Novus N2000 Instruction Manual Download Page 1

NOVUS AUTOMATION 

1/11 

 

 

Controller N2000 

UNIVERSAL PROCESS CONTROLLER – INSTRUCTIONS MANUAL – V3.0x E 

SAFETY ALERTS 

The symbols below are used on the equipment and throughout this 

document to draw the user’s attention to important operational and 

safety information. 

 

 

CAUTION or WARNING: 

Read complete instructions prior to 

installation and operation of the unit. 

CAUTION or WARNING: 

Electrical Shock Hazard 

All safety related instructions that appear in the manual must be 

observed to ensure personal safety and to prevent damage to either 

the instrument or the system. If the instrument is used in a manner 

not specified by the manufacturer, the protection provided by the 

equipment may be impaired. 

PRESENTATION 

The N2000 is an extraordinarily versatile process controller. It holds 

in one single instrument all the main features needed for the vast 

majority of industrial processes. It accepts in a single model virtually 

all the sensors and signals used in the industry and provides the 

main output types required for the operation of diverse processes.  
The configuration can be performed directly on the controller or through 

the USB interface. The NConfig  software (free) is the configuration 

management tool. Connected to the USB of a Windows computer, the 

controller is recognized as a serial communications port (COM) running 

with a Modbus RTU protocol. 
Through the USB interface, even if disconnected from the power 

supply, the configuration performed in a piece of equipment can be can 

be saved in a file and repeated in other pieces of equipment that 

require the same configuration.  
It is important that the users read carefully this manual before using the 

controller.  Verify if the release of this manual matches the instrument 

version (the firmware version is shown when the controller is 

energized). 

 

Multi-sensor universal input (sensors and standard signals); 

 

Relay, 4-20 mA and logic pulse control outputs all available in the 

standard model; 

 

Self-tuning of PID parameters; 

 

Automatic / Manual function with “bumpless”  transfer; 

 

Four modes of independents alarms, with functions of minimum, 

maximum, differential (deviation), open sensor and event; 

 

Timer functions that can be associated to the alarms; 

 

Retransmission of PV or SP in 0-20 mA or 4-20 mA; 

 

Input for remote setpoint; 

 

Digital input with 5 functions; 

 

Programmable soft-start

 

7 setpoint profile programs with 7 segments each, with the ability 

to be linked together for a total of 49 segments; 

 

RS-485 Serial communication, MODBUS RTU protocol; 

 

Password for parameters protection; 

 

Universal power supply. 

CONFIGURATION 

INPUT TYPE SELECTION 
Select the input type (in parameter “

tYPE

”) from Table 1 below. 

TYPE 

CODE 

CHARACTERISTICS 

Tc j 

 Range: -110 a 950 ºC (-166 a 1742 ºF) 

Tc k 

 Range: -150 a 1370 ºC (-238 a 2498 ºF) 

Tc t 

 Range: -160 a 400 ºC (-256 a 752 ºF) 

Tc n 

 Range: -270 a 1300 ºC (-454 a 2372 ºF) 

Tc r 

 Range: -50 a 1760 ºC (-58 a 3200 ºF) 

Tc s 

 Range: -50 a 1760 ºC (-58 a 3200 ºF) 

Tc b 

 Range: 400 a 1800 ºC (752 a 3272 ºF) 

Tc e 

 Range: -90 a 730 ºC (-130 a 1346 ºF) 

Pt100 

Pt 

 Range: -200 a 850 ºC (-328 a 1562 ºF) 

0–50 mV 

L.0.50 

 Linear Signals 
 Programmable indication from-1999 to 9999 

4-20 mA 

L.4.20 

0-5 Vdc 

L0.5 

0-10 Vdc 

L0.10 

4-20 mA  

Sqrt 

 4-20 mA input with Square Root extraction.  
 Programmable indication from-1999 to 9999 

4-20 mA 

NO 

LINEAR 

ln j 

 Non Linear Analog Signals  
 Indication range depends on the selected sensor 

Ln k 

ln t 

ln n 

ln r 

ln s 

ln b 

ln E 

Ln.Pt 

Table 1 - Input Types 

Note: All input types are factory calibrated. 

OUTPUTS, ALARMS AND DIGITAL INPUTS CONFIGURATION 
The controller input/output channels can assume multiple functions, 

depending on configuration: control output, alarm output, digital 

output, digital input, and PV or  SV analog retransmission. These 

channels are identified as I/O1, I/O2, I/O3, I/O4, I/O 5 and I/O6. 
The basic controller model comes loaded with: 
I/O1 and I/O2 - SPDT relay output;  

I/O3 and I/O4 - SPST relay output; 

I/O5 - analog output (0-20 or 4-20 mA), pulse 10 V max, digital I/O; 

I/O6 - Digital Input.  
Note: When a function is selected to operate through digital 

input, the controller does not respond to the equivalent function 

command given in the frontal keypad. 

Summary of Contents for N2000

Page 1: ...ing of PID parameters Automatic Manual function with bumpless transfer Four modes of independents alarms with functions of minimum maximum differential deviation open sensor and event Timer functions that can be associated to the alarms Retransmission of PV or SP in 0 20 mA or 4 20 mA Input for remote setpoint Digital input with 5 functions Programmable soft start 7 setpoint profile programs with ...

Page 2: ...s opened again Closed Contact Enables execution of the program Opened Contact Interrupts execution of the program Note Even when the execution of the program is interrupted the control output remains active and controlling the process at the point Setpoint of interruption The program will resume its normal execution starting from this same point when the digital input is closed PR 1 Digital input ...

Page 3: ...ain a voltage output by installing a resistor shunt 550 Ω max to the current output terminals terminals 7 and 8 The actual resistor value depends on the desired output voltage span SOFT START The soft start feature avoids abrupt variations in the power delivered to the load regardless of the system power demand This is accomplished by defining a limiting ramp for the control output The output is a...

Page 4: ...tely disconnected from the input output signals Using the USB in any other type of connection is possible but requires a careful analysis by the person responsible for installing it When MONITORING for long periods of time and with connected inputs and outputs we recommend using the RS485 interface which is available or optional in most of our products INSTALLATION CONNECTIONS The controller must ...

Page 5: ...alue of PV Process Variable When in programming mode shows the parameter name Parameter display SV shows the SV Setpoint Variable value and the value of other parameters of the controller COM Indicator Flashes when communication messages are sent by the controller TUNE Indicator Lights during the execution of PID automatic tuning MAN Indicator Lights when the controller is in manual RUN Indicator ...

Page 6: ...ibration level The factory default for the password code is 1111 Protection of the access code The protection system built into the controller blocks for 10 minutes the access to protected parameters after 5 consecutive frustrated attempts of guessing the correct password Master Password The Master Password is intended for allowing the user to define a new password in the event of it being forgott...

Page 7: ...s must be activated during a ramp and soak program segment Alarm function depends on rS setting Table 3 Lp Link Program Link Program number of the next profile program to be linked following the current program 0 do not link to any other program 1 a 7 number of the program to be linked to ALARM CYCLE Fva1 Fva2 Fva3 Fva4 Function Alarm Functions of Alarms Defines the functions for the alarms among ...

Page 8: ...ed at I O 6 relay 6 Refer to Table 2 for functions f fnc F Key Function Selects the I O function assigned to the front panel key Available functions are off Key not used rvn Start Stop the controller RUN function rSP Select remote setpoint kprg Execute Hold ramp and soak profile PR1 Enable Disable ramp and soak profile 1 aven Enable The Key Enable or disable operation of the key Yes key enabled NO...

Page 9: ...f the profile If this deviation is exceeded the program will be interrupted until the deviation falls to within the tolerance band Programming 0 zero at this prompt disables the tolerance and the profile execution will not to be halted even if PV does not follow SV time priority as opposed to SV priority The ramp and soak event function is used to activate alarms at any segment of program 1 This a...

Page 10: ...t provided by the controller ANALOG OUTPUT CALIBRATION 1 Select type 11 or 12 at the I O5 prompt 2 Connect a current meter at the analog output 3 Disable the auto tune and soft start functions 4 Set the output low limit ovLL to 0 0 and the output high limit ovkL to 100 0 5 Select the manual mode at the avto prompt 6 Enable the output at the rvn prompt 7 At the operation cycle set the MV to 0 0 8 A...

Page 11: ...S PC UL94 V 0 ELECTROMAGNETIC COMPATIBILITY EN 61326 1 1997 and EN61326 1 A1 1998 EMISSION CISPR11 EN55011 IMMUNITY EN61000 4 2 EN61000 4 3 EN61000 4 4 EN61000 4 5 EN61000 4 6 EN61000 4 8 and EN61000 4 11 SECURITY EN61010 1 1993 and EN61010 1 A2 1995 UL file E300526 USB INTERFACE 2 0 CDC class virtual communications port MODBUS RTU protocol SPECIFIC CONNECTIONS FOR TYPE FORK TERMINALS OF 6 3 mm PR...