background image

- 14 - 

ОМ-310

 

                                                                                                                                                      

NOVATEK-ELECTRO

 

2.2.2 Disabled keypad mode 

When keypad is locked, viewing and resetting programmable parameters is not possible. 
When keypad is locked, pushing SETUP button will result in LOC message display.  To unlock the keyboard the 

SETUP button shall be pressed again.  The "SETUP" LED lights up, and figure "0" is blinking on the indicator. With 
the UP and DOWN buttons user enters a password digit from 1 to 9 and presses the RECORD/RESET/SELECT  
button. If the password is correct, the keypad will be unlocked. If after the keypad was unlocked no button is 
pressed during 15 sec and the lockage setting is not released by user, the keypad will relock. 

The unblocked keypad allows: 
-  to operate in MMSP mode; 

-

  to change and to view the user level parameters; 

-

  to view the service engineer level parameters. 

2.2.3 MMSP – mode with minimum number of setting parameters 

MMSP is devised to ease the service personnel’s operations with ОМ

-310. 

To employ MMSP mode in OM-310, the user needs to set 



=1 parameter, or perform resetting to factory set-

tings. (2.2.4). When ОМ

-310  unit is in this operation mode, green LED 

MMSP

  is on. 

In MMSP for normal activity of OM-310 is enough fix parameter 



 (nominal active power table 1.5 if necessary 

parameters 



 (time where through loading  relay will be switched OFF after  of  energy input exceedence of main 

thresholds table 1.5) and 



 (time  interval of cut off  loading relay on energy input exceedence  of main threshold 

table 1.5) 

On duty of external TT is necessary to fix following parameters: 
-type of TT (parameter 



, table 1.5) external; 

-nominal current of TT (parameter 



, table1.5). 

 
The difference between MMSP mode and the user mode is that the parameters not included in the MMSP regis-

ter are set to default factory values. 

 

ATTENTION! If some programmable parameters have been modified by the user or service engineer, but 

not included in the MMSP register, switching to MMSP mode will reset such parameters to factory settings.

  

 

The parameters included in this register cannot be viewed or modified. Operations with the MMSP register pa-

rameters are similar to the user level operations. 

Adding parameters to the MMSP register and MMSP mode disabling is possible only in service engineer 

access mode. 

When switching off the MMSP mode (setting 

parameter 



=0) LED “MMSP

” goes off. In the user mode all 

parameters list is displayed, but to change a parameter, parform the following:

 

- with DOWN and UP buttons choose  the parameter to be added; 
 - push buttons DOWN and UP simultaneously. 

 

2.2.4  User level 

To view and to change the user level parameters one needs to press the SETUP button, then "SETUP" LED will 

glow. Scroll parameters with DOWN and UP buttons, enter parameter change mode – repeat push SETUP button 
(the parameter value starts to flicker), change parameters –  with DOWN and UP buttons, record parameter   -  
RECORD/RESET/SELECT , to return to menu without change – press SETUP button again. If no button is pressed 
during 15 sec the 

ОМ

-310 will transfer to the initial state. 

If a parameter change is forbidden (a dot in the middle digit field of the parameter mnemonic indicator glows), 

then the parameter change is possible only in Service Engineer level after the prohibition has been released. 

 

2.2.5 Service Engineer Level 

Access to the Service Engineer level. 
Push SETUP button and hold for 5 sec. If the level is protected by a password, the label PAS appears on the 

indicator. The "SETUP" LED lights up, and indication "000" flickers on the parameter value indicator. With the UP 
and DOWN buttons enter the three-digit service engineer password, digits from 1 to 9 and separate dialing with 
pressing the RECORD/RESET/SELECT  button. If the password is incorrect, the PAS label lights on blinking in the 

higher position of the value indicator, and ОМ

-310 goes back to the initial state after 15 sec, otherwise the first pa-

rameter of the service engineer menu appears on the indicator. 

Scroll parameters with DOWN and UP buttons, enter parameter change mode – repeat push SETUP button (the 

parameter value starts to flicker), change parameters –  with DOWN and UP buttons, record parameter  -  
RECORD/RESET/SELECT , to return to menu without change – press SETUP button again. If no button is pressed 
during 1

5 sec the ОМ

-310 will transfer to the initial state. 

While ОМ

-310  is in Service Engineer mode, the decimal point in the lower digit position of the mnemonic indica-

tor is on. 

In the Service Engineer level the access to any user level parameter can be prohibited or permitted by simulta-

neous the SET and DOWN buttons pressing. Access denial is indicated by decimal point in the middle digit position 
of the mnemonic indicator. 

Summary of Contents for OM-310

Page 1: ...NOVATEK ELECTRO LTD Research and Manufacture Company POWER LIMITER OM 310 USERS MANUAL www novatek electro com...

Page 2: ...ontrol Modes 13 2 2 2 Disabled keypad mode 14 2 2 3 MMSP mode 14 2 2 4 User level 14 2 2 5 Service Engineer Level 14 2 2 6 Restoring factory settings 15 2 3 OM 310 PRE OPERATION PROCEDURE 15 2 4 INTEN...

Page 3: ...OM 310 is possible via OM 310 Control Panel Software that can be downloaded from the Novatek Electro website http www novatek electro com production_ htm OM 310 Control Panel software is dedicated fo...

Page 4: ...ccuracy for wattage of rated wattage at most 5 Tripping threshold accuracy for current of rated current at most 2 Tripping threshold accuracy for voltage V at most 3 Phase imbalance detection accuracy...

Page 5: ...V 100 300 3 V 111 112 113 Power voltage RMS values V 100 450 5 114 115 116 Positive sequence voltage V 100 300 3 B 117 Negative sequence voltage V 3 300 3 B 118 Zero sequence voltage vector sum of thr...

Page 6: ...aggregate threshold calculation total power for all phases equals Pnn 154 Main threshold 50 150 110 155 Additional threshold 30 100 90 156 Time before load relay de energizing sec main threshold 0 300...

Page 7: ...3 2 0 1 0 171 Protection function permission 0 2 0 0 protection function prohibited 1 protection function permitted after tripping automatic reset prohibited 2 protection function permitted after trip...

Page 8: ...from Table 1 5 187 Min number of setting parameters mode ena ble 0 1 1 0 mode disabled 1 mode enabled The mode change is enabled in the service engineer mode only 188 Indication on OM 310 display pan...

Page 9: ...red LED SETUP glows when the relay is in parameter setup mode 2 green LED LOAD glows when the load relay is closed 3 green LED RELAY glows when the characterizing relay is closed 4 green LED MMSP mod...

Page 10: ...g it for connection of additional loading After 310 energizing after AR time parameter the load relay will close If during operation the active power consumed by the load crosses the main threshold fo...

Page 11: ...on which event a or b comes first If during operation the active power consumed by the load crosses the additional threshold line 1 figure 1 3 for a time period that is longer than assigned by parame...

Page 12: ...It is engaged when at least one of the phase current values reach the tripping threshold The protection has a time delay setting The delay can be independent constant or dependent SIT reverse depende...

Page 13: ...time assigned by parameter 1 2 6 6 Protection based on phase sequence order trips in case of phase sequence order fault or phase coin cidence it opens the load relay and locks its further operation 1...

Page 14: ...access mode When switching off the MMSP mode setting parameter 0 LED MMSP goes off In the user mode all parameters list is displayed but to change a parameter parform the following with DOWN and UP b...

Page 15: ...th 5A rated output current shall be connected in accor dance with Fig 2 1 For correct OM 310 operation the current transformers polarity must be observed 2 3 2 Run all three power phase cables through...

Page 16: ...h use of external CTs and at 2 characterizing relay operation in the mode of controlling additional load 2 4 INTENDED USE Note In the 310 operation description it is assumed that the protections descr...

Page 17: ...0 or within 15 sec and then phase A current 1 indication is displayed again 2 4 3 Characterizing relay operation Functions performed by the characterizing relay are defined by parameter When 0 the re...

Page 18: ...command code and DATA data symbols Data symbols format depends on command codes Command code 0x03 n words read For example read 2 continuous words swapped from 2102H in 310 initial address with 01H co...

Page 19: ...ode 08h diagnostics 08h function provides a number of tests for checking communication system between PC and OM 310 and for OM 310 integrity control The function uses the sub function field to specify...

Page 20: ...crc_chk unsigned char data unsigned char length int j unsigned int reg_crc 0xFFFF while length reg_crc data for j 0 j 8 j if reg_crc 0 01 reg_crc reg_crc 1 0xA001 LSB b0 1 else reg_crc reg_crc 1 retur...

Page 21: ...f the data transferred unsupported function code etc 310 receives the request frame and forms a response with the error indicator and code A high order function field bit inserted in the unit serves a...

Page 22: ...on in the remote control mode is defined by the parameter When 0 the load energize cutoff by means of remote breaker is prohibited When 1 310 with the open terminal of the S1 remote breaker fig 2 1 fu...

Page 23: ...olling performed by pressing UP and DOWN buttons To exit log view mode press RECORD RESET SELECT button or the log will close automatically after 30 sec since last button was pressed Fault information...

Page 24: ...e humidity when there are no fumes in the air that have a damaging effect on package and the equipment material The customer shall provide for the 310 equipment protection against mechanical dam age w...

Page 25: ...25 NOVATEK ELECTRO 310 APPENDIX 1 Dependent time delay current based protection types...

Page 26: ...26 310 NOVATEK ELECTRO...

Page 27: ...27 NOVATEK ELECTRO 310...

Page 28: ...28 310 NOVATEK ELECTRO...

Page 29: ...220 240 LYQ20DC12 6031007G 6131406HQ 6 1393099 3 6 1393099 8 6 1393122 4 6 1393123 2 6 1393767 1 6 1393843 7 6 1415012 1 6 1419102 2 6 1423698 4 6 1608051 6 6 1608067 0 6 1616170 6 6 1616248 2 6 16162...

Reviews: