Novus N1100HC Manual Download Page 6

N1100HC Controller 

NOVUS AUTOMATION 

6/7 

7.7

 

I/O CYCLE (INPUTS AND OUTPUTS) 

I

 

o 1

 

I/O 1 FUNCTION: Selects the I/O function to be used 
at I/O 1 (relay 1). Options 0 to 5 are possible for this 
output.  It  is  normally  used  as  option  5,  PWM  main 
control output. Refer to 

Table 2

 for functions. 

I

 

o 2

 

I/O 2 FUNCTION: Selects the I/O function to be used 
at I/O 2 (relay 2). Options 0 to 5 are available. This 
output is normally used as alarm output. See 

Table 2

 

for functions. 

I

 

o 3

 

I/O 3 FUNCTION: Selects the I/O function to be used 
at I/O 3  (option  1). I/O 3 can  be a  relay output or a 
digital  input/output.  Functions  0  to  10  are  available. 
Refer to 

Table 2

 for functions. The  presence of this 

I/O  option  is  detected  by  the  controller  and  the 
prompt  menu  will  only  be  shown  if  the  expansion 
option is available. 

I

 

o 4

 

I/O 4 FUNCTION: Selects the I/O function to be used 
at I/O 4 (option 2). I/O 4 can be a digital input/output. 
Functions 0 to 10 are available. Refer to 

Table 2

 for 

functions. The prompt menu will only be shown if the 
expansion option is present. 

I

 

o 5

 

I/O 5 FUNCTION: Selects the I/O function to be used 
at  I/O  5  (Analog  Output).  Functions  0  to  15  are 
available (See 

Table 2

). This option is normally used 

for main control output or PV analog retransmission. 

7.8

 

CALIBRATION CYCLE 

All  input  and  output  types  are  factory  calibrated.  This  cycle 
should only be accessed by experienced personnel. If in doubt 
do not press the 

 

or

 

 

keys in this cycle. 

Inl(

 

INPUT  LOW  CALIBRATION:  Sets  the  Process 
Variable  low  calibration  (offset).  Several  keystrokes 
at 

 

or

 

  might  be  necessary  to  increment  one 

digit. 

Inx(

 

INPUT  HIGH  CALIBRATION:  Sets  the  Process 
Variable span calibration (gain). 

ovll

 

OUTPUT  LOW  CALIBRATION:  Sets  the  analog 
current output low calibration (offset). 

Ovx(

 

OUTPUT  HIGH  CALIBRATION:  Sets  the  analog 
current output span calibration (gain). 

(j l

 

COLD JUNCTION OFFSET CALIBRATION: Sets the 
cold junction offset calibration. 

xtyp

 

HARDWARE  TYPE:  Configures  the  controller  to 
recognize  the  actual  installed  optional  hardware 
(accessories).  The  parameters  menu  will  show  the 
parameters relative to the optional hardware: 

 

0 - no optionals or c/ RS485 only 

 

1 - relay 3 (I/O 3) 

 

2 - Digital I/O (2 inputs/outputs) 

 

3

 - 

Heater break protection (option).

 

Rsl(

 

REMOTE SET POINT LOW CALIBRATION: Sets the 
Remote  Set  Point  low  calibration  (offset).  Several 
keystrokes  at 

  or 

  might  be  necessary  to 

increment one digit. 

Rsx(

 

REMOTE  SET  POINT  HIGH  CALIBRATION:  Sets 
the Remote Set Point span calibration (gain). 

 

 

 

8

 

CONTROL # 2 

The N1100HC incorporates a second control output with proportional 
action.  This  second  control  output  is  intended  primarily  for 
refrigeration, since the control #1 is normally used for heating.  

The Control #2 cycle of parameters is listed in 7.3 above. 

If the application requires both heat  and cool outputs, configure the 
parameters 

ACt

ACt

ACt

ACt

=

re

re

re

re

  e 

ACt2

ACt2

ACt2

ACt2

=

dir

dir

dir

dir

  and  set  the  overlap  (

OLAP

OLAP

OLAP

OLAP

accordingl, as follows. 

1) 

OLAP 

OLAP 

OLAP 

OLAP 

> 0; both outputs may be delivering power to the system. 

 

C o ntro l o utp ut 

Pro cess va ria ble 

O verlap  

P b1 

P b2 

O u tpu t 1 

O u tpu t 2 

S et Po int 

 

OLAP

OLAP

OLAP

OLAP

 < 0; for setting a dead-band. 

 

C o ntro l O u tp ut 

Pro cess V ariab le 

 D ead  b an d 

P b1 

P b2 

O u tpu t 1 

O u tpu t 2 

SetP oint 

 

OLAP

OLAP

OLAP

OLAP

 = 0; no superposition or dead-band for the outputs. 

 

C o ntro l O u tp ut 

Pro cess V ariab le 

P b1 

P b2 

O u tpu t 1 

O u tpu t 2 

S et Po int 

 

Output  2  has  independent  proportional  band  and  PWM  period,  as 
well as maximum and minimum limits for the output.  

If Pb2=0, the control #2 becomes ON-OFF, and the OLAP parameter 
becomes the Hysteresis for the control #2.  

 

C o ntro l O u tp ut 

Pro cess V ariab le 

P b1 

oLA P  

O u tpu t 1 

O u tp ut 2  

O F F  

O N  

S et Po in t 

 

9

 

RAMP AND SOAK PROFILE PROGRAM 

Seven  ramp  and  soak  profiles  with  up  to  7  segments  each  can  be 
programmed. Longer profiles of up to 49 segments can be created by 
linking 2 or more profiles. 

 

SP  

tim e 

T 1 

T2 

T 3 

T4 

T5 

S P0 

SP 1 

S P2 

S P 3 

S P4 

SP 5 

SP 6 

S P 7 

T6 

T7 

 

Figure 1

 - Example of a complete ramp and soak profile 

To  execute  a  profile  with  fewer  segments  just  program  0  (zero)  for 
the time intervals that follow the last segment to be executed. 

 

SV 

time 

T1 

T2 

T3 

SP0 

SP1 

SP2 

SP3 

T4=0 

 

Figure 2

 - Example of a profile with fewer segments. (T4 is set 0) 

Summary of Contents for N1100HC

Page 1: ...e resistance compensation Analog output 0 20 mA or 4 20 mA 1500 levels 550 Ω max CONTROL OUTPUT Standard Version up to 3 outputs Two 3 A 250 Vac Relays 3 A 30 Vdc Isolated 0 20 mA or 4 20 mA control output or PV or SP retransmission 1500 level resolution 550 Ω max Load Logic pulse for SSR drive 0 or 20 mA Any of the above and options 1 and 2 can be selected as the main control output and the remai...

Page 2: ...60 C 32 a 3200 ºF S 5 5 5 5 range 0 to 1760 C 32 to 3200 ºF Pt100 6 6 6 6 range 199 9 to 530 0 C 328 0 to 986 0 ºF Pt100 7 7 7 7 range 200 to 530 C 328 to 986 ºF 4 20 mA 8 8 8 8 J linearization Programmable range 110 to 760 C 4 20 mA 9 9 9 9 K linearization Programmable range 150 to 1370 C 4 20 mA 10 10 10 10 T linearization Programmable range 160 to 400 C 4 20 mA 11 11 11 11 N Linearization Faixa...

Page 3: ...The 3 modes of operation are pulse delayed actuation oscillator The desired function can be achieved programming the parameters A1t1 A1t1 A1t1 A1t1 A1t2 A1t2 A1t2 A1t2 A2t1 A2t1 A2t1 A2t1 and A2t2 A2t2 A2t2 A2t2 see Table 4 The LEDs associated to the alarms will light when the alarm condition is recognized not following the actual state of the output which may be temporarily OFF because of the tem...

Page 4: ...vto avto CONTROL MODE YES indicates automatic control mode closed loop PID or ON OFF NO indicates manual control mode open loop Bumpless transfer from auto to manual mode is available If in doubt program YES PV Indication Red MV Indication Green MANIPULATED VARIABLE VALUE MV The upper display shows PV value and the lower display shows the percentage of MV applied to the control output When in manu...

Page 5: ...bla4 bla4 bla4 bla4 ALARM BLOCK 1 TO 4 This function blocks the alarm at power up when the units is first energized YES enables and NO inhibits this blocking function When enabled the alarm will not be active at power up waiting for PV Process Variable to reach a non alarm situation From this point on the alarm will be free to actuate should a new alarm situation occur xya1 xya1 xya1 xya1 ALARM 1 ...

Page 6: ...optional hardware accessories The parameters menu will show the parameters relative to the optional hardware 0 no optionals or c RS485 only 1 relay 3 I O 3 2 Digital I O 2 inputs outputs 3 Heater break protection option Rsl REMOTE SET POINT LOW CALIBRATION Sets the Remote Set Point low calibration offset Several keystrokes at or might be necessary to increment one digit Rsx REMOTE SET POINT HIGH C...

Page 7: ...troller resumes at the beginning of the segment it was previously 10 AUTO TUNE During auto tune the process is controlled in ON OFF mode at the programmed SetPoint SV Depending on the process characteristics large oscillations above and below SV may occur and auto tuning may take several minutes to be concluded The recommended procedure is as follows Disable the control output at the rvn rvn rvn r...

Reviews: