~ 9 ~
NOVATEK-ELECTRO UBZ-305
Table 2.5 (Continued)
Measurement functions
Range
Accu-
racy
Mnemonic
Address
Data transfer
units
Phase U3
47
Volt
Effective values of line voltages, V
100
–
475
5V
Line U1
Line U2
Line U3
48
49
50
Volt
Positive-sequence voltage, V
100
–
300
3V
Positive sU
51
Negative-sequence voltage, V
3
– 300
3V
Revers sU
52
Zero-sequence voltage (vector sum of three
phase voltages divided by three), (it is defined
when connecting to the neutral wire of UBZ), V
3
– 100
3V
Zero sU
53
Miscellaneous
Time counter of motor operation, day
0
– 999
Time
motor
54
Motor insulation resistance
1
, MOhm
0
– 19.9
10%
Insulation
55
Hundreds of
kOm
Mains frequency, Hz
45
– 65
1%
Frequency
56
Tenths of Hertz
Hold time before automatic restart
2
, s
0
– 900
1 s
End of AR
57
Second
Time to overload trip (it indicates the time
remaining until shutdown made by thermal
overload protection)
3
, s
0
– 600
1 s
Before
OvL
58
Second
Waiting time after overload trip (it indicates
waiting time before permit to start-up blocked
by thermal overload protection)
3
, s
0
– 900
1 s
After OvL
59
Second
Full power
4
, kVA
0
– 5000
5%
Apparent P
60, 61
Dozens
of
Watts
Active power
4
, kW
0
– 5000
5%
Active P
62, 63
Reactive power
4
, kVA
r
0
– 5000
5%
Reactive P
64, 65
Cosine of angle between voltage and phase
current L1
0
– 1
5%
Cos A
66
Cosine of
angle between
voltage and
current *1000
Cosine of angle between voltage and phase
current L2
0
– 1
5%
Cos B
67
Cosine of angle between voltage and phase
current L3
0
– 1
5%
Cos C
68
Temperature of transmitter 1
5
, °C
minus 40
– 80
1°C
Temp
dat 1
69
5000
–
transmitter is
off
1000+-10
–
s.c. of
transmitter
2000+-10
–
transmitter
breakout
Temperature of transmitter 2
5
, °C
minus 40
– 220
1°C
Temp
dat 2
70
Current value at analogue input "4-20 mA", mA
0
– 25
2%
Input i
71
Voltage value at analog input "0-10 V", V
0
– 10
2%
Input U
72
Full electric power
6
, kVA/h
0
–
200000000
5%
ApE
90
91
Active electric power
6
, kW/h
0
–
200000000
5%
AcE
92
93
Reactive electric power
6
, kVA
r
/h
0
–
200000000
5%
ReE
94
95
Notes:
1
If the insulation resistance of the motor is more than 20 MOm, then the value indicator displays code
“>20M“.When the motor is running (energized motor) the insulation resistance is not defined and the code
indicator displays “---“(when measuring circuit of motor insulation connecting).
2
If ARS is disabled, the indicator displays
“not”.
3
If the time before shutdown by thermal overload protection or waiting time before permit to start-up is not defined
(more than 900 s), then the value indicator displays code
“undef“. If the protection function is disabled, the
indicator displays
“not”.
4
If the power consumed by the load is more than 999 kW (kVA, kVA
r
), the values of power are displayed with MW
(MVA, MVA
r
).
5
If the temperature value exceeds specified limits, then the indicator displays the alarm code in accordance with
table 5.12. If the temperature sensor is disabled by software, then the indicator instead of temperature values
displays
“Off”.
6
In excess of the energy meter of the value 200 000 000, the counter is reset and the energy metering will start
from zero. Recording the current values of the energy in the non-volatile memory is performed every 15 min.