Description

Novar Controls Corporation’s Heat Pump Controller (HPC) and the Heat Pump
Controller Plus (HPC Plus) are dedicated, direct digital control modules that
provide precise and integrated control for heat pump applications.

The HPC is applied to single-stage (1 H/1 C) heat pumps that energize the reversing
valve internally and require a “call for heat” or a “call for cooling” like a conventional
thermostat. It features a time delay that allows a loop water pump time to respond to
a call for heating or cooling before it actually energizes the heating or cooling outputs.

The HPC Plus energizes the reversing valve and compressors directly—it does
not contain a conventional heating or cooling output. Like the HPC, it
incorporates a compressor delay to allow time for a loop water pump to turn on
before energizing the compressors. The HPC Plus also features a special general
fault input to receive contact closure signals from a variety of safety switches.
This input can be used to initiate an alarm or shut down the heat pump unit when
the signal is received from the switch.

To select the proper unit for an application, examine the inputs and outputs of
these modules carefully.

This document provides procedures for mounting the HPC or HPC Plus,
connecting the power and network communications, wiring the inputs and
outputs, setting the module address, and checking installation.

NOTE! The HPC Plus requires an EP/2, Savvy, or Lingo as the

executive module. The HPC works with any executive module.

Specifications

Agency Approvals

UL, Energy Management

Listed Device: UL/CUL File #E90949

Equipment UL-916:

Power Requirements

Voltage:

24 VAC, Class 2

Consumption:

8 VA

Operating Environment

Temperature:

HPC: 32° to 100°F (0° to 38°C)
HPC Plus: –40° to 158°F (–40° to 70°C)

Humidity:

0 to 99% Relative, noncondensing

Physical Dimensions

Height:

5.5 inches

Width:

8 inches

Depth:

1.875 inches

Weight:

1.75 lb

DOC. #569062000

2/20/01

1

HPC/HPC Plus Installation Instructions

Summary of Contents for 738005000

Page 1: ...INTERFERENCE AND 2 THIS DEVICE MUST ACCEPT ANY INTERFERENCE RECEIVED INCLUDING INTERFERENCE THAT MAY CAUSE UNDESIRED OPERATION MAX ALLOWABLE AMBIENT TEMP 38 C 100 F 70 C 158 F REFER TO INSTALLATION I...

Page 2: ...tus does not exceed the Class B limits for radio noise emissions from digital apparatus set out in the interference causing equipment standard entitled Digital Apparatus ICES 003 of Industry Canada Ce...

Page 3: ...neral fault input to receive contact closure signals from a variety of safety switches This input can be used to initiate an alarm or shut down the heat pump unit when the signal is received from the...

Page 4: ...e 1 3 Drill holes at the locations marked on the mounting surface 4 Insert metal screws not included through the module and the mounting surface and tighten to secure the module 2 DOC 569062000 2 20 0...

Page 5: ...ections The inputs are Terminals 1 through 10 located on the left side of the terminal strip see Figure 2 NOTE On the HPC Plus Terminals 13 and 14 under the Analog Outputs label are used as a digital...

Page 6: ...abel Each HPC or HPC Plus must use a Remote Temperature Sensor RTS UVC for discharge air and one of the following sensors UVC Wall Mount Indoor Temperature Sensor WTS UVC Futura Temperature Sensor FTS...

Page 7: ...have a status LED The software defines the length of time that the override remains in effect The Futura Temperature Sensor provides an override switch and status LED Refer to the installation instru...

Page 8: ...lus Only The HPC Plus damper analog output terminals are listed under the label Analog Outputs immediately to the right of the input connections Figure 2 Step Procedure 1 Connect the damper actuator s...

Page 9: ...regulated switched through Terminals 21 26 A F The relay outputs are isolated from the other connections to permit the additional power source The transformer powering the module can be used if it ha...

Page 10: ...the address of the HPC or HPC Plus being installed Refer to Figure 3 and set the switches with the correct address from 00 to 63 If a Lingo is used as the executive processor address switches 64 127 d...

Page 11: ...ed for proper operation by pressing it during a scheduled off mode The LED flashes rapidly until the override period ends The six relay output status LEDs indicate the status of each active digital ou...

Page 12: ...This page intentionally left blank 10 DOC 569062000 2 20 01 HPC HPC Plus Installation Instructions...

Reviews: