Novus N1500FT Instruction Manual Download Page 7

N1500FT Flow Indicator 

NOVUS AUTOMATION 

7/8 

MESSAGE 

PROBLEM DESCRIPTION 

VVVVV 

Value reading is above limits allowed for this 

sensor or signal.   

nnnnn 

Value reading is below limits allowed for this 

sensor or signal.   

------ 

Open input. No sensor or signal. 

SPECIAL RECOMMENDATIONS 
Should your indicator be repaired, special care must be taken with 

handling. The device must be removed from the case and immediately 

placed in an antistatic wrap, protected from extreme heat and humidity. 

CALIBRATION 

Both analog input and output are factory calibrated, and recalibration 

should not be performed by inexperienced operators. If recalibration 

of a given range is necessary, proceed as follows. 
INPUT CALIBRATION 
1.

 

Set input type to be calibrated to 4-20 mA; 

2.

 

Program 

inll

  (lower limit) and 

inkl

  (higher limit) indication 

parameters to maximum and minimum values of input type; 

3.

 

Apply to entry a signal corresponding to a known indication and 

close to its lower limit; 

4.

 

Enter calibration cycle with correct password; 

5.

 

Access 

inl(

  parameter. With 

  and 

 

keys, have 

parameter display show applied value. Then Press 

6.

 

Apply to entry a signal corresponding to a known indication and 

close to its higher limit; 

7.

 

Access 

ink(

  parameter. With 

  and 

 

keys, have 

parameter display show applied value; 

8.

 

Press 

 or 

 to exit screen and activate calibration. 

OUTPUT CALIBRATION 
1.

 

Mount a milliammeter in the analog control output; 

2.

 

Enter calibration cycle with correct password; 

3.

 

Select 

oUL(

 parameter. Use 

 and 

 keys so that the 

device recognizes the process of calibration of current output.  

4.

 

Read current in the milliammeter and enter it in the 

oUL(

 

parameter using 

 and 

 keys. Then press 

5.

 

In parameter 

oUx(

, use 

 and 

 keys so that the device 

recognizes the process of calibration of current output; 

6.

 

Read current in the milliammeter and enter it in the 

oUx(

 

parameter using 

 and 

 keys; 

7.

 

Press 

 or 

 to exit screen and activate calibration. 

SERIAL COMMUNICATION 

The indicator may be optionally supplied with a RS485 asynchronous 

serial communication interface for communicating with a supervisor 

computer (master). The indicator always operates as slave.  
Communication is always initiated by the master, which sends a 

request to the slave address with which it wants to communicate. The 

addressed slave takes control and sends a response to the master.  
The indicator takes broadcast type commands (addresses to all 

network instruments). For this type of command, the indicator does 

not send any reply or acknowledgement. 

FEATURES 
Signals compatible with RS485 standard. MODBUS (RTU) Protocol. 

2-wire connection between 1 master and up to 31 indicators (it is 

possible to address up to 247 units) in bus topology. 
Communication signals are electrically isolated from the rest of the 

indicator. 

 

Maximum connection distance: 1000 meters. 

 

Selectable speed; 8 bits of data; 1 stop bit; selectable parity (no 

parity, even or odd). 

 

Start time of response transmission: 100 ms maximum after 

receiving the command. 

ELECTRICAL CONNECTIONS: RS485 INTERFACE 
RS485 signals are: 

D1 

D+ 

Bi-directional data line 

Terminal 25 

D0 

 

D- 

Reverse bi-directional data 

line 

Terminal 26 

Optional connection that 

improves communication 

performance. 

Terminal 27 

GND 

CONFIGURATION OF SERIAL COMMUNICATION PARAMETERS 
Two parameters must be configured for serial use: 

Baud

:   Communication speed. 

Prty

:   Communication parity. 

Addr

:   Communication address of indicator.  

REDUCED REGISTERS TABLE FOR 

SERIAL COMMUNICATION 

Communication Protocol 
Slave MODBUS RTU protocol supported. All configurable 

parameters of the indicator may be read and/or written through serial 

communication. Writing on registers in broadcast mode using the 

address 0 is also allowed. 
The following Modbus commands are available: 
 

03 - Read Holding Register   

06 - Preset Single Register 

 

05 - Force Single Coil  

 

 

16 - Preset Multiple Register 

Holding Registers Table 
The following are the most commonly used registers. For further 

information, refer to the Table of Registers for Serial 

Communication  available for download on the flow indicator 

webpage at 

www.novusautomation.com

The registers below are read-only. The ones that are available in a 

floating point format require two registers for being 32-bit values. 

Address  Parameter 

Register Description 

0000  

and  

0001 

Instantaneou

s flow rate 

Instantaneous flow value in floating 

point (IEEE-754). 

0002  

and  

0003 

Total flow 

rate 

Flow totalization value in floating point 

(IEEE-754). 

0004  

and  

0005 

Non-

resettable 

total flow rate 

Grand total flow value in floating point 

(IEEE-754). 

0013  

to  

0016 

Total flow 

rate 

Flow totalization value in integer format 

(with signal) of 64 bits. The most 

significant part is in the first register. 

0017  

to  

0020 

Non-

resettable 

total flow rate 

Grand total flow value in integer format 

(with signal) of 64 bits. The most 

significant part is in the first register. 

Summary of Contents for N1500FT

Page 1: ...ays With pulse flow input totalization will continue even if the input rate is below the minimum rate required Instantaneous flow rate indication will be zero whenever there is a time lapse of 10 seco...

Page 2: ...maximum values of instantaneous flow rate These values can be viewed on the first screen of the main cycle by pushing and respectively The key can be set to zero maximum and minimum values FEEDER The...

Page 3: ...this key for more than 10 seconds inside the main cycle the 8 digit serial number will be shown on both displays FUNCTION OPERATION METHOD Go to the next cycle Press for more than 3 seconds Go to nex...

Page 4: ...t from off and 1 Error BLA3 Block Alarm 3 A3t1 Alarm 3 Timer 1 Visible only if Fva3 is different from off A3t2 Alarm 3 Timer 2 Fva4 Function Alarm 4 Selection of Function Alarm 4 off 1 Error Lo x1 and...

Page 5: ...ion applies quadratic function on the input signal within the limits programmed in inLL and inkL Table 7 Input setup cycle keys 1 Special application of alarm outputs When an alarm is set as Feeder an...

Page 6: ...dard current close to 20 mA will be applied Measure current in mA and enter it on this screen rstr Restore Restores factory calibration Pa x Password Change Changes user password Prot Protection Prote...

Page 7: ...ster The indicator takes broadcast type commands addresses to all network instruments For this type of command the indicator does not send any reply or acknowledgement FEATURES Signals compatible with...

Page 8: ...Communication Nothing shown basic version with no serial communication 485 version with RS485 serial Modbus protocol D Power Supply Nothing shown basic version power supply of 100 to 240 Vac 24V vers...

Reviews: