is reached, the timer returns the main screen 

(Indication of Elapsed time).  
The modified values are stored in a non-volatile memory when the 

P

 

key is pressed to move to the next parameter.  

PROGRAM SECURITY 

To avoid tampering, parameter “

Prot

” and a hardware jumper can 

be used to disable access to programming parameters. 
With the jumper in the OFF  position, all program levels are 

unprotected. The “

Prot

” parameter can only be changed with the 

jumper in the OFF position. 
With the jumper in the ON position or removed, the protection level 

is defined by the current value of the “

Prot

” parameter: 

0

  No protection. All parameters can be accessed; 

1

  No access to Operating mode level. 

2

  No access to Operating mode level and Configuration level. 

3

 

Full protection. 

 

OFF 

 

 

ON 

 

Figure 2 – Protection Disabled 

Figure 3 – Protection Enabled 

Temporization Setpoints Level 

T1.sp 

Timer 1 SetPoint

 

Timer Setpoint: It defines the total time to be 

counted by the timer. In up counting, the timer 

counts from zero to the value programmed in 

t1.SP

. In countdown, the timer counts from the 

value programmed in 

t1.SP

 to zero. 

0v1.t 

Output 1 Time 

 

Output temporization: Defines the interval of time 

the output is to remain active after the time 

programmed in 

t1.SP

  has elapsed (parameter 

T1.S4

  shall be set to 1 

  output turns off after 

output temporization).  
During the output temporization the relays are 

maintained active while the corresponding LEDs 

blink to indicate the output temporization is taking 

place. 

Reviews: