Novus DIGIRAIL-2A Instruction Manual Download Page 1

NOVUS AUTOMATION 

1/2

 

 

 

 

DIGIRAIL-2A

 

UNIVERSAL ANALOG INPUT MODULES 

INSTRUCTION MANUAL 

 

V1.0x F

 

INTRODUCTION 

The universal analog input Modbus module 

DigiRail-2A

 is a remote 

measuring unit with two configurable analog inputs. An RS485 serial 

interface allows reading and configuring  these inputs  through  the 

communication network. It is  appropriate for mounting on DIN 35 

mm rails. 
The inputs are electrically insulated from the serial interface and the 

module supply. There is no electrical insulation between inputs. 

There is  also no electrical insulation between serial interface and 

supply. 

DigiRail-2A

 configuration is performed through the RS485 interface 

by using Modbus RTU commands. The 

DigiConfig

 software allows 

configuring all 

DigiRail 

features as well as performing its diagnostic.  

DigiConfig

 offers features for detecting the devices present in the 

Modbus network and for configuring the 

DigiRail-2A

 communication 

parameters. 
This manual provides instructions to install and connect the module. 

The 

DigiConfig

 installer and the documentation regarding Modbus 

communication for 

DigiRail-2A

  (

DigiRail-2A  Communication 

Manual

) are available at 

www.novusautomation.com

ELECTRICAL INSTALLATION 

INSTALLATION RECOMMENDATIONS 

 

Input and communication signal conductors must pass through 

the  system plant separated from the electrical network 

conductors. If possible, in grounded conduits. 

 

The supply for the instruments must be provided from a proper 

instrumentation network. 

 

In control and monitoring applications, it is essential considering 

what may occur if any of the system parts should fail. 

 

We  recommend  the  use  of  RC  FILTERS  (47Ω  and  100nF, 

series) in parallel with contactor and solenoid coils which are 

close or connected to 

DigiRail

ELECTRICAL CONNECTIONS 

Figure 1

 shows the necessary electrical connections. The terminals 

1, 2, 3, 7, 8 and 9

 are intended for the input connections, 5 and 6 for 

the module supply and 10, 11 and 12 for the digital communication. 

 

For obtaining a better electrical contact with the connectors, we 

recommend the use of pin terminals at the conductor end. For direct 

w

ire connection, the minimum gage recommended is 0.14 mm², not 

exceeding 4.00 mm².

 

 

Be careful when connecting the supply terminals to 

the 

DigiRail

. If the positive conductor of the supply 

source is connected, even momentarily, to one of the 

communication  connection terminals, the module 

may be damaged. 

         

 

Figure 1 –

 

Electrical connections 

Table  1

  shows how to connect the connectors to the RS485 

communication interface: 

 

 

 

 

Bidirectional data line. 

Terminal 10 

 

 

 

 

Inverted bidirectional data 

line. 

Terminal 11 

 

Optional connection which 

improves the communication 

performance. 

Terminal 12 

 

Table 1 –

 

 

RS485 Connections 

CONNECTIONS – INPUT 0-5 VDC / 0-10 VDC 

For using the 0

-

5 Vdc and 0

-

10 Vdc input types, 

it is necessary to 

switch the position of the inner  module jumpers. To this end, the 

module must be opened and jumpers J1 and J2 (input 1 and input 2, 

respectively) must be changed due to the following options: 

 

For 0

-

5 Vdc and 0

-

10 Vdc input types, positions 1 and 2 must 

be strapped. 

 

For all other input typ

es, positions 2 and 3 must be strapped 

(factory position). 

 

Figure 2 –

 

Jumper for 0

-5 Vdc and 

0

-

10

 Vdc input 

 

 

 