Novar-NRC
KMB systems
7
Tab. 2.1 : Novar-1xxx NRC Additional and Affected Parameters
#
name
range
step
default
comment
1
(7)
target PF for
metering rate 1
(2)
actual remote
controlled
target PF
0.80 L ÷ 0.80 C
„EX.XX“ format indicates
remote controlled target PF
value in the „RCC“-mode
0.01
0.98 L
in the „RCC“-mode (see par. 53), depending
on the metering rate 2 parameter setting and
state, the actual value of target PF is defined
by setting of the „remote controlled target
PF“ (par. 80) and by actual state of the
„remote controlled PF serial number“ (par.
81)
6 metering rate 2
enable/disable
0 – 1 – E
—
0
when the metering rate 2 parameter enabled
(value "1" or "E") and the "RCC"-mode (par.
53) enabled, PF control is carried out by the
„remote controlled target PF“ when the
metering rate 2 just active only (i. e. when
digital input activated or active power export
occurs ); for metering rate 1, the PF is
controlled by the target PF for metering rate
1 (par. 01), regardless to the „remote
controlled target PF“ value
30 alarm setting
0 / indication only / actuation
only / indication and actuation
—
indication and
actuation
from
undercurrent,
voltage signal
absence or
section error
1... undercurrent
…
14 … external alarm
15 ... NRC86 connection loss
Alarm No. 15 is activated when no response
from the NRC86 unit occurs during approx. 20
seconds. The alarm actuation function is
intended mainly for the „I/O“-mode.
40 alarm
instantaneous
condition
„0“ indicates passive state, „1“ indicates active
state. Alarm numbering according par. 30.
50 instrument
address
1 ÷ 255
1
1
In the„RCC“- and a the„I/O“-mode the preset
value has no meaning. The fixed address 200
is used for communication with the NRC86
unit.
51 communication
rate
4800 – 9600 – 19200 Bd
—
9600
In the„RCC“- and a the„I/O“-mode the value
must correspond to that of the NRC86 unit
52 communication
protocol
NRC86
response
timeout
KMB(P0)
0 – 1 – 2 – 3 – 8 sec
-
KMB(P0)
0 sec
Modbus-RTU protocol cannot be set.
In the„RCC“- and a the„I/O“-mode (par. 53)
the parameter defines the NRC86 unit
response timeout in seconds.
53 remote control
mode
-(=off) / IO / IO. / RCC / RCC.
/ RCCP
-
-(=off)
- … remote control mode switched off -
comm. interface available for standard
remote monitoring (protocol KMB only)
- IO … „I/O“-mode only (with up to 7 NRC86s)
- IO. … „I/O“-mode with actual PFC state
broadcast
- RCC … „RCC“-mode with optional
simultaneous „I/O“-mode (with up to 6
additional NRC86s)
- RCC. … „RCC“-mode with actual PFC state
broadcast
- RCCP … „RCCP“-mode (passive)
80 remote
controlled
target PF No. 1
÷ 5 ( in
„RCC“-mode )
0.80 L ÷ 0.80 C
0.01
1. = 0.95 C
2. = 0.97 C
3. = 1.00
4. = 0.97 L
5. = 0.95 L
individual remote controlled target PF values
EC1
÷÷÷÷
EC5 corresponding to remote
controlled PF serial number (par. 81) can be
set in a side branch
81 remote
controlled PF
serial number
( in „RCC“-
mode )
1 ÷ 5
1
3
the value is periodically read from the NRC86
unit
- slowly flashing dec. point indicates off-line
state; the value displayed corresponds to the
last read value
- slowly flashing dec. point indicates default
state 3 ( at long time off-line state )