Novus N2000 Instruction Manual Download Page 3

Controller N2000  

NOVUS AUTOMATION 

3/11 

The alarm functions are described in Table 3

TYPE 

PROMPT 

ACTION 

Disabled 

off

 

No active alarm. This output can be used as a 

digital output to be set by the serial 

communication. 

Sensor Break 

(input Error) 

ierr

 

Alarm will be ON if PV sensor breaks, input signal 

is out of range or Pt100 is shorted. 

Event Alarm 

(ramp and 

Soak) 

rs

 

Can be activated at a specific segment of ramp 

and soak program. 

Low Alarm 

lo

 

SPAn

PV

 

High Alarm 

ki

 

 

SPAn 

PV 

 

LOW 

Differential 

difl

 

 

SV 

PV 

SV - SPAn 

 

positive SPAn  

 

SV 

PV 

SV - SPAn 

 

negative SPAn  

HIGH 

Differential 

difk

 

 

positive SPAn 

 

negative SPAn 

Differential 

dif

 

SV

PV

SV + SPAn

SV - SPAn

 

positive SPAn 

 

SV 

PV 

SV - SPAn 

 

SV + SPAn 

 

 

negative SPAn 

Table 3 - Alarm functions 

ALARM TIMER FUNCTIONS 
The controller alarms can be configured to perform 4 timer modes: 

 

Continuous (normal mode).

 

 

One pulse with defined duration;

 

 

Delayed activation; 

The illustrations in Table 4 show the behavior of the alarm output for 

various combinations of times T1 and T2. The timer functions can be 

configured in parameters 

A1t1

A2t1

A3t1

A4t1

A1t2

A2t2

A3t2

A4t2

ALARM 

FUNCTION 

T1 

T2 

ACTION 

Normal 

Alarm Event

Alarm

Output

 

Delayed 

1 s to 6500 

Alarm Event

Alarm

Output

T2

 

Pulse 

1 s to 6500 

Alarm Event

Alarm

Output

T1

 

Oscillator  1 s to 6500 

s  

1 s to 6500 

Alarm Event

Alarm

Output

T1

T2

T1

 

Table 4 - Advanced Timer Alarm. 

The LEDs associated to the alarms will light when the alarm 

condition is recognized, not following the actual state of the output, 

which may be temporarily OFF because of the temporization. 

ALARM INITIAL BLOCKING 
The initial blocking option inhibits the alarm from being recognized if 

an alarm condition is present when the controller is first energized. 

The alarm will actuate only after the occurrence of a non alarm 

condition followed by a new occurrence for the alarm. 
The initial blocking is disabled for the sensor break alarm function. 

SQUARE ROOT EXTRACTION 
Available when input type 19 is selected. The indicator displays the 

square root of the current signal input applied to terminals 22 and 24. 

ANALOG RETRANSMISSION OF PV AND SP 
The analog output, when not used for control purposes, is available 

for retransmitting the SV and SP values in 0-20 or 4-20 mA. This 

analog output is electrically isolated from other inputs and outputs. 

The analog output signal is scaleable, with the output range 

determined by the values programmed in the parameters “

SPLL

” 

and “

SPkL

”. To obtain a voltage output, connect a resistor shunt to 

the current output terminals. 
It is possible to obtain a voltage output by installing a resistor shunt 

(550 

Ω 

max.) to the current output terminals (terminals 7 and 8). The 

actual resistor value depends on the desired output voltage span. 

SOFT START 
The soft-start feature avoids abrupt variations in the power delivered 

to the load regardless of the system power demand. 
This is accomplished by defining a limiting ramp for the control output. 

The output is allowed to reach maximum value (100 %) only after the 

time programmed (in seconds) in the soft-start parameter has elapsed.   
The Soft-start function is generally used in processes that require slow 

start-up, where the instantaneous application of 100 % of the available 

power to the load may cause damages to parts of the system.  
In order to disable this function, the soft-start  parameter must be 

configured with 0 (zero). 
Note: 
1- This feature is available only with PID (Proportional Band greater 

than zero). 
2- This feature is disabed if the parameter is set to 0 (zero) 

REMOTE SETPOINT 
The controller can have its Setpoint value defined by an analog, 

remotely generated signal. This feature is enabled through the 

channels I/O3, I/O4 or I/O5 when configured as digital inputs and 

configured with the function 

rsp

 (Remote SP selection) or through 

the parameter 

E.rsp

. The remote Setpoint input accepts the signals 

0-20 mA, 4-20 mA, 0-5 V and 0-10 V.  
For the signals of 0-20 and 4-20 mA, a shunt resistor of 100 

 is 

required between terminals, as shown in Figure 4d

LBD - LOOP BREAK DETECTION ALARM 
The parameter defines a time interval, in minutes, within which the 

PV is expect to react to a control output signal. If the PV does not 

react properly within the time interval configured in 

lbd.t

, the 

controller interprets this as a control loop break and  signals this 

occurrence in the display.  
A LBD event may be sent to any I/O channel. Simply configure the 

LDB

  function to the desired I/O channel: the selected output will be 

activated when  a 

LDB

  condition is detected. When the 

lbd.t

 

parameter is programmed with 0 (zero), the 

LDB

 function is disabled. 

The 

LDB

 is useful in system supervision and troubleshooting, allowing 

early detection of problems in the actuator, power source or load. 

 KEY FUNCTIONS 

Both the    key digital input can be programmed to execute 

functions 

RVN , RSP,  kPRG,  PR1 

shown in Table 2. The key 

function is configured in parameter (

fFvn

).  

   

 KEY   

The 

   

  key in front panel executes function 6 of Table 2

Auto/Manual mode change. Operation of this key is enabled in 

parameter 

mAN

. The MAN indicator lights when the manual control 

mode is selected.   

EXTRA 24 VDC POWER SUPPLY – AUXILIARY P.S. 
The controller provides a voltage power supply of 24 Vdc to excite 

field transmitters with 25 mA current capacity. Available at the back 

panel terminals 17 and 18. 

Summary of Contents for N2000

Page 1: ...ing of PID parameters Automatic Manual function with bumpless transfer Four modes of independents alarms with functions of minimum maximum differential deviation open sensor and event Timer functions that can be associated to the alarms Retransmission of PV or SP in 0 20 mA or 4 20 mA Input for remote setpoint Digital input with 5 functions Programmable soft start 7 setpoint profile programs with ...

Page 2: ...s opened again Closed Contact Enables execution of the program Opened Contact Interrupts execution of the program Note Even when the execution of the program is interrupted the control output remains active and controlling the process at the point Setpoint of interruption The program will resume its normal execution starting from this same point when the digital input is closed PR 1 Digital input ...

Page 3: ...ain a voltage output by installing a resistor shunt 550 Ω max to the current output terminals terminals 7 and 8 The actual resistor value depends on the desired output voltage span SOFT START The soft start feature avoids abrupt variations in the power delivered to the load regardless of the system power demand This is accomplished by defining a limiting ramp for the control output The output is a...

Page 4: ...tely disconnected from the input output signals Using the USB in any other type of connection is possible but requires a careful analysis by the person responsible for installing it When MONITORING for long periods of time and with connected inputs and outputs we recommend using the RS485 interface which is available or optional in most of our products INSTALLATION CONNECTIONS The controller must ...

Page 5: ...alue of PV Process Variable When in programming mode shows the parameter name Parameter display SV shows the SV Setpoint Variable value and the value of other parameters of the controller COM Indicator Flashes when communication messages are sent by the controller TUNE Indicator Lights during the execution of PID automatic tuning MAN Indicator Lights when the controller is in manual RUN Indicator ...

Page 6: ...ibration level The factory default for the password code is 1111 Protection of the access code The protection system built into the controller blocks for 10 minutes the access to protected parameters after 5 consecutive frustrated attempts of guessing the correct password Master Password The Master Password is intended for allowing the user to define a new password in the event of it being forgott...

Page 7: ...s must be activated during a ramp and soak program segment Alarm function depends on rS setting Table 3 Lp Link Program Link Program number of the next profile program to be linked following the current program 0 do not link to any other program 1 a 7 number of the program to be linked to ALARM CYCLE Fva1 Fva2 Fva3 Fva4 Function Alarm Functions of Alarms Defines the functions for the alarms among ...

Page 8: ...ed at I O 6 relay 6 Refer to Table 2 for functions f fnc F Key Function Selects the I O function assigned to the front panel key Available functions are off Key not used rvn Start Stop the controller RUN function rSP Select remote setpoint kprg Execute Hold ramp and soak profile PR1 Enable Disable ramp and soak profile 1 aven Enable The Key Enable or disable operation of the key Yes key enabled NO...

Page 9: ...f the profile If this deviation is exceeded the program will be interrupted until the deviation falls to within the tolerance band Programming 0 zero at this prompt disables the tolerance and the profile execution will not to be halted even if PV does not follow SV time priority as opposed to SV priority The ramp and soak event function is used to activate alarms at any segment of program 1 This a...

Page 10: ...t provided by the controller ANALOG OUTPUT CALIBRATION 1 Select type 11 or 12 at the I O5 prompt 2 Connect a current meter at the analog output 3 Disable the auto tune and soft start functions 4 Set the output low limit ovLL to 0 0 and the output high limit ovkL to 100 0 5 Select the manual mode at the avto prompt 6 Enable the output at the rvn prompt 7 At the operation cycle set the MV to 0 0 8 A...

Page 11: ...S PC UL94 V 0 ELECTROMAGNETIC COMPATIBILITY EN 61326 1 1997 and EN61326 1 A1 1998 EMISSION CISPR11 EN55011 IMMUNITY EN61000 4 2 EN61000 4 3 EN61000 4 4 EN61000 4 5 EN61000 4 6 EN61000 4 8 and EN61000 4 11 SECURITY EN61010 1 1993 and EN61010 1 A2 1995 UL file E300526 USB INTERFACE 2 0 CDC class virtual communications port MODBUS RTU protocol SPECIFIC CONNECTIONS FOR TYPE FORK TERMINALS OF 6 3 mm PR...

Reviews: