The  program  tolerance  “

Ptol

Ptol

Ptol

Ptol

  defines  the  maximum  deviation 

between PV and SV for the execution of the profile. If this deviation is 
exceeded, the program will be interrupted until the deviation falls to 
within the tolerance band. 

Programming 0 (zero) at this prompt disables the tolerance and the 
profile execution will not to be halted even if PV does not follow SV 
(time priority as opposed to SV priority). 

 

SV 

time 

T1 

T2 

T3 

T4 

T5 

T1 

T2 

T3 

T4 

SP0 

SP1 

SP2 

SP3 

SP4 

SP5 / SP0 

SP1  SP2 

SP3 

SP4 

Program 1 

Program 2 

 

Figure 3

 - Example of two linked programs 

The ramp and soak event function is used to activate alarms at any 
segment of program 1. This applies only to program 1. 

To  enable  this  event  function  the  alarms  to  be  activated  must  be 
selected for 

rS

rS

rS

rS

 

function and are programmed at the

 

PE 0

PE 0

PE 0

PE 0

  to 

PE 5

PE 5

PE 5

PE 5

  

prompts.  The  number  to  be  programmed  at  the  prompt  defines  the 
alarms to be activated (

Table 5

). 

Code 

Alarm 1  Alarm 2  Alarm 3  Alarm 4 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

10 

 

 

11 

 

12 

 

 

13 

 

14 

 

15 

Table 5

 - Event codes for ramp and soak 

To configure and execute a ramp and soak program: 

  Program the tolerance value, SV, time and event. 

  If  any  event  alarm  is  required  program  the  ramp  and  soak  event 

function. 

  Set the control mode to automatic. 

  Select    ramp  and  soak  program  to  be  executed  at  prompt   

Prn 

Prn 

Prn 

Prn 

 

(0 to 4)  

  Start control at the run prompt 

rvn

rvn

rvn

rvn

  by selecting 

YES

Before executing the program the controller waits for PV to reach the 
first set point 

SP0

SP0

SP0

SP0

 

if

 

PtoL

PtoL

PtoL

PtoL

 

is

 

different than zero.  

Should  any  power  failure  occur  the  controller  resumes  at  the 
beginning of the segment it was previously. 

 

 

 

 

 

 

 

 

10

 

AUTO TUNE 

During  auto  tune  the  process  is  controlled  in  ON/OFF  mode  at  the 
programmed  SetPoint  (SV).  Depending  on  the  process 
characteristics large oscillations above and below SV may occur and 
auto tuning may take several minutes to be concluded. 

The recommended procedure is as follows: 

  Disable the control output at the

 

rvn

rvn

rvn

rvn

 

prompt by selecting 

NO

  Select auto mode operation at the 

Avto

Avto

Avto

Avto

 prompt by selecting 

YES

  Disable  the  ramp  and  soak  function  (select 

NO

)  and  program  a 

new SV value other than the present PV (close to the desired set 
point). 

  Enable auto tuning at the 

Atvn

Atvn

Atvn

Atvn

 prompt by selecting 

YES. 

  Enable the control output at the

 

rvn

rvn

rvn

rvn

 prompt by selecting 

YES

During the auto tune procedure the soft-start function will not operate 
and large oscillations will be induced around the setpoint. Make sure 
the  process  can  accept  these  oscillations  and  fast  control  output 
changes. 

If auto tuning results are not satisfactory refer to 

Table 6

 for manual 

fine tuning procedure. 

PARAMETER 

RESPONSE 

SOLUTION 

Slow Response 

Decrease 

Proportional 

Band 

Large Oscillation 

Increase 

Slow Response 

Incre ase 

Integral Rate 

Large Oscillation 

Decrease 

Slow Response or Instability 

Decrease 

Derivative Time 

Large Oscillation 

Increase 

Table 6

 - Suggestions for manual tuning of PID parameters 

11

 

SERIAL COMMUNICATION  

An optional RS485 serial communication interface is available which 
allows up to 247 controllers in a network to communicate to a master 
device. 

RS485 Interface 

 

Compatible signals with RS485 standard; 

 

Two-wire connection from master to up to 247 slave  controllers 
in a multidrop bus; 

 

Maximum communication distance: 1000 meters; 

General Characteristics 

 

Optically isolated serial interface 

 

Programmable Baud rate: 1200, 2400, 4800, 9600 or 19200 bps. 

 

Data Bits: 8 

 

Parity: None 

 

Stop Bits: 1 

 

Summary of Contents for N1100HC

Page 1: ...e resistance compensation Analog output 0 20 mA or 4 20 mA 1500 levels 550 Ω max CONTROL OUTPUT Standard Version up to 3 outputs Two 3 A 250 Vac Relays 3 A 30 Vdc Isolated 0 20 mA or 4 20 mA control output or PV or SP retransmission 1500 level resolution 550 Ω max Load Logic pulse for SSR drive 0 or 20 mA Any of the above and options 1 and 2 can be selected as the main control output and the remai...

Page 2: ...60 C 32 a 3200 ºF S 5 5 5 5 range 0 to 1760 C 32 to 3200 ºF Pt100 6 6 6 6 range 199 9 to 530 0 C 328 0 to 986 0 ºF Pt100 7 7 7 7 range 200 to 530 C 328 to 986 ºF 4 20 mA 8 8 8 8 J linearization Programmable range 110 to 760 C 4 20 mA 9 9 9 9 K linearization Programmable range 150 to 1370 C 4 20 mA 10 10 10 10 T linearization Programmable range 160 to 400 C 4 20 mA 11 11 11 11 N Linearization Faixa...

Page 3: ...The 3 modes of operation are pulse delayed actuation oscillator The desired function can be achieved programming the parameters A1t1 A1t1 A1t1 A1t1 A1t2 A1t2 A1t2 A1t2 A2t1 A2t1 A2t1 A2t1 and A2t2 A2t2 A2t2 A2t2 see Table 4 The LEDs associated to the alarms will light when the alarm condition is recognized not following the actual state of the output which may be temporarily OFF because of the tem...

Page 4: ...vto avto CONTROL MODE YES indicates automatic control mode closed loop PID or ON OFF NO indicates manual control mode open loop Bumpless transfer from auto to manual mode is available If in doubt program YES PV Indication Red MV Indication Green MANIPULATED VARIABLE VALUE MV The upper display shows PV value and the lower display shows the percentage of MV applied to the control output When in manu...

Page 5: ...bla4 bla4 bla4 bla4 ALARM BLOCK 1 TO 4 This function blocks the alarm at power up when the units is first energized YES enables and NO inhibits this blocking function When enabled the alarm will not be active at power up waiting for PV Process Variable to reach a non alarm situation From this point on the alarm will be free to actuate should a new alarm situation occur xya1 xya1 xya1 xya1 ALARM 1 ...

Page 6: ...optional hardware accessories The parameters menu will show the parameters relative to the optional hardware 0 no optionals or c RS485 only 1 relay 3 I O 3 2 Digital I O 2 inputs outputs 3 Heater break protection option Rsl REMOTE SET POINT LOW CALIBRATION Sets the Remote Set Point low calibration offset Several keystrokes at or might be necessary to increment one digit Rsx REMOTE SET POINT HIGH C...

Page 7: ...troller resumes at the beginning of the segment it was previously 10 AUTO TUNE During auto tune the process is controlled in ON OFF mode at the programmed SetPoint SV Depending on the process characteristics large oscillations above and below SV may occur and auto tuning may take several minutes to be concluded The recommended procedure is as follows Disable the control output at the rvn rvn rvn r...

Reviews: