2.3. TIMER PROGRAMMING 
 

2.3.1. SEQUENTIAL TIMER PROGRAMMING 

 

1. Fix switch RUN/PROG in position PROG. 
2. For sequential timer selection fix switch SEQ/COMB in position SEQ. Supply power to 
inputs A1 and A2. 
3. Using the button RELAY select the channel 1. 
4. Using the button DLY/ON select time DLY for time setting, during which the contacts of 
channel relay will be open. 
5. Press RANGE for selection of necessary time range. 
6. Using arrow buttons set the necessary time. 
7. Repeat steps 4 through 6 for status time setting ON, during which the contacts of channel 
relay will be closed. 
8. Repeat steps 3 through 7 for setting of other channels. 
 
2.3.1. COMBINATION TIMER PROGRAMMING 
 
1. Fix switch RUN/PROG in position «PROG». 
2. For selection of combination timer fix switch SEQ/COMB in position COMB. Energize 
the inputs A1 and A2. 
3. Using button RELAY select channel 1. 
4. Using button COMBINATION select combination 1. 
5. Using button DLY/ON select time DLY for time setting, during which the contacts of 
channel relay will be open. 
6. Press RANGE for selection of necessary time range. 
7. Using arrow buttons set the necessary time. 
8. Repeat steps 5 through 7 for set of status ON, during which contacts of channel relay will 
be closed. 
9. Repeat steps 4 through 8 for setting the other channel combinations. 
10. Repeat steps 3 through 9 for setting of other channels and their combinations. 

 
2.4. TIMER START 
 

1. Fix the switch RUN/PROG in position RUN. Energize inputs A1 and A2. 
2. Closure of contacts S1 and S2 on the front panel for at least 150 milliseconds causes 
execution of set program by the timer. 
3. Execution of program is started from the first channel (first combination) and position of 
contacts OFF. 
4. Contacts S1 and S2 may be permanently closed from start of program after power supply. 
 

2.5. RESETTING 

 
For resetting to default settings (zero) it is necessary in program mode switch SEQ/COMB in 

opposite position.

 

Summary of Contents for TK-415

Page 1: ...TD Sequential and Combination Timer TK 415 with RS 232 communication OPERATION MANUAL WWW NOVATEK ELECTRO COM EN 2011 www novatek electro in 15 channel Traffic Controller TK 415 Sequential cum Combina...

Page 2: ...possible RS 232 communication port for programming and possibility of operation through PC DCS free PC software 1 2 BASIC TECHNICAL BRIEF Table 1 1 Supply voltage V 85 to 270 AC DC Frequency range Hz...

Page 3: ...mum electric resource 4A 250V AC os 0 4 times minimum 107 100 000 30 000 100 000 Signal Start Contact Closure S1 and S2 maximum at 150 milliseconds Mounting onto standard 35 mm DIN rail Mounting posit...

Page 4: ...g to technical specifications 10 RANGE Button for selection of range of time programming DLY ON according to the Table 1 2 Table 1 2 Designation Range HRS MIN from 1 minute to 99 hours 59 minutes MIN...

Page 5: ...e of channel contacts 18 Indicator of selected time range see Table1 2 19 Indicator displaying current mode of time programming of open DLY or closed ON contacts on Time indicator 20 Indicator of sele...

Page 6: ...6 II Sequential timer cycling mode inputs C1 and C2 are not shorted Diagram 1 2...

Page 7: ...7 III Combination timer mode of execution of one cycle of program inputs C1 and C2 are shorted Diagram 1 3 Where for example R2C5 means the fifth combination of the second channel relay...

Page 8: ...8 IV Combination timer cycle mode inputs C1 and C2 are not shorted Diagram 1 4...

Page 9: ...ETTING AND OPERATION 2 1 CONNECTION The Figure 2 1 represents the typical method of timer connection Load is connected to output of channel RLY10 as an example Figure 2 1 Typical method of timer conne...

Page 10: ...rs with possibility of cycle work upon completion of operation of last timer the first one starts operating is represented at Figure 2 3 Figure 2 3 Cycle operation of timers in case of cascade connect...

Page 11: ...nel 1 4 Using button COMBINATION select combination 1 5 Using button DLY ON select time DLY for time setting during which the contacts of channel relay will be open 6 Press RANGE for selection of nece...

Page 12: ...ce see Diagram 1 1 2 9 JOINT OPERATION OF SEVERAL TIMERS IN SEQUENTIOAL MODE In case of cascade connection of several timers outputs O1 and O2 of the first timer should be connected to inputs S1 and S...

Reviews: