Notifier NOTI-FIRE-NET Manual Download Page 2

Precau-Lg.p65    01/18/2000

An automatic fire alarm system

–typically made up of smoke

detectors, heat detectors, manual pull stations, audible warn-
ing devices, and a fire alarm control with remote notification
capability–can provide early warning of a developing fire.
Such a system, however, does not assure protection against
property damage or loss of life resulting from a fire.

The Manufacturer recommends that smoke and/or heat detec-
tors be located throughout a protected premise following the
recommendations of the current edition of the National Fire
Protection Association Standard 72 (NFPA 72),
manufacturer's recommendations, State and local codes, and
the recommendations contained in the Guide for Proper Use
of System Smoke Detectors, which is made available at no
charge to all installing dealers.  A study by the Federal Emer-
gency Management Agency (an agency of the United States
government) indicated that smoke detectors may not go off in
as many as 35% of all fires.  While fire alarm systems are de-
signed to provide early warning against fire, they do not guar-
antee warning or protection against fire.  A fire alarm system
may not provide timely or adequate warning, or simply may not
function, for a variety of reasons:

Smoke detectors

 may not sense fire where smoke cannot

reach the detectors such as in chimneys, in or behind walls, on
roofs, or on the other side of closed doors.  Smoke detectors
also may not sense a fire on another level or floor of a build-
ing.  A second-floor detector, for example, may not sense a
first-floor or basement fire.

Particles of combustion or "smoke"

 from a developing fire

may not reach the sensing chambers of smoke detectors be-
cause:

• Barriers such as closed or partially closed doors, walls, or

chimneys may inhibit particle or smoke flow.

• Smoke particles may become "cold," stratify, and not reach

the ceiling or upper walls where detectors are located.

• Smoke particles may be blown away from detectors by air

outlets.

• Smoke detectors may be drawn into air returns before

reaching the detector.

The amount of "smoke" present may be insufficient to alarm
smoke detectors.  Smoke detectors are designed to alarm at
various levels of smoke density.  If such density levels are not
created by a developing fire at the location of detectors, the
detectors will not go into alarm.

Smoke detectors, even when working properly, have sensing
limitations.  Detectors that have photoelectronic sensing
chambers tend to detect smoldering fires better than flaming
fires, which have little visible smoke.  Detectors that have ion-
izing-type sensing chambers tend to detect fast-flaming fires
better than smoldering fires.  Because fires develop in differ-
ent ways and are often unpredictable in their growth, neither
type of detector is necessarily best and a given type of detec-
tor may not provide adequate warning of a fire.

Smoke detectors cannot be expected to provide adequate
warning of fires caused by arson, children playing with
matches (especially in bedrooms), smoking in bed, and violent
explosions (caused by escaping gas, improper storage of
flammable materials, etc.).

Heat detectors do not sense particles of combustion and
alarm only when heat on their sensors increases at a prede-
termined rate or reaches a predetermined level.  Rate-of-rise
heat detectors may be subject to reduced sensitivity over time.
For this reason, the rate-of-rise feature of each detector
should be tested at least once per year by a qualified fire pro-
tection specialist.  

Heat detectors are designed to protect

property, not life.

IMPORTANT! 

 Smoke detectors 

must be installed in the

same room as the control panel and in rooms used by the sys-
tem for the connection of alarm transmission wiring, communi-
cations, signaling, and/or power.  If detectors are not so lo-
cated, a developing fire may damage the alarm system, crip-
pling its ability to report a fire.

Audible warning devices

 such as bells may not alert people

if these devices are located on the other side of closed or
partly open doors or are located on another floor of a building.
Any warning device may fail to alert people with a disability or
those who have recently consumed drugs, alcohol or medica-
tion.  Please note that:

• Strobes can, under certain circumstances, cause seizures

in people with conditions such as epilepsy.

• Studies have shown that certain people, even when they

hear a fire alarm signal, do not respond or comprehend the
meaning of the signal.  It is the property owner's responsibil-
ity to conduct fire drills and other training exercise to make
people aware of fire alarm signals and instruct them on the
proper reaction to alarm signals.

• In rare instances, the sounding of a warning device can

cause temporary or permanent hearing loss.

A fire alarm system

 will not operate without any electrical

power.  If AC power fails, the system will operate from standby
batteries only for a specified time and only if the batteries
have been properly maintained and replaced regularly.

Equipment used in the system

 may not be technically com-

patible with the control.  It is essential to use only equipment
listed for service with your control panel.

Telephone lines

 needed to transmit alarm signals from a

premise to a central monitoring station may be out of service
or temporarily disabled. For added protection against tele-
phone line failure, backup radio transmission systems are rec-
ommended.

The most common cause

 of fire alarm malfunction is inade-

quate maintenance.  To keep the entire fire alarm system in
excellent working order, ongoing maintenance is required per
the manufacturer's recommendations, and UL and NFPA stan-
dards.  At a minimum, the requirements of Chapter 7 of NFPA
72 shall be followed.  Environments with large amounts of
dust, dirt or high air velocity require more frequent mainte-
nance.  A maintenance agreement should be arranged
through the local manufacturer's representative.  Maintenance
should be scheduled monthly or as required by National and/
or local fire codes and should be performed by authorized pro-
fessional fire alarm installers only.  Adequate written records
of all inspections should be kept.

While a fire alarm system may lower insurance
rates, it is not a substitute for fire insurance!

Fire Alarm System Limitations

Technical Manuals Online! - http://www.tech-man.com

firealarmresources.com

Summary of Contents for NOTI-FIRE-NET

Page 1: ...Document 50257 E 7 5 01 Rev E PN 50257 E ECN 01 146 NOTI FIRE NET Manual Technical Manuals Online http www tech man com firealarmresources com...

Page 2: ...proper storage of flammable materials etc Heat detectors do not sense particles of combustion and alarm only when heat on their sensors increases at a prede termined rate or reaches a predetermined le...

Page 3: ...ct AC power and batteries prior to removing or in serting circuit boards Failure to do so can damage circuits Remove all electronic assemblies prior to any drilling filing reaming or punching of the e...

Page 4: ...ons 13 Configuration Definitions 13 Characteristic Impedance In a Point to Point Configuration 14 Characteristic Impedance In a Bus Configuration 15 Terminating Point To Point and Bus Configurations 1...

Page 5: ...ons port The network has the ability to send acknowledge signal silence drill and reset commands to the AFP 200 or AFP 300 AFP 400 AFP 200 or AFP 300 AFP 400 zones may be used to activate other networ...

Page 6: ...s onto the NRT NET card to complete the network interface Each NRT or NCS requires a network node address The Repeaters RPT boost data signals between network nodes extending communication distances T...

Page 7: ...a fiber optic segment The following paragraphs detail each procedure Twisted Pair Circuits The length of cable for each segment in the system must fall within the range specified in Table 2 If the dis...

Page 8: ...100 Low 1200 2000 N A BRAND REX 93782 01 16 AWG 1 Pair Shielded Contact Manufacturer High 1 1400 1 100 Low 1200 2000 N A Genesis GJ 854020514 14 AWG 1 Pair Shielded FPLP NEC Article 760 High 1 400 1 1...

Page 9: ...t Number and Number of Gauges Conductors Manufacturer s Specifications Data Threshold All Nodes And Or Repeaters On A Cable Segment Permissible Single Twisted Pair Range In Feet For Each Cable Segment...

Page 10: ...ave to travel from one end of the network to the other end refer to Figure 2 The length is influenced by the total number of MIB NAM 232 RPT devices and medium along the circuit path Refer to Figure 3...

Page 11: ...A B C or D When employing the SIB NET a MIB W MIB WF or MIB F is required The SIB 2048A may also be used as a NOTI FIRE NET interface with the NAM 232 Initiating Devices Initiating device requirement...

Page 12: ...to the right of the break However the fragment to the right of the break can receive information from the fragment to the left of the break Figure 5 Fiber Optic Style 4 System Break Note A wire to wi...

Page 13: ...optic cable or mixed media wire and fiber Figure 6 Style 7 Configurations Configuration Definitions The following configurations are defined Point To Point Configuration A point to point wiring config...

Page 14: ...r network with more than two nodes Terminating resistors are only needed for the first and last nodes of the bus configuration all other terminating resistors must be removed In a bus configuration mo...

Page 15: ...upport point to point connections to the remaining buildings in the system Figure 9 Combination Wiring Terminating Point To Point and Bus Configurations Both point to point and bus configurations requ...

Page 16: ...R70 These point to point circuit segments are terminated at each node repeater A bus circuit spans multiple nodes repeaters with a terminating resistor at each end of the circuit segment A point to po...

Page 17: ...rations for point to point and bus wire configurations In the examples that follow the MIB WF or NAM 232W may be used in place of the MIB W Point To Point Configuration In a point to point configurati...

Page 18: ...s through switch SW3 is ON allowing the left node to provide ground fault detection for the two point to point wire connections on the left and right of the repeater The Port A switch on the right MIB...

Page 19: ...etection along the bus The primary difference is that one node can provide ground fault detection for multiple nodes along the bus refer to EXAMPLE 1 and 2 Note Refer to the Network Adaptor Module NAM...

Page 20: ...ft separate ground fault detection circuits must be fed through The node second from the right continues to provide ground fault detection up to the RPT W Port B and must be an AFP 200 AFP 300 AFP 400...

Page 21: ...ng with the supplied tie wrap at each end of the cylinder 4 If used repeat for the remaining twisted pair s on a MIB W second port Figure 19 Installation of the Ferrite Cylinder on the NRT NCS Install...

Page 22: ...22 NOTI FIRE NET PN 50257 E 7 5 01 Notes Technical Manuals Online http www tech man com firealarmresources com...

Page 23: ...ting constitutes the only warranty made by NOTIFIER with respect to its products NOTIFIER does not represent that its products will prevent any loss by fire or otherwise or that its products will in a...

Page 24: ...World Headquarters 12 Clintonville Road Northford CT 06472 1653 USA 203 484 7161 Fax 203 484 7118 www notifier com Technical Manuals Online http www tech man com firealarmresources com...

Reviews: