Novus DIGIRAIL-2A Instruction Manual Download Page 2

DigiRail-2A 

NOVUS AUTOMATION 

2/2

 

CONFIGURATION 

The user will receive the module perfectly calibrated. No adjustment 

will be required. The original configuration features the following 

features: 

Sensor thermocouple type J, Indication °C, Filter = 0 

Address = 247, Baud Rate = 1200, Parity = Even,  

1 Stop Bit 

The application 

DigiConfig

  is a program for Windows  used  to 

configure  the 

DigiRail 

modules. For its installation, run the 

DigiConfigSetup.exe

 file, available on our website and follow the 

instructions as shown. 

DigiConfig

  is provided with a help file.  For using it, start the 

application and select 

the "Help" menu or press the F1 key.

 

Go t

www.novusautomation.com

 

to obtain the 

DigiConfig 

installer 

and the additional product manuals. 

SPECIFICATIONS 

Inputs:

 

2 universal analog inputs.

 

Input signals: 

Configurable. Refer to 

Table 2

Thermocouples

: Types J, K, T, R, S, B, N and E, according to 

NBR 

12771. Impedance >> 1M

 

Pt100

: 3-wires type, 

α

 

= .00385, NBR 13773, Excitation

700

 

µ

A. 

For using Pt100 2

-

wires, interconnect terminals 2 and 3.

 

 

When gauging the module using the calibrator for 

Pt100, be sure that the minimum current requir

ed for 

it is compatible with the specified excitation current: 

700

 

µ

A. 

Other Signals

 

0 to 20 mV, 

-

10 to 20 mV, 0 to 50 mV.

 

Impedance >> 1 M

 

 

0 to 5 Vdc, 0 to 10 Vdc. Impedance >> 1 M

 

 

0 to 20 mA, 4 to 20 mA. 

 

Impedance = 100 

 

(+ 1.7 Vdc)

 

Overall accuracy (at 25°C):  Thermocouples

:  0.25

  % of the 

maximum range, 

±

 

1

 

°C; Pt100, voltage and current: 0.15

 % of the 

maximum range. 

 

In  the  standard  model,  the  0

-5 Vd

c  and  0

-

10  V

dc 

inputs are not factory calibrated and have an 

accuracy of about 5 %. 
When properly calibrated, they can have an accuracy 

of up to 0.15 %.

 

 

INPUT SIGNAL 

MAXIMUM MEASURING RANGE 

Thermocouple J 

-

130 to 940 °C

 (-

202 to 1724 

°F) 

Thermocouple K 

-

200 to 1370 °C

 (-

328 to 2498 

°F) 

Thermocouple T 

-

200 to 400 °C (

-

328 to

 

752 

°F) 

Thermocouple E 

-

100 to 720 

°C (-

148 to 1328 

°F) 

Thermocouple N 

-

200 to 1300 °C

 (-

328 to 2372 

°F) 

Thermocouple R 

0 to 1760 °C

 (-

32 to 3200 

°F) 

Thermocouple S 

0 to 1760 °C

 (-

32 to 3200 

°F) 

Thermocouple B 

500 to 1800 °C

 

(932 to 3272 

°F) 

Pt100

 

-

200 to 650°C

 (-

328 to 1202 

°F) 

INPUT SIGNAL 

MAXIMUM MEASURING RANGE 

0 to

 

20 mV

 

 

-

10 to 20 mV

 

 

0 to 50 mV

 

 

*

 

0 to 5 Vdc

 

Adjustable between -

31000 and +31000

 

*

 

0 to 10 Vdc

 

 

0 to 20 mA

 

 

4 to 20 mA

 

 

Table 2 –

 

Sensors and signals accepted by the module 

Sampling rate:

 

from 2.5 to 10 sample

s per second

 

Internal compensation of Cold Junction for thermocouples. 
Power

: 10 to 35 Vdc. Typical consumption: 50 mA @ 24 V. 

Internal 

protection against polarity inversion.

 

Electrical insulation between inputs and supply/serial port: 

1000 Vac

.

 

Serial communication:

 RS485 at two wires, Modbus RTU protocol. 

Configurable parameters: Communication speed: F

rom  1200  to 

115200 bps; Parity: 

Even, odd or none

 

Key for restoring communication parameters:

 The RCom key, at 

the front panel, will set the device in diagnostics mode (Address = 

246

;  Baud rate  = 

1200

;  Parity  =  Even,  Stop  Bit 

=  1

), able to be 

detected and configured by the 

DigiConfig

 software. 

Frontal light indicators for communication and status: 

TX

: Signalizes that the device is sending data on the RS485 

line. 

RX

: Signalizes that the device is receiving data on the RS485 

line. 

Status

: When the light is permanently on, this means that the 

device is in normal operation.  When the light is flashing in a 

second interval (approximately), this means that the device is in 

diagnostics mode.  When the light is flashing fast, this means 

that there is an internal error.

 

Operating temperature

: 0 to 70 °C

 

Operational relative humidity

: 0 to 90

 % RH

 

Envelope of the terminals:

 Polyamide 

Assembly:

 DIN 35 mm rail 

Certification

: CE

 

Dimensions:

 Refer to 

Figure 3

.

 

 

Figure 3 –

 

Dimensions 

WARRANTY 

Warranty conditions are available on our website 

www.novusautomation.com/warranty

. 