NFS-320/E/C Installation Manual —
P/N 52745:M2 7/1/14
33
Installing Remote Printers and/or CRT
Installation
Enter the CRT-2 setup menu by pressing and holding the <Ctrl> key while pressing the <Scroll
Lock> key. Use arrow keys to move through the selections in each setup group; press the space bar
to view the options for each parameter. When finished programming all setup groups, press the
<Pause> key. To save all changes, press <Y>.
Table 3.4 shows the standard settings for using the CRT-2 with the NFS-320/E/C; for one instance
where these settings may change slightly see Section 3.11.4 “Connecting Multiple Printers, CRTs,
or CRT/PRN Combination”. The basic settings for using the CRT-2 with NFS-320/E/C are:
• Baud Rate 9600 • Data format 8 1 N • Protocol xon/off.
3.11.4 Connecting Multiple Printers, CRTs, or CRT/PRN
Combination
Connecting multiple devices requires changing the CRT-2 setup using the F1(Quick) menu:
NOTE:
This section covers installation only; for information on how the CRT-2 functions as part
of the fire alarm system, see the
NFS-320/E/C Operations Manual
.
NOTE:
The CRT cannot be connected at the same time as the network.
Function Key
CRT-2 Parameters
F1: Quick
(“Read Status” key)
Emulation=CRT-2
Comm Mode=Full Duplex
Enhanced=On
EIA Baud Rate=9600
Aux Baud Rate=9600
Language=U.S.
EIA Data Format=8/1/N
Aux Data Format=8/1/N
Host/Printer=EIA/Aux
F2:Genrl
(“Alter Status” key)
Emulation=CRT-2
Auto Font Load=On
Monitor Mode=Off
Host/Printer=EIA/Aux
Enhanced=On
Auto Page=Off
Bell Volume=09
Auto Wrap=Off
Auto Scroll=On
Warning Bell=On
F3: Displ
(“Prog” key)
Page Length=24
Display Cursor=On
Columns=80
Scroll=Jump
Screen Length=26 Lines
Cursor=Blink Line
Width Change Clear=Off
Refresh Rate=60 Hz
Screen Video=Normal
Auto Adjust Cursor=On
Speed=Normal
Overscan Borders=Off
F4: Kybd
(“Spl Funct” key)
Language=U.S.
Keyclick=Off
Key Lock=Caps
Char Set Mode=ASCII
Key Repeat=Off
Keyboard Present=Yes
Key Mode=ASCII
Margin Bell=Off
F5: Keys
(“Prior” key)
Enter Key=<CR>
Alt Key=Meta
Pound Key=U.S.
Return Key=<CR>
Disconnect=Pause
Backspace=<BS>/<DEL>
Desk Acc=Disabled
F6: Ports
(“Next” key)
EIA Baud Rate=9600
Aux Baud Rate=9600
EIA Xmt=Xon-Xoff
Aux Xmt=Xon-Xoff
EIA Break=Off
Aux Break=Off
EIA Data Format=8/1/N
Aux Data Format=8/1/N
EIA Recv=Xon-Xoff(XPC)
Aux Recv=Xon-Xoff(XPC)
EIA Modem Control=Off
Aux Modem Control=Off
EIA Parity Check=On
Aux Parity Check=On
EIA Xmt Pace=Baud
Aux Xmt Pace=Baud
EIA Disconnect=2 sec
Aux Disconnect=2 sec
F7: Host
(“Auto Step” key)
Comm Mode=Full Duplex
Recv <DEL>=Ignore
Send Block Term=<CR>
Local=Off
Send ACK=On
Null Suppress=On
Recv <CR>=<CR>
Send Line Term=<CR><LF>
F8: Print
(“Activ Signal” key)
Prnt Line Term=<CR><LF>
Prnt Block Term=<CR>
Secondary Recv=Off
F9: Emul
Attribute=Page
WPRT Intensity=Dim
WPRT Blink=Off
Status Line=Off
Bright Video=Off
WPRT Reverse=Off
Display NV Labels=Off
Fkey Speed=Normal
Page Edit=Off
WPRT Underline=Off
Save Labels=On
F10
Setup Group F10 does not affect communications with the control panel.
F11
Setup Group F11 does not affect communications with the control panel.
F12: Prog
(“Ack Step” key)
Program the function keys as follows: F1 ~A F2 ~B F3 ~C F4 ~D F5 ~E F6 ~F F7 ~G
F8 ~H F9 ~I F10 ~J F11 ~K F12 ~L F13 ~M F14 ~N F15 ~O F16 ~P Shift F13 ~Q
Table 3.4 Standard CRT-2 Settings for Use with NFS-320/E/C