BEFORE INSTALLING

If  the  modules  will  be  installed  in  an  existing  operational  system, 
inform the operator and local authority that the system will be tem-
porarily  out  of  service.  Disconnect  the  power  to  the  control  panel 
before installing the modules. This system contains static sensitive 
components. Always ground yourself with a proper wrist strap be-
fore handling any circuits so that static charges are removed from the 
body. The module housing should also be grounded.

NOTICE:

  This  manual  should  be  left  with  the  owner/user  

of this equipment.

GENERAL DESCRIPTION

The XP6-MA Six Zone Interface Module is intended for use in an 
intelligent alarm system. Each module provides an interface be-

N500-80-00 

I56-1806-006 

Notifier, 12 Clintonville Rd., Northford, CT 06472-1653 Phone: (203)484-7161

XP6-MA Six Zone Interface Module 

Installation And Maintenance Instructions

SPECIFICATIONS

Normal Operating Voltage: 

15-32VDC

Stand-By Current: 

2 mA

Alarm Current: 

40 mA (assumes all six LEDs solid on)

Temperature Range: 

32ºF to 120ºF ( 0ºC to 49ºC)

Humidity: 

10 to 93% Non-condensing

Dimensions: 

6.8˝H x 5.8˝W x 1.0˝D

Accessories: 

CHS-6 Chassis; BB-25 Cabinet; BB-XP Cabinet; CAB-4 Series Cabinets; CAB-3 Series Cabinets

Wire Gauge: 

12-18 AWG  

 

 

          

Maximum IDC Wiring Resistance: 

25 Ohms

External Power Supply Voltage: 

Regulated 24VDC

Ripple Voltage: 

0.1 volts RMS maximum

IDC (supervised and power limited)
 

DC Voltage: 

18-28 volts power limited

 

Frequency: 

DC     

 

Current: 

90mA per circuit

  DET.  

 

DETECTOR  

 MODEL 

COMP. ID 

MANUFACTURER 

BASE MODEL 

MAX DET.

  1151 

SYSTEM SENSOR 

B110LP, B401 

20

  1451 

SYSTEM SENSOR 

B401, B401B 

20

 1451DH 

SYSTEM SENSOR 

DH400 

20

  2151 

SYSTEM SENSOR 

B110LP, B401 

20

  2451 

SYSTEM SENSOR 

DH400, B401B, B401 

20

 2451TH 

SYSTEM SENSOR 

B401, B401B 

20

  5451 

SYSTEM SENSOR 

B401 

20

  1100 

SYSTEM SENSOR 

N/A 

20

  1400 

SYSTEM SENSOR 

N/A 

20

** 2100AT 

SYSTEM SENSOR 

N/A 

20

  2100B 

SYSTEM SENSOR 

N/A 

20

  2100D 

SYSTEM SENSOR 

N/A 

20

  2100S 

SYSTEM SENSOR 

N/A 

20

 2100TB 

SYSTEM SENSOR 

N/A 

20

 2100TD 

SYSTEM SENSOR 

N/A 

20

 2100TS 

SYSTEM SENSOR 

N/A 

20

  2300B 

SYSTEM SENSOR 

N/A 

20

 2300TB 

SYSTEM SENSOR 

N/A 

20

  2400 

SYSTEM SENSOR 

N/A 

20

 2400TH 

SYSTEM SENSOR 

N/A 

20

*  2W-B 

SYSTEM SENSOR 

N/A 

20

* 2W-TB 

SYSTEM SENSOR 

N/A 

20

 DH100LP 

SYSTEM SENSOR 

N/A 

20

* Class B, Style B only
** No Accessory will be supported by 2100AT

tween the intelligent alarm system and a conventional alarm sys-
tem loop. A common SLC input is used for all modules, and the 
initiating  device  loops  share  a  common  supervisory  supply  and 
ground. Otherwise, each monitor operates independently from the 
others. Each module has its own unique address.
A pair of rotary code switches is used to set the address of the first 
module from 01 to 154. The remaining modules are automatically 
assigned to the next five higher addresses. Provisions are included 
for disabling a maximum of two unused modules to release the 
addresses to be used elsewhere. Each module also has panel con-
trolled bicolor LED indicators. The panel can cause the LEDs to 
blink, latch on, or latch off.

Compatible Two-wire System Sensor Smoke Detectors for use with XP6-MA with Zone Identifier A

I56-1806-006