background image

N1030 Controller  

NOVUS AUTOMATION 

2/5 

dif

 

Differential  alarm.  In this function, SPA1 represents 

an error (difference) between CONTROL PV and SP.  

 

SP 

PV 

SP + SPA1 

SP – SPA1 

 

 

SP 

PV 

SP – SPA1 

 

 

SP + SPA1 

 

 

Positive SPA1  

Negative SPA1 

difl

 

Alarm of minimum differential value. It triggers when 

the PV value is 

below

 the defined point by SP-SPA1. 

 

SP 

PV 

SP – SPA1 

 

 

SP 

PV 

SP – SPA1 

 

Positive SPA1 

Negative SPA1  

difk

 

Alarm of maximum differential. It triggers when the PV 

value is 

above

 the defined point by SP+SPA1. 

 

SP 

PV 

SP + SPA1 

 

 

SP 

PV 

SP + SPA1 

 

Positive SPA1 

Negative SPA1 

ierr

 

Open sensor alarm.  It triggers when the input 

presents problems such as a broken sensor, poorly 

connected sensor etc. 

Table 2 –

 

 

Alarm functions  

Important note

: Alarms configured with the 

ki

dif

, and 

difk

 

functions also trigger their associated output when a sensor fault is 

identified and signaled by the controller. A relay output, for example, 

configured to function as a Higher Alarm (

ki

), will operate when the 

SPA1  value is exceeded and when the sensor connected to the 

controller input is broken. 

ALARM INITIAL BLOCKING 

The 

Initial Blocking

 option inhibits the alarm from being triggered if 

an alarm condition exists when the controller is turned on. The alarm 

is triggered only after the process goes through a non-alarm 

condition. 
The initial blocking is useful, for example, when one of the alarms is 

configured as a minimum value alarm, which can cause the alarm to 

be triggered as soon as the process is started (a behavior that is 

often undesired). 
The initial block is not valid for the 

ierr

 function. 

OFFSET 

Function that allows you to make a small adjustment to the PV 

indication. Allows you to correct measurement errors that appear, for 

example, when replacing the temperature sensor. 

OPERATION  

The front panel of the controller can be seen in the figure below:  

 

Figure 2 –

 

Front panel identification 

Display

:  Displays the measured variable, configuration parameter 

symbols and their respective values/conditions. 

TUNE Indicator

: Stays on while the controller is in tuning process. 

OUT Indicator

: Signals the control output(s) status. 

A1 and A2 Indicators

: Signal the occurrence of an alarm condition. 

 

  Key

:  Key used to advance the successive parameters and 

parameter cycles. 

 

 Increment key and 

 

 Decrement key

: Keys used to change 

parameter values. 

 

  Back key

:  Key used to move back parameters during 

configuration. 

OPERATION 

When turned on, the controller shows the software version for the 

first 3 seconds, then it shows the value of the measured process 

variable (PV) in the upper display. In the lower display, it shows the 

SP value. This is the 

Indication Screen

To be used in a process, the controller must be previously 

configured. To configure it, each of the various parameters presented 

must be defined.  You  must understand the importance of each 

parameter and determine a valid condition or value. 
The configuration parameters are gathered in affinity groups, called 

parameter cycles. The 3 parameter cycles are: 

1 – Tuning / 2 – Input / 3 – Calibration  

The 

 

 key gives access to the cycles and their parameters. 

By keeping the 

 

  key pressed, every 2 seconds the controller 

jumps from one cycle to another, presenting the first parameter of 

each cycle:  

PV

  >>  

atvn

  >>   

type

  >>  

PASS 

>>  

PV

  … 

To enter the desired cycle, simply release the 

 

 key when the first 

parameter is displayed. To move forward through the parameters of 

that cycle, use the 

 

  key. To go backwards through the 

parameters, use the 

 

 key. 

The symbol of each parameter is shown in the upper display. Its 

respective value/condition is shown in the lower display. 
Depending on the configuration protection that you have adopted, the 

PASS

 parameter is shown as the first parameter of the cycle where 

the protection starts. See 

Configuration Protection

 chapter. 

PARAMETERS DESCRIPTION 

INDICATION SCREEN 

PV  
SP 

Temperature indication screen

. The upper (red) 

display shows the value of the measured variable (

PV

temperature.  
The lower display (green) shows the control setpoint 

value (

SP

), which is the desired value for the process 

temperature. 

Spa1

 

Alarm SP. Value that defines the alarm actuation point. 

For 

Differential

  type functions, this parameter 

specifies error (*). 

TUNING CYCLE 

Atvn 

 

AUTO-TUNE

.  Enables the automatic tuning of the 

PID parameters  (

pb

,

ir

dt

).  See 

PID Parameters 

Definition

 chapter.  

off

     

Auto-tune off.  

Fast  

Perform tuning in fast mode.  

Full  

Perform tuning in precise mode.  

PB 

 

Proportional Band. Value of the term 

P

 of the control 

mode PID, in percentage of the maximum span of the 

input type.  
Adjustable between 0 and 500.0 %. 

When set to zero (0), control action is ON/OFF. 

 

ir 

 

Integral Rate. Value of the term 

I

 of the PID algorithm, 

in repetitions per minute (Reset).  
Adjustable between 0 and 24.00.  
Displayed only if proportional band 

 0.  

Reviews: