6.8 Fault localization

These are likely causes of breakdowns/ 
failures:

Deficiency in performance:

•Blocked air supply to the fan inlet side:

– Damper closed
– Duct choked
– Supply fan, if any, stopped
– Motor defective
– Motor disconnected

• Wrong direction of rotation of impel-

ler

Noise/vibrations:

• Bearings in electric motor defective
• Impeller out of balance
• Impeller worn/damaged
• Bolts/components loose
• Impeller blades have different pitch 

angles

• Fan operates in the stalling area. May 

result in breakdown. Repair failures, 
see “Deficiency in performance”.

7. Test of operability and 

operating condition

ACN-smoke approved for smoke con-
trol must be tested four times a year as to 
operability and operating condition.
If smoke exhaust fans type ACN-smoke 
are used for standard ventilation as well, 
a test every six months is sufficient if the 
regular starts of the fans ensure at least 
one start a day - as a result of connection 

to a time switch or carbon monoxide 
alarm.

7.1 Periodic inspection

Novax smoke exhaust fans must always 
be kept in operational and perfect condi-
tion by the user. The fans should be in-
spected twice a year to ensure a satisfac-
tory function and long life.

The inspection must include:
• Measuring of power consumption
• Measuring  of  vibrations on fan casing
• Check of torque for fixing bolts and – 

correction of it, if necessary.

• Visual inspection of impeller, fan cas-

ing, and connection to the electricity 
supply

• Cleaning:

– inside with pressure air
– outside with water

It is recommended to enter all values and 
observations in a log.

8. Sound

The sound generation of the fans de-
pends on installation and operating con-
ditions, which means that no general da-
ta of the sound generation can be given.
Reference is made to our catalogues or 
computer programs for calculation of 
the specific sound generation.

9.  Attestation of conform-

ity

EU – Attestation of Conformity

The Machinery Directive 2006/42/EC, 
part 2, A 

Novenco A/S
Industrivej 22
DK-4700 Naestved

Hereby declares that axial flow fans type 
ACN-smoke 400-1600 have been manu-
factured in conformity with the Coun-
cil's directives 
2006/42/EC regarding mutual approxi-
mation of the machinery laws (the Ma-
chinery Directive) of the member states.

Applied standards:

EN ISO 12100-1: Safety of machinery

part 1

EN ISO 12100-2: Safety of machinery

part 2

EN ISO 13857: Safety of machinery - 

Safety distances

EN 12101-3:

Smoke and heat control
systems - Part 3, class 1

EN 60204-1:  Safety of machinery - 

Electrical equipment of
machines Part 1: 
General Requirements

It is a condition that Novenco's instruc-
tions for installation have been followed.

Naestved, 01.06.2010

Steen Hansen
R&D Manager
Novenco A/S 

Figure 6. Electric connection through fan casing to external terminal box 

External terminal box

External terminal box

Electric cable/

Electric cable/
Flexible metallic conduit

Flexible metallic conduit

Metal

Metal

 cable gland

 cable gland

 (relief)

 (relief)

Nut

Nut

Novenco A/S

Industrivej 22

Tel. (+45) 70 12 42 22

DK-4700 Naestved Fax  (+45) 55 75 65 50
Denmark

www.novencogroup.com

Summary of Contents for FALKINN ACN

Page 1: ...supplied with approval number class category are also men tioned as well as test standard applied EN 12101 3 Fan pressure air quantity output and maximum speed per minute The fan is also provided with a motor nameplate with relevant motor data in cluding insulation class of the motor 2 2 Weight The total weights shown in table 1 apply to axial flow fan type ACN smoke The totalweightisdeterminedont...

Page 2: ...uspended in the fan casing flanges or in special carriers The carriers must not hamper the free in let and outlet of air When the fan has been finally secured makesurethattheimpellerrotatesfreely in the casing If the motor is provided with drain holes for condensed water the fan must be ori ented so that the holes turn downwards lowest point Generally it is of the utmost importance for the perform...

Page 3: ...med by the person responsible for the operation of the system and the documentation must be kept and produced whenever asked for Prior to start of operation check that the fan and duct connections are clean and free from tools and foreign substances Also check that the electric connections meet the prescribed requirements that any wire guard fitted on the fan inlet or outlet side is correctly moun...

Page 4: ...r bearings or other fan compo nents 6 6 Mounting of motor for types ACN smoke see fig 5 After servicing remount the motor take care that the motor flange item 10 is cor rectly located and that the motor shaft is concentrically placed in the fan casing before tightening the bolts item 06 Mount the impeller item 04 on the mo tor shaft by means of a tool fastened in the threaded hole of the motor sha...

Page 5: ...ectricity supply Cleaning inside with pressure air outside with water Itisrecommendedtoenterallvaluesand observations in a log 8 Sound The sound generation of the fans de pends on installation and operating con ditions which means that no general da ta of the sound generation can be given Reference is made to our catalogues or computer programs for calculation of the specific sound generation 9 At...

Reviews: