6. NRC86 Remote Controller Technical Specifications
parameter
NRC86 Model
NRC86-85 24VDC
NRC86-07 230VAC
aux. supply voltage, power
18 ÷ 36 V DC, 4W
80 ÷ 275 V AC, 43 ÷ 67 Hz, 5 VA
100 ÷ 300 V DC, 5 W
number of output relays
5
7
output relay load rating
250 V AC / 4 A
110 V DC / 0.3 A
number of logic inputs
8
0
logic inputs parameters :
- character
- maximum voltage
- impedance
- voltage corresponding to „log. 0“
- voltage corresponding to „log. 1“
- serial number of remote controlled
PF switchover signal duration („log.
1”, RCC-mode)
galvanically isolated, polarity free
36 V DC
~ 5 kΩ
< 4 V DC
> 8 V DC
> 100 ms
communication interface
- type
- transmission rate
- protocol
- bias voltage impedance
- terminating resistor (TR)
RS-485, galvanically isolated
4.8 ÷ 19.2 kBaud
KMB / Modbus RTU
2 x 4.7 kΩ
330 Ω
working environment
class C1 in compliance with IEC 654-1
operating temperature
-40° ÷ +60°C
relative humidity
5 to 100 %
installation overvoltage class / level of
pollution
III-2 in compliance with EN 61010-1
EMC :
- noise suppression level
- immunity
EN 50081-2; EN 55011, class A; EN 55022, class A;
EN 61000-6-2
enclosure
IP 20
dimensions
106 x 100 x 58 mm
mass
max. 0.3 kg