Novus N2000 Instruction Manual Download Page 2

Controller N2000  

NOVUS AUTOMATION 

2/11 

The function to be used in each channel of I/O is defined by the user 

in accordance with the options shown in the Table 2

I/O FUNCTION 

I/O TYPE 

CODE 

No function 

OFF 

Alarm 1 Output 

Output 

A1 

Alarm 2 Output 

Output 

A2 

Alarm 3 Output 

Output 

A3 

Alarm 4 Output 

Output 

A4 

LDB Output - Loop break detection 

Output 

Lbd 

Control Output (Relay or Digital Pulse) 

Output 

CTRL 

Automatic/Man mode change 

Digital Input 

mAN 

Run/Stop mode change 

Digital Input 

RVN 

Selected Remote SP 

Digital Input 

RSP 

Freezes program execution 

Digital Input 

KPRG 

Program 1 selection 

Digital Input 

PR 1 

0 to 20 mA analog control output 

Analog Output 

(.0.20 

4 to 20 mA analog control output 

Analog Output 

(.4.20 

0 to 20 mA PV retransmission 

Analog Output 

P.0.20 

4 to 20 mA PV retransmission 

Analog Output 

P.4.20 

0 to 20 mA SP retransmission 

Analog Output 

S.0.20 

4 to 20 mA SP retransmission 

Analog Output 

S.4.20 

Table 2 - I/O channel functions 

The description for the functions follows: 

 

OFF

 - No function.  

The I/O channel programmed with code 0 will not be used by the 

controller. It is available to be used by serial communication as digital 

output. 

 

A1, A2, A3, A4

 - Alarm output. 

 Available for all I/O channels. The selected channel can be used as 

output to Alarms 1 to 4.  

 

Lbd

 – Loop Break Detector function.  

Assigns the output of the Loop Break Detector alarm to an I/O 

channel. Available to all I/O channels. 

 

CTRL

 - PWM control output. 

Defines the channel to be used as control output (relay or digital 

pulse). Available for all the channels. The digital pulse is available  

on (when available) I/O5 and I/O6. 

 

mAN

 - Digital input with Auto/Manual function. 

Defines the channel as Digital Input with the function of switching the 

control mode between Automatic  and  Manual. Available  for  I/O5, 

I/O6 and key  . 

Closed:     Manual control /no 

Opened:    Automatic control /YES 

 

RVN

 - Digital input - Standard for I/O5, I/O6 and    key. Start/Stop 

input (“

rvn

”: YES / no). 

Closed:    outputs enabled/ YES 

Opened:   outputs disabled/ no 

 

 

RSP

 - Digital input - Standard for I/O5, I/O6 and   key. 

Closed:     remote SP (4-20 mA in remote SP input) 

Opened:    main SP (internal programmed SV) 

 

KPRG

 - Digital input - Standard for I/O5, I/O6 and    key. 

Opened: enables R&S program 

Closed: holds R&S program (the program resumes when the contact 

is opened again) 

Closed Contact:    Enables execution of the program 

Opened Contact:   Interrupts execution of the program 

Note: Even when the execution of the program is interrupted, 

the control output remains active and controlling the process at 

the point (Setpoint) of interruption. The program will resume its 

normal execution starting from this same point when the digital 

input is closed. 

 

PR 1

 - Digital input - Standard for I/O5, I/O6 and   key. Selects 

R&S program 1. Used to alternate between the main Setpoint and 

a second Setpoint defined by the R&S program 1. 

Closed:  selects program 1 

Opened: uses main Setpoint 

 

(.0.20

 / 

(.4.20

 - 0-20 mA and 4-20 mA Control Output.  

Available for I/O 5 only, defines the channel as a 0-20 mA and 4-20 mA 

control output. 

 

P.0.20

 / 

P.4.20

- 0-20 mA and 4-20 mA PV retransmissions. 

Available for I/O 5 only, configures the channel to retransmit the PV 

measurement in 0-20 mA and 4-20 mA. 

 

S.0.20

  / 

s.4.20

-  0-20 mA and  4-20 mA SP (Setpoint) 

retransmissions. 

Available for I/O 5 only, configures the channel to retransmit the 

values of SP in 0-20 mA and 4-20 mA. 

 

ALARMS FUNCTIONS  
The controller has 4 independent alarms. They can be programmed 

to operate with eight different functions, represented in Table 3

 

off

 – Alarms turned 

off

 

ierr

 – Sensor break alarm 

It is activated whenever the input sensor is broken or disconnected. 

 

rs

 – Ramp & soak program event alarm 

This alarm is activated by the Ramp & Soak program (refer to the 

PROGRAMS OF RAMP AND SOAK section on how to set the event 

alarm). 

 

lo

 – Alarm of Absolute Minimum Value 

It is activated when the measured value is below the value defined in 

the alarm Setpoint. 

 

ki

 – Alarm of Absolute Maximum Value 

It is activated when the measured value is above the value defined in 

the alarm Setpoint. 

 

dif

 – Alarm of Differential Value 

In this function, the parameters “

SPA1

”, “

SPA2

”,”

SPA3

” and “

SPA4

” 

represent the PV deviation as compared to the main SP. 
Using the Alarm 1 as example: for Positive SPA1 values, the 

differential alarm will be triggered when the PV value is out of the 

range defined in: 

(SP –SPA1) to (SP + SPA1) 

For a negative SPA1 value, the differential alarm will be triggered 

when the PV value is within the range defined above 

 

difl

 – Alarm of Minimum Differential Value 

It is activated when the PV value is below the value defined in: 

(SP –SPA1) 

Using the Alarm 1 as example. 

 

difk

 – Alarm of Maximum Differential Value 

It is activated when the PV value is above the value defined in: 

(SP + SPA1) 

Using the Alarm 1 as example. 

 

Summary of Contents for N2000

Page 1: ...ing of PID parameters Automatic Manual function with bumpless transfer Four modes of independents alarms with functions of minimum maximum differential deviation open sensor and event Timer functions that can be associated to the alarms Retransmission of PV or SP in 0 20 mA or 4 20 mA Input for remote setpoint Digital input with 5 functions Programmable soft start 7 setpoint profile programs with ...

Page 2: ...s opened again Closed Contact Enables execution of the program Opened Contact Interrupts execution of the program Note Even when the execution of the program is interrupted the control output remains active and controlling the process at the point Setpoint of interruption The program will resume its normal execution starting from this same point when the digital input is closed PR 1 Digital input ...

Page 3: ...ain a voltage output by installing a resistor shunt 550 Ω max to the current output terminals terminals 7 and 8 The actual resistor value depends on the desired output voltage span SOFT START The soft start feature avoids abrupt variations in the power delivered to the load regardless of the system power demand This is accomplished by defining a limiting ramp for the control output The output is a...

Page 4: ...tely disconnected from the input output signals Using the USB in any other type of connection is possible but requires a careful analysis by the person responsible for installing it When MONITORING for long periods of time and with connected inputs and outputs we recommend using the RS485 interface which is available or optional in most of our products INSTALLATION CONNECTIONS The controller must ...

Page 5: ...alue of PV Process Variable When in programming mode shows the parameter name Parameter display SV shows the SV Setpoint Variable value and the value of other parameters of the controller COM Indicator Flashes when communication messages are sent by the controller TUNE Indicator Lights during the execution of PID automatic tuning MAN Indicator Lights when the controller is in manual RUN Indicator ...

Page 6: ...ibration level The factory default for the password code is 1111 Protection of the access code The protection system built into the controller blocks for 10 minutes the access to protected parameters after 5 consecutive frustrated attempts of guessing the correct password Master Password The Master Password is intended for allowing the user to define a new password in the event of it being forgott...

Page 7: ...s must be activated during a ramp and soak program segment Alarm function depends on rS setting Table 3 Lp Link Program Link Program number of the next profile program to be linked following the current program 0 do not link to any other program 1 a 7 number of the program to be linked to ALARM CYCLE Fva1 Fva2 Fva3 Fva4 Function Alarm Functions of Alarms Defines the functions for the alarms among ...

Page 8: ...ed at I O 6 relay 6 Refer to Table 2 for functions f fnc F Key Function Selects the I O function assigned to the front panel key Available functions are off Key not used rvn Start Stop the controller RUN function rSP Select remote setpoint kprg Execute Hold ramp and soak profile PR1 Enable Disable ramp and soak profile 1 aven Enable The Key Enable or disable operation of the key Yes key enabled NO...

Page 9: ...f the profile If this deviation is exceeded the program will be interrupted until the deviation falls to within the tolerance band Programming 0 zero at this prompt disables the tolerance and the profile execution will not to be halted even if PV does not follow SV time priority as opposed to SV priority The ramp and soak event function is used to activate alarms at any segment of program 1 This a...

Page 10: ...t provided by the controller ANALOG OUTPUT CALIBRATION 1 Select type 11 or 12 at the I O5 prompt 2 Connect a current meter at the analog output 3 Disable the auto tune and soft start functions 4 Set the output low limit ovLL to 0 0 and the output high limit ovkL to 100 0 5 Select the manual mode at the avto prompt 6 Enable the output at the rvn prompt 7 At the operation cycle set the MV to 0 0 8 A...

Page 11: ...S PC UL94 V 0 ELECTROMAGNETIC COMPATIBILITY EN 61326 1 1997 and EN61326 1 A1 1998 EMISSION CISPR11 EN55011 IMMUNITY EN61000 4 2 EN61000 4 3 EN61000 4 4 EN61000 4 5 EN61000 4 6 EN61000 4 8 and EN61000 4 11 SECURITY EN61010 1 1993 and EN61010 1 A2 1995 UL file E300526 USB INTERFACE 2 0 CDC class virtual communications port MODBUS RTU protocol SPECIFIC CONNECTIONS FOR TYPE FORK TERMINALS OF 6 3 mm PR...

Reviews: