2.6 Alert Threshold
The Alert Threshold screen allows the user to adjust the tolerance from the
Reference Voltage which, if exceeded in either direction, the output channels will
report a fault status. The default threshold value is set at
±
55% percent from the
current state of the amplifier, and is user programmable in 5% increments, from
±10% to ±60%.
Each channel has a Reference Voltage which can be set, all at once, by latching
the channels’ current value in the Latch Channel Average Screen. Each channel’s
Reference voltage can be set individually by writing the value serially with the
$SET command. After saving the current configuration on a channel, any
subsequent deviation on that channel which exceeds the Alert Threshold
percentage will trigger an alert.
Steps to ensure correct Alert configuration:
1.
Connect distribution cabling to channels 1 through 16.
2.
Set Alert Threshold to desired range.
3.
Save current channel voltages with the Latch Channel Values Screen.
4.
Save current settings on the Save Configuration screen.