Figure. 7:

TENS

0

7 8

6

5

4

3

2

1

9

10

11

12

13

14

15

NOTE:

  Power  must  not  be  applied  to  the  unit  when  changing 

functionality of the shunts.

4.  A  shunt  is  provided  to  disable  a  maximum  of  two  unused 

modules in Class B operation and one unused module in Class 
A  operation.  Modules  are  disabled  from  the  highest  address 
and work downward.  If two modules are disabled, the lowest 
eight addresses will be functional, while the highest two will 
be disabled. For example, in Class B operation, if the shunt for 
Address Disable is placed on “two” and the base switch is set 
to 28, the modules will be assigned to 28, 29, 30, 31, 32, 33, 
34 and 35 while disabling the highest two positions.

5.  A  communications  loss  feature  is  available  on  some  panels. 

Upon a communication loss, due to a microprocessor failure at 
the control unit, the XP10-M will send a signal to the control 
unit to activate the notification device circuits upon initiating 
of an alarm on the XP10-M. A single shunt is used to enable 
(shunt on) or disable (shunt off) this feature for all modules 
on the board.

NOTE:

 Place unused shunts on single pin to store on board for  

 

future use.

WIRING NOTES

• Power-limited circuits must employ type FPL, FPLR, or FPLP   
  cable as required by Article 760 of the NEC.

PROGRAMMING

The  XP10-M  module  operates  with  the  following  Fire  Alarm 
Control Panels:
• AM2020/AFP1010

• AFP-200

• AFP-300/AFP-400

• S-5000 with AIM-200

• AFC-600

• NFS-640
• NFS-3030
The modules are programmed as devices in each system according 
to the programming instructions in the appropriate FACP manual.

N500-77-00 

I56-1803-007

Figure 6b. Installation of XP10-M module in front    
 

chassis position:

Step 1:   Insert the bottom edge of the XP10-M module down into 

a front slot of the chassis.

Step 2:    Carefully swing the upper edge of the board towards the 

back of the chassis until it touches the 1

1

4

˝ (31.75mm) 

standoffs installed on the rear module.

Step 3:    Align two 4-40 screws with the two standoffs and tighten.
Step 4:    Address and wire the modules according to the instruc-

tions in this manual.

WIRING

NOTE:

  All  wiring  must  conform  to  applicable  local  codes,  or-

dances, and regulations.

1.  Install module wiring in accordance with the job drawings and 

appropriate wiring diagrams.

2.  All wiring to the XP10-M is done via terminal blocks. In order 

to properly make electrical connections strip approximately 

1

4

˝ 

of insulation from the end of wire, sliding the bare end of the 
wire under the clamping plate screw.  

3.  Set the address on the modules per the job drawing. Use the 

rotary  code  switches  to  set  the  address  of  the  first  module 
(between 01 and 150).

In  Class  B  operation,  the  remaining  modules  are  automati-
cally  assigned  to  the  next  nine  higher  addresses.  For  exam- 
ple, if the base address switch is set to 28, the next nine modules 
will be addressed to 29, 30, 31, 32, 33, 34, 35, 36, and 37.

The module is shipped in Class B position, remove shunt for 
Class A.

  When operating in Class A, alternate modules are paired 

together (+0/+1, +2/+3, +4/+5, +6/+7, +8/+9), resulting 
in a total of five modules. For example, if the base address switch 
is set to 28, then 30, 32, 34 and 36 will be automatically assigned 
to  the  modules  while  29,  31,  33,  35  and  37  are  available  to  be 
used for other modules on the SLC. For Class A and B operation, 
DO NOT set the lowest address above 150, as the other modules 
will be assigned to nonexistent addresses.

NOTE:

  The  XP10-M  must  have  power  cycled  for  shunt  changes 

to take effect. 

NOTE:

  Some  panels  support  extended  addressing.  In  order  to 

set the module above address 99 on compatible systems, 
carefully remove the stop on the upper rotary switch (see 
Figure 7). If the panel does not support extended address-
ing, do not set the lowest address above 90.

FCC Statement

This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and (2) this 

device must accept any interference received, including interference that may cause undesired operation.

NOTE:

 This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to Part 15 of the FCC Rules. These limits are designed to 

provide reasonable  protection against harmful interference in a residential installation. This equipment generates,  uses and can radiate radio frequency energy and, if not 

installed and used in accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference will not 

occur in a particular installation.  If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off 

and on, the user is encouraged to try to correct the interference by one or more of the following measures:

 

 

– Reorient or relocate the receiving antenna.

 

 

– Increase the separation between the equipment and receiver.

 

 

– Connect the equipment into an outlet on a circuit different from that to which the receiver is connected.

 

 

– Consult the dealer or an experienced radio/TV technician for help.

C0226-00

C0227-00

2

3

1

Summary of Contents for XP10-M

Page 1: ...ltage 10 2 VDC Maximum IDC Current 240µA per device C0202 00 C0206 00 BEFORE INSTALLING If the modules will be installed in an existing operational system inform the operator and local authority that the system will be temporarily out of service Disconnect the power to the control panel before installing the modules This system contains static sensitive components Always ground yourself with a pro...

Page 2: ...l be installed in the chassis position in front of it Refer to Figures 6a and 6b for method two All necessary screws and standoffs are supplied with the modules Figure 5 Installation of rear module only method one Step 1 Insert the bottom of the XP10 M module down into a rear slot on the chassis Step 2 Carefully swing the upper edge of the board back towards the back of the chassis until it touche...

Page 3: ...g plate screw 3 Set the address on the modules per the job drawing Use the rotary code switches to set the address of the first module between 01 and 150 In Class B operation the remaining modules are automati cally assigned to the next nine higher addresses For exam ple if the base address switch is set to 28 the next nine modules will be addressed to 29 30 31 32 33 34 35 36 and 37 The module is ...

Page 4: ...structions NOTE Any number of UL listed contact closure devices may be used DO NOT mix fire alarm initiating and supervisory devices on the same initiating device circuit Install contact closure devices per manufacturer s installation instructions BASE ADDRESS TO NEXT DEVICE STATUS INDICATORS IDC ADDRESS 0 1 2 3 4 5 6 7 8 9 IDC ADDRESS IDC ADDRESS IDC ADDRESS IDC ADDRESS SLC FROM PANEL OR PREVIOUS...