Notifier NOTI-FIRE-NET Manual Download Page 5

General Description

NOTI•FIRE•NET™  PN 50257:E  7/5/01

5

General Description

NOTI•FIRE•NET™

 is a series of modules and products which allow a group of Fire Alarm 

Control Panels (FACPs) and other control equipment to connect, forming a true peer-to-peer 
network.

Network Nodes

Equipment that connects to 

NOTI•FIRE•NET™

 and communicates with other equipment using 

the network may be referred to as a network node.  The network supports communications over 
twisted pair wire and fiber optic media.  A combination of both wire and fiber may exist in the same 
network.  

NOTI•FIRE•NET™

 supports up to 103 nodes with a total capacity of 201,960 points.  

The following may all be network nodes:

AM2020/AFP1010 Fire Alarm System with a Network Serial Interface Board (SIB-NET) 
installed -

 The AM2020/AFP1010 FACP collects information about modules and peripherals 

connected to the network and makes this information accessible to all nodes connected to the 
network.  Information from the panel may include the following signals: fire alarm, security 
alarm, trouble, and supervisory.

AM2020/AFP1010 Fire Alarm System with a Network Adaptor Module (NAM-232) -

 The 

AM2020/AFP1010 occupies a single node address on the network.  This configuration has 
limited capability.  Functions are limited to the display of signals at an INA or NRT, network 
acknowledge, silence, and reset functions.  Other features such as  cooperative-control-by-
event, read status, alter status, etc. are not supported in this configuration.  Use of the NAM-
232 prevents use of a primary CRT at the panel.  

AFP-200 or AFP-300/AFP-400 with a Network Adaptor Module (NAM-232) -

 The AFP-200 or 

AFP-300/AFP-400 occupies a single node address on the network similar to an AM2020 or AFP1010.  
The NAM-232 connects to the AFP-200 or AFP300/AFP-400 through the EIA-232 serial 
communications port.  The network has the ability to send acknowledge, signal silence, drill, and reset 
commands to the AFP-200 or AFP-300/AFP-400.  AFP-200 or AFP-300/AFP-400 zones may be 
used to activate other network node devices.  Some NRT and INA functions are not supported in this 
configuration.   Use of the NAM-232 prevents use of a printer or CRT at the panel on the AFP-200.

Network Reporting Terminal (NRT) - 

The Network Reporting Terminal (NRT) is a computer-

based platform that allows the user to program network nodes (systems), display network 
information, and break the network into desirable groups of nodes.  The NRT can perform resets, 
signal silence, and acknowledge on sets of nodes.  The NRT also contains a history buffer which 
can record events and actions which have occurred in the network.  It works with 

NOTI•FIRE•NET™ 

software versions up to and including Software Version 2.8.

Network Control Station (NCS)

 - The Network Control Station (NCS) is similar to the NRT, 

providing a PC-based graphical interface for monitoring and controlling activity of multiple nodes 
on a network.  It allows the user to program network nodes, display network information, and break 
the network into desirable groups fo nodes.  It can perform resets, signal silence, and acknowledge 
on sets of nodes.  It also contains a history buffer which can record events and actions that have 
occurred in the network.  It works with 

NOTI•FIRE•NET™ 

Software Version 3.0.

Intelligent Network Annunciator (INA) - 

The Intelligent Network Annunciator (INA) can 

display and store network information.  The INA can perform resets, signal silence, and 
acknowledge on sets of nodes.  The INA has EIA-232 printer and CRT interfaces used to 
record/display network status, and an EIA-485 ACS interface.

Network Interface Boards

The Media Interface Board (MIB) provides a physical communication interface to the following 
medium which connects nodes together forming a network:

Twisted Pair Wire - MIB-W

Technical Manuals Online! - http://www.tech-man.com

firealarmresources.com

Summary of Contents for NOTI-FIRE-NET

Page 1: ...Document 50257 E 7 5 01 Rev E PN 50257 E ECN 01 146 NOTI FIRE NET Manual Technical Manuals Online http www tech man com firealarmresources com...

Page 2: ...proper storage of flammable materials etc Heat detectors do not sense particles of combustion and alarm only when heat on their sensors increases at a prede termined rate or reaches a predetermined le...

Page 3: ...ct AC power and batteries prior to removing or in serting circuit boards Failure to do so can damage circuits Remove all electronic assemblies prior to any drilling filing reaming or punching of the e...

Page 4: ...ons 13 Configuration Definitions 13 Characteristic Impedance In a Point to Point Configuration 14 Characteristic Impedance In a Bus Configuration 15 Terminating Point To Point and Bus Configurations 1...

Page 5: ...ons port The network has the ability to send acknowledge signal silence drill and reset commands to the AFP 200 or AFP 300 AFP 400 AFP 200 or AFP 300 AFP 400 zones may be used to activate other networ...

Page 6: ...s onto the NRT NET card to complete the network interface Each NRT or NCS requires a network node address The Repeaters RPT boost data signals between network nodes extending communication distances T...

Page 7: ...a fiber optic segment The following paragraphs detail each procedure Twisted Pair Circuits The length of cable for each segment in the system must fall within the range specified in Table 2 If the dis...

Page 8: ...100 Low 1200 2000 N A BRAND REX 93782 01 16 AWG 1 Pair Shielded Contact Manufacturer High 1 1400 1 100 Low 1200 2000 N A Genesis GJ 854020514 14 AWG 1 Pair Shielded FPLP NEC Article 760 High 1 400 1 1...

Page 9: ...t Number and Number of Gauges Conductors Manufacturer s Specifications Data Threshold All Nodes And Or Repeaters On A Cable Segment Permissible Single Twisted Pair Range In Feet For Each Cable Segment...

Page 10: ...ave to travel from one end of the network to the other end refer to Figure 2 The length is influenced by the total number of MIB NAM 232 RPT devices and medium along the circuit path Refer to Figure 3...

Page 11: ...A B C or D When employing the SIB NET a MIB W MIB WF or MIB F is required The SIB 2048A may also be used as a NOTI FIRE NET interface with the NAM 232 Initiating Devices Initiating device requirement...

Page 12: ...to the right of the break However the fragment to the right of the break can receive information from the fragment to the left of the break Figure 5 Fiber Optic Style 4 System Break Note A wire to wi...

Page 13: ...optic cable or mixed media wire and fiber Figure 6 Style 7 Configurations Configuration Definitions The following configurations are defined Point To Point Configuration A point to point wiring config...

Page 14: ...r network with more than two nodes Terminating resistors are only needed for the first and last nodes of the bus configuration all other terminating resistors must be removed In a bus configuration mo...

Page 15: ...upport point to point connections to the remaining buildings in the system Figure 9 Combination Wiring Terminating Point To Point and Bus Configurations Both point to point and bus configurations requ...

Page 16: ...R70 These point to point circuit segments are terminated at each node repeater A bus circuit spans multiple nodes repeaters with a terminating resistor at each end of the circuit segment A point to po...

Page 17: ...rations for point to point and bus wire configurations In the examples that follow the MIB WF or NAM 232W may be used in place of the MIB W Point To Point Configuration In a point to point configurati...

Page 18: ...s through switch SW3 is ON allowing the left node to provide ground fault detection for the two point to point wire connections on the left and right of the repeater The Port A switch on the right MIB...

Page 19: ...etection along the bus The primary difference is that one node can provide ground fault detection for multiple nodes along the bus refer to EXAMPLE 1 and 2 Note Refer to the Network Adaptor Module NAM...

Page 20: ...ft separate ground fault detection circuits must be fed through The node second from the right continues to provide ground fault detection up to the RPT W Port B and must be an AFP 200 AFP 300 AFP 400...

Page 21: ...ng with the supplied tie wrap at each end of the cylinder 4 If used repeat for the remaining twisted pair s on a MIB W second port Figure 19 Installation of the Ferrite Cylinder on the NRT NCS Install...

Page 22: ...22 NOTI FIRE NET PN 50257 E 7 5 01 Notes Technical Manuals Online http www tech man com firealarmresources com...

Page 23: ...ting constitutes the only warranty made by NOTIFIER with respect to its products NOTIFIER does not represent that its products will prevent any loss by fire or otherwise or that its products will in a...

Page 24: ...World Headquarters 12 Clintonville Road Northford CT 06472 1653 USA 203 484 7161 Fax 203 484 7118 www notifier com Technical Manuals Online http www tech man com firealarmresources com...

Reviews: