background image

- 6 - 

ОМ-310

 

                                                                                                                                                      

NOVATEK-ELECTRO

 

Note

. When working with external transformers of rated current over 100A, the currents (measured and cal-

culated), except for the zero sequence current (ground fault) are transferred via RS-232/RS485 in amperes. 
** 

Note.

 If power consumed by the load is over 999 kW (kVA, kVAr), then MW (MVA, MVAr) is displayed on 

screen with a “

п

” – shaped point in the middle position. For instance, if the display shows 3

п

4”, it means  3.4 

MW (MVA, MVAr).  
*** 

Note.

 If automatic reset is forbidden, "not" message is displayed. 

**** 

Note.

 If the time is not defined, "---" is displayed on screen.  

1.2.3 Programmable parameters and their variability ranges

 are shown below in table 1.5. 

 

Table 1.5 - Programmable parameters 

 

                                                                                                                                         

Settings and read-off 
parameters  

Code pa-
rameters 

Minimum 
values 

Max. 
values 

Default 
setting 

Operation 

Address 

Transformers

 

 

 

CT in use 



0-intergrated CT are in use 
1-external CTs are in use 

150 

CT rated current, A 



20 

800 

100 

For an external CT 

151 

CT rated current, A 



700 

10 

Used for calsculating the current and 
the time of overcurrent protection  

152 

Power Control

 

 

 

Rated

 

power

 

of load, kW 



450 

 

153 

Power limiter tripping 
thresholds calculation 
parameter  



0 – threshold calculation for each 
phase (power handling capability for 
each phase equals Pnn/3) 
1 – threshold calculation for each 
phase +20% (total power for al pha-
ses equals Pnn, but not more than 
Pnn*1,2/3 for each phase) 
2 – aggregate threshold calculation 
(total power for all phases equals Pnn) 

154 

Main threshold, % 



50 

150 

110 

 

155 

Additional threshold*, % 



30 

100 

90 

 

156 

Time before load relay 
de-energizing, sec 
(main threshold) 



300 

60 

Time before load disconnect tripping 
when the load wattage main threshold 
is exceeded  

157 

Time while load relay is 
open, min 
(main threshold) 



60 

Time during which load relay is open 
after tripping when the load wattage 
main threshold is exceeded  

158 

Time before characteriz-
ing relay de-energizing*, 
sec 
(additional threshold) 



300 

10 

Time after which the characterizing re-
lay will open after tripping when the 
load wattage main threshold is ex-
ceeded  

159 

Time while the charac-
terizing relay is open, 
min (additional thre-
shold)  



60 

Time during which the characterizing 
relay is open after tripping which take 
place when the load wattage main 
threshold is exceeded  

160 

Additional threshold of 
the characterizing relay 
closure, % 



100 

30 

Threshold for the characterizing relay 
closure after overload triggered 
opening  

161 

Characterizing relay 
operation mode 



0 - the relay is used as an alarm relay 
1- the relay is used as a time relay 
(closes after time specified in 



 pa-

rameter after load relay closure ) 
2-the relay is used for connecting addi-
tional load 
3- the relay will close when load wat-
tless power threshold 



 is exceeded 

4- relay will be switched on after ex-
ceeding of main tripping 

162 

Characterizing relay 
activation mode when 



 



0 – relay will close after expiration of 
time 



 

1 – relay will close after reduction of 
consumed wattage  to level 



 

163 

Summary of Contents for OM-310

Page 1: ...NOVATEK ELECTRO LTD Research and Manufacture Company POWER LIMITER OM 310 USERS MANUAL www novatek electro com...

Page 2: ...ontrol Modes 13 2 2 2 Disabled keypad mode 14 2 2 3 MMSP mode 14 2 2 4 User level 14 2 2 5 Service Engineer Level 14 2 2 6 Restoring factory settings 15 2 3 OM 310 PRE OPERATION PROCEDURE 15 2 4 INTEN...

Page 3: ...OM 310 is possible via OM 310 Control Panel Software that can be downloaded from the Novatek Electro website http www novatek electro com production_ htm OM 310 Control Panel software is dedicated fo...

Page 4: ...ccuracy for wattage of rated wattage at most 5 Tripping threshold accuracy for current of rated current at most 2 Tripping threshold accuracy for voltage V at most 3 Phase imbalance detection accuracy...

Page 5: ...V 100 300 3 V 111 112 113 Power voltage RMS values V 100 450 5 114 115 116 Positive sequence voltage V 100 300 3 B 117 Negative sequence voltage V 3 300 3 B 118 Zero sequence voltage vector sum of thr...

Page 6: ...aggregate threshold calculation total power for all phases equals Pnn 154 Main threshold 50 150 110 155 Additional threshold 30 100 90 156 Time before load relay de energizing sec main threshold 0 300...

Page 7: ...3 2 0 1 0 171 Protection function permission 0 2 0 0 protection function prohibited 1 protection function permitted after tripping automatic reset prohibited 2 protection function permitted after trip...

Page 8: ...from Table 1 5 187 Min number of setting parameters mode ena ble 0 1 1 0 mode disabled 1 mode enabled The mode change is enabled in the service engineer mode only 188 Indication on OM 310 display pan...

Page 9: ...red LED SETUP glows when the relay is in parameter setup mode 2 green LED LOAD glows when the load relay is closed 3 green LED RELAY glows when the characterizing relay is closed 4 green LED MMSP mod...

Page 10: ...g it for connection of additional loading After 310 energizing after AR time parameter the load relay will close If during operation the active power consumed by the load crosses the main threshold fo...

Page 11: ...on which event a or b comes first If during operation the active power consumed by the load crosses the additional threshold line 1 figure 1 3 for a time period that is longer than assigned by parame...

Page 12: ...It is engaged when at least one of the phase current values reach the tripping threshold The protection has a time delay setting The delay can be independent constant or dependent SIT reverse depende...

Page 13: ...time assigned by parameter 1 2 6 6 Protection based on phase sequence order trips in case of phase sequence order fault or phase coin cidence it opens the load relay and locks its further operation 1...

Page 14: ...access mode When switching off the MMSP mode setting parameter 0 LED MMSP goes off In the user mode all parameters list is displayed but to change a parameter parform the following with DOWN and UP b...

Page 15: ...th 5A rated output current shall be connected in accor dance with Fig 2 1 For correct OM 310 operation the current transformers polarity must be observed 2 3 2 Run all three power phase cables through...

Page 16: ...h use of external CTs and at 2 characterizing relay operation in the mode of controlling additional load 2 4 INTENDED USE Note In the 310 operation description it is assumed that the protections descr...

Page 17: ...0 or within 15 sec and then phase A current 1 indication is displayed again 2 4 3 Characterizing relay operation Functions performed by the characterizing relay are defined by parameter When 0 the re...

Page 18: ...command code and DATA data symbols Data symbols format depends on command codes Command code 0x03 n words read For example read 2 continuous words swapped from 2102H in 310 initial address with 01H co...

Page 19: ...ode 08h diagnostics 08h function provides a number of tests for checking communication system between PC and OM 310 and for OM 310 integrity control The function uses the sub function field to specify...

Page 20: ...crc_chk unsigned char data unsigned char length int j unsigned int reg_crc 0xFFFF while length reg_crc data for j 0 j 8 j if reg_crc 0 01 reg_crc reg_crc 1 0xA001 LSB b0 1 else reg_crc reg_crc 1 retur...

Page 21: ...f the data transferred unsupported function code etc 310 receives the request frame and forms a response with the error indicator and code A high order function field bit inserted in the unit serves a...

Page 22: ...on in the remote control mode is defined by the parameter When 0 the load energize cutoff by means of remote breaker is prohibited When 1 310 with the open terminal of the S1 remote breaker fig 2 1 fu...

Page 23: ...olling performed by pressing UP and DOWN buttons To exit log view mode press RECORD RESET SELECT button or the log will close automatically after 30 sec since last button was pressed Fault information...

Page 24: ...e humidity when there are no fumes in the air that have a damaging effect on package and the equipment material The customer shall provide for the 310 equipment protection against mechanical dam age w...

Page 25: ...25 NOVATEK ELECTRO 310 APPENDIX 1 Dependent time delay current based protection types...

Page 26: ...26 310 NOVATEK ELECTRO...

Page 27: ...27 NOVATEK ELECTRO 310...

Page 28: ...28 310 NOVATEK ELECTRO...

Page 29: ...220 240 LYQ20DC12 6031007G 6131406HQ 6 1393099 3 6 1393099 8 6 1393122 4 6 1393123 2 6 1393767 1 6 1393843 7 6 1415012 1 6 1419102 2 6 1423698 4 6 1608051 6 6 1608067 0 6 1616170 6 6 1616248 2 6 16162...

Reviews: