Novus N1500FT Instruction Manual Download Page 1

NOVUS AUTOMATION 

1/8 

 

 

N1500FT Indicator 

FLOW RATE INDICATOR – INSTRUCTIONS MANUAL – V1.0x A 

SAFETY ALERTS 

The symbols below are used on the equipment and throughout this 

document to draw the user’s attention to important operational and 

safety information. 

 

 

CAUTION: 

Read this manual carefully prior to 

installation and operation of the 

unit. 

CAUTION OR DANGER: 

Electric shock hazard 

All safety related instructions that appear in the manual must be 

observed to ensure personal safety and to prevent damage to either 

the instrument or the system.  If the device is used in a manner not 

specified in this manual, its safety features may be impaired. 

INTRODUCTION 

This flow rate indicator provides indication, totalization, 

retransmission, alarm and RS485 communication features (optional 

RTU Modbus slave).  It reads most flow signals available in the 

market, such as pulse, magnetic pickup and 4-20 mA.  The pulse 

input allows connecting sensors with outputs such as reed-switch, 

NPN, PNP and tension. Both for pulse input and 4-20 mA input, unit 

is selectable and a scale factor is set to turn the input signal into the 

unit of choice. It provides an isolated pulse output for totalized flow 

retransmission and a 4-20 mA output for immediate flow 

retransmission. Alarms are set off through 2 to 4 relays, depending 

on the equipment model.  
AC models provide a 24 Vdc / 50 mA output. 

INPUTS 

The flow rate indicator allows for two basic input types: 

 

Instantaneous flow input through a 4-20 mA signal. In this case, 

flow totalization is obtained by integrating instantaneous flow rate. 

 

Totalized flow input through a pulse signal. In this case, 

instantaneous flow rate is obtained by deriving totalized flow rate. 

Pulse signals may come from sensors/transmitters with NPN, PNP, dry 

contact  (reed switch) and tension signal output, or even magnetic 

pickup outputs. 
When the input is set to 4-20 mA, you should establish on screens 

InLL

 and 

InKL

 which flow values are equivalent to 4 and 20 mA. 

When the 4-20 mA input is not used as flow input, it may be used 

alternatively as auxiliary input. This way it is possible to measure the 

pressure of a pipeline, for instance. 
The pulse flow input may be scaled, both for instantaneous and 

totalized flow rates (independently), through ‘k’ multiplication factors: 

k.1nst

 and 

k.tot

.

 

Both flow time base and unit must be defined on screen 

Un1t 1

To do so, there are six characters, the first five of which are used to 

set the unit and the last one (to the right) is used to set the time base 

on which the flow rate is measured. Available time bases are ‘s’ 

(seconds), ‘m’ (minutes), ‘h’ (hours) and ‘d’ (days). 

With pulse flow input, totalization will continue even if the input rate is 

below the minimum rate required. Instantaneous flow rate indication 

will be zero whenever there is a time lapse of 10 seconds without 

input variation. In this case, whenever there is a totalization increase 

(more input pulses), the instantaneous flow value will be shown for 

the nest 10 seconds. 

CUSTOMIZED LINEARIZATION 
When the flow rate is read through a 4-20 mA input, it is possible to 

apply a customized linearization composed of 30 input points and 30 

output points. Whenever the reading falls between two input points, it 

will be normalized to the range defined by the respective points in the 

output range. 
The search for framing the value read is done while the list of input 

points is incrementally declared. The search is terminated if the next 

point in the list is lower than the current one. If the input value is 

lower than the first value in the list of input points, linearization will 

return the first output value. Similarly, if the input value is greater 

than the highest value in the list of input points, linearization will 

return the highest value in the output list. 
IMPORTANT: At least two pairs of input-output points are required 

for adequate customized linearization. 

RETRANSMISSION 

Flow rate retransmission can be done via 4-20 mA output and pulse 

output. 
The 4-20 mA output may be used regardless of the type of flow input. 

To use it, just set the retransmission range to 

RTLL

  and 

RTKL

associating the flow rates to 4 and 20 mA. 
In the case of retransmission  via pulse output, one must choose 

between volumetric pulse output and frequency pulse output. The 

former may be used regardless of the type of input, while the latter is 

available only for pulse inputs. 
In the volumetric mode, a pulse of configurable length is generated 

every time the totalizer accumulates a preset volume. For example, 

for a period of 1 second and volume of 10 liters, a 1-second pulse will 

be generated for every 10 liters totalized. 
In the frequency mode, the pulse output will divide the input 

frequency by a programmable constant whose value is equal to or 

higher than 2. 
IMPORTANT: Maximum output frequency has hardware limitation. 

See Specifications. 

ALARMS 

The indicator’s basic version has 2 alarm outputs, with the option of 

up to 4 alarms. Whenever an alarm is on, a corresponding light 

signal will be displayed on the front panel. 

ALARM FUNCTIONS 
The alarms can be programmed to operate with four different 

functions, described below. They may also be turned 

off

Alarms use only the instantaneous flow rate reading. Totalization 

readings cannot be used as input for alarms. The auxiliary 4-20 mA 

input (when it is not being used for flow rate measurement) may be 

used only as input for the open sensor alarm. 

Summary of Contents for N1500FT

Page 1: ...ays With pulse flow input totalization will continue even if the input rate is below the minimum rate required Instantaneous flow rate indication will be zero whenever there is a time lapse of 10 seco...

Page 2: ...maximum values of instantaneous flow rate These values can be viewed on the first screen of the main cycle by pushing and respectively The key can be set to zero maximum and minimum values FEEDER The...

Page 3: ...this key for more than 10 seconds inside the main cycle the 8 digit serial number will be shown on both displays FUNCTION OPERATION METHOD Go to the next cycle Press for more than 3 seconds Go to nex...

Page 4: ...t from off and 1 Error BLA3 Block Alarm 3 A3t1 Alarm 3 Timer 1 Visible only if Fva3 is different from off A3t2 Alarm 3 Timer 2 Fva4 Function Alarm 4 Selection of Function Alarm 4 off 1 Error Lo x1 and...

Page 5: ...ion applies quadratic function on the input signal within the limits programmed in inLL and inkL Table 7 Input setup cycle keys 1 Special application of alarm outputs When an alarm is set as Feeder an...

Page 6: ...dard current close to 20 mA will be applied Measure current in mA and enter it on this screen rstr Restore Restores factory calibration Pa x Password Change Changes user password Prot Protection Prote...

Page 7: ...ster The indicator takes broadcast type commands addresses to all network instruments For this type of command the indicator does not send any reply or acknowledgement FEATURES Signals compatible with...

Page 8: ...Communication Nothing shown basic version with no serial communication 485 version with RS485 serial Modbus protocol D Power Supply Nothing shown basic version power supply of 100 to 240 Vac 24V vers...

Reviews: