background image

NBG-12LA Wiring

From FACP

IDC

12345678

12345678

12345678

1234

1234

1234

1234

1234

1234

1234

1234

1234

1234

1234

To Next Device
IDC

Aux. Contact

Aux. Contact

12LA

wiring.wmf

NBG12-Active.wmf

NBG-12LA Pull Station

(Shown Activated)

Document 51300 Revision A1    ECN: 01-293   09/14/01

CAUTION

Install the pull station in accordance with the supplied instructions, applicable NFPA standards, national and local Fire and Electrical

codes and the requirements of the Authority Having Jurisdiction (AHJ).  Conduct regular testing of the devices using appropriate

NFPA standards.  Notifier is not responsible for devices that have not been properly installed, tested or maintained.  For ADA

compliance, if the clear floor space only allows forward approach to an object, the maximum forward reach height allowed is

48 inches (121.92cm).  If the clear floor space allows parallel approach by a person in a wheelchair, the maximum side reach height

allowed is 54 inches (137.16cm).

Wiring Instructions

1) Before mounting the pull station, pull all necessary wiring

through the backbox.

2) Remove the correct amount of wire insulation.  The pull

station’s backplate is molded with a strip gauge to measure

the amount of insulation to be removed.

3) Connect  the  wiring  from  the  fire  alarm  control  panel’s

Initiating Device Circuit (IDC), or any previous device on

the IDC to terminals 1 and 2 located on the pull station’s

terminal strip.  Connect the next device on the IDC or End-

of-Line Resistor (ELR) to terminals 1 and 2.  Note:  Maintain

consistent polarity with all connections throughout the IDC.

4) Connect the wiring for the normally open (N/O) auxiliary

switch circuit to terminals 3 & 4.

Operation

To activate the dual-action station, first push in the handle, and

then pull the handle down.  The handle locks into the activated

position. The word ‘ACTIVATED’ appears after the handle is

pulled down.  The pull station remains in the activated position

until reset with the key lock.
1) Reset the NBG-12LA by inserting the key into the lock and

turning it ¼ turn (counter-clockwise).

2) Open the door until the handle returns to the ‘NORMAL’

position.

3) Close and lock the door.  Closing the door automatically

resets the switch to the ‘NORMAL’ position.  Note: Opening

the pull station door will not activate or deactivate the FACP

alarm switch or the auxiliary function switch.