Notifier LCD-160 Manual Download Page 16

16

LCD-160 P/N 51850:A  09/26/2003

Section 5  Mounting

This section describes how to mount the LCD-160 into an enclosure.

5.1  Mount the Cabinet or Backbox 

Select an appropriate knockout on the enclosure for your wiring to run 
through and snap it out. Fasten the cabinet or backbox to the wall. 
Ground the enclosure to a solid metallic ground, such as a grounded cold 
water pipe. Pull all LCD-160 wiring into the enclosure as illustrated in 
Figure 4. Connect LCD-160 wiring to the removable terminal blocks as 
specified in “Connecting the RDP Bus” on page 19. 

5.2  Mount the LCD-160 

In an CAB-4 Series backbox:

1. Place the annunciator/dress-plate assembly into the backbox and secure with four screws.

2. Plug the two annunciator 

terminal blocks into the 
annunciator to complete 
communication and power circuit 
connections as described on 
“Connecting the RDP Bus” on 
page 19
 and “Power Supply 
Connections” on page 21. 

3. If using a semi-flush-mount 

backbox, attach the door. Align 
the door with the dress plate, and 
slide the door down onto the pins 
on the dress plate. When 
positioned correctly, the door will 
open and close freely.

In an ABS-2D/4D or ABF-2B/4B 
backbox:

1. Plug the two annunciator terminal blocks into the annunciator to complete communication and 

power circuit connections as described in “Connecting the RDP Bus” on page 19 and “Power 
Supply Connections” on page 21.

2. Place the annunciator/dress-plate assembly into the backbox and secure with four screws.

3.  If using a semi-flush-mount backbox, attach the door. Align the door with the dress plate, and slide 

the door down onto the pins on the dress plate. When positioned correctly, the door will open and 
close freely.

!

A

WARNING:

Use a grounding strap before handling any circuits so that static charges are removed 

from the body.

Figure 4 Pull Wiring 

into Enclosure

A

nW

ir_

in

.tif

Figure 5 Mounting the LCD-160 to the Dress Panel

Mounting Screws

Mounting Screws

Summary of Contents for LCD-160

Page 1: ...A P N 51850 A ECN 03 419 Document 51850 09 26 2003 Rev Liquid Crystal Display LCD 160 Manual...

Page 2: ...ate warning of fires caused by arson children playing with matches especially in bedrooms smoking in bed and violent explosions caused by escaping gas improper storage of flammable materials etc Heat...

Page 3: ...l electronic assemblies prior to any drilling filing reaming or punching of the enclosure When possible make all cable entries from the sides or rear Before making modifi cations verify that they will...

Page 4: ...information Product name and version number if applicable Printed manual or online Help Topic Title for online Help Page number for printed manual Brief description of content you think should be imp...

Page 5: ...l Hardware 15 Section 5 Mounting 16 Mount the Cabinet or Backbox 16 Mount the LCD 160 16 In an CAB 4 Series backbox 16 In an ABS 2D 4D or ABF 2B 4B backbox 16 Section 6 Wiring 17 Overview 17 The RDP B...

Page 6: ...hic Screen 32 Programming Screens 33 Setting the Programming Switch 33 Panel Program Menu 34 LCD Display 35 Programming Confirmation Dialog 36 Operating Screens 37 Event Counts Display 37 More Informa...

Page 7: ...ipment damage irreversible loss of programming data or personal injury Table 1 1 Typographic Conventions in this Manual When you see Specifies Example text in all caps and bold text In body text text...

Page 8: ...or the Installation of Fire Alarm Systems Applicable Local and State Building Codes Requirements of the Local Authority Having Jurisdiction The Canadian Electrical Code Part 1 2 1 Related Documentatio...

Page 9: ...ort diagnostics Software upgrades and foreign languages character sets via serial port from a panel or other device via the Remote Data Port RDP interface Upgrades do not require the replacement of an...

Page 10: ...rd layout is illustrated in Figure 1 J1 Key Switch LED 13 Transmit LED 12 Receive SW17 LED14 MicroFail LED11 Status TB2 Power TB1 RDP Port See Figure 11 See Figure 8 See Figure 13 See Figures 9 and 21...

Page 11: ...ough 10 indicate system status and are visible to the user See Status LED Indicators on page 25 for information on LED indicators 1 10 Table 3 1 Diagnostic LED Indicators Reference LED Name Color Desc...

Page 12: ...12 LCD 160 P N 51850 A 09 26 2003 System Overview Features and Specifications...

Page 13: ...7 Mount the dress panel to the backbox 8 Make all electrical connections RDP bus shielding if necessary Figures 7 8 Power circuit Figure 11 9 Attach doors to backboxes Section 5 2 10 Power up system...

Page 14: ...semi flush enclosure for mounting one to four rows of equipment plus batteries up to two 25AH batteries There are four different sizes available The separately ordered doors can be mounted on the lef...

Page 15: ...y to threaded studs on the dress panel An LCD 160 mounted on an ADP 4B fits in front of most CAB 4 series chassis as long as the top layer of the chassis is displayless or unoccupied Figure 3 ADP 4B s...

Page 16: ...on page 19 and Power Supply Connections on page 21 3 If using a semi flush mount backbox attach the door Align the door with the dress plate and slide the door down onto the pins on the dress plate Wh...

Page 17: ...different knockouts Install tie wraps and adhesive squares to secure the wiring WARNING Remove all power sources to equipment while connecting electrical components Leave the external main power break...

Page 18: ...e the RDP bus as shown in Connecting the RDP Bus on page 19 These requirements must be followed There is a maximum of 4000 feet at 12 AWG to 18 AWG between the panel and the last device on the RDP bus...

Page 19: ...vides RDP circuit diagrams for the LCD 160 See RDP Bus Wiring Specifications on page 18 for circuit requirements End of Line Resistor for RDP Devices If the LCD 160 is the last device on the RDP bus t...

Page 20: ...earth ground such as a cold water pipe Connect the LCD 160 s Earth Ground located on the RDP interface to a mounting screw on the backbox or cabinet See Figures 8 and 10 Figure 9 SW17 ELR Disabled LC...

Page 21: ...n have ground fault detection enabled The power run to the LCD 160 need not contain a Power Supervision Relay because loss of power is inherently supervised through communication loss loss of RDP comm...

Page 22: ...etection disabled Common Reference LCD 160 Remote Power Supply A caba3 wmf Fire Alarm Control Panel Two wire RDP bus Power Loop When more than one power supply is used on an RDP bus a common reference...

Page 23: ...well as other information Enter or change fields and issue commands on the display by using both the fixed function and soft keys on the keypad 7 2 The Keypad The keypad consists of two types of keys...

Page 24: ...to the appropriate FACP manual for further information about this function SYSTEM RESET Press this key to send a system reset command to the panel The exact action to take on a reset command is contr...

Page 25: ...dged Security Blue Illuminates when at least one security event exists It will flash if any of these events are unacknowledged Supervisory Yellow Illuminates when at least one supervisory event exists...

Page 26: ...40 characters long Line one is a custom message Line two is a standard message showing the System Normal status Line five indicates the current time and date Event Reporting Format When there is an o...

Page 27: ...been acknowledged or cleared Event Format nottrouble or pre alarm Event Format trouble Line 1 DisplaysPREALARM the sensitivity reading and whether it has been acknowledged or cleared PREALARM 120 OF...

Page 28: ...Event Display Example The event counts section shows the counts for outstanding events The date in line eight gives the current time The soft keys may be used to deal with the event their functions ar...

Page 29: ...CC all remote displays with Local Control ON will automatically participate Refer to the FACP programming manual for more information When an LCD 160 is not the DCC pressing Signal Silence System Rese...

Page 30: ...ntrol to the requesting device NO Press this key to deny control to the requesting device FIRE ALARM ELEVATOR LOBBY EAST WING FIFTH FLOOR Z005 SMOKE PHOTO 11 57 45A WED JUN 26 2003 N112L03D052 RELEASE...

Page 31: ...individually event acknowledge or as a group block acknowledge Event Acknowledge Event acknowledge acknowledges off normal events one at a time you must press the acknowledge key once for each event t...

Page 32: ...Program screen This option will not be visible if any unacknowledged fire alarms exist or if the programming switch is disabled See pages 33 34 GRAPHIC SCREEN Press this key to display the Graphic Sc...

Page 33: ...arm present Setting the Programming Switch The LCD 160 s programming switch must be enabled to program the LCD 160 Set dip switch 1 on SW17 to permit programming on the LCD 160 SW17 is located on the...

Page 34: ...bled Refer to Setting the Programming Switch on page 33 SOFT KEYS ADDRESS CHANGE Press this key to increase the LCD 160 s address on the RDP bus The address will cycle from 1 to 32 PIEZO Press this ke...

Page 35: ...by 4 BACKLIGHT Pressing this key toggle the status of the backlight between ON OFF and ON EXCEPT AC FAIL DEFAULT Press this key to revert all screen preferences to their factory settings ACCEPT Press...

Page 36: ...atabase and reminds them not to power off the system during the update SOFT KEYS YES Press this key to write the changes you made in the Panel Program Menu and the LCD Display screen to the database N...

Page 37: ...ge 26 Lines six and seven display current counts of off normal events in six categories The counts include both acknowledged and unacknowledged events During an off normal event line eight will displa...

Page 38: ...event information on the More Information screen PROGRAM Press this key to go to the Panel Program Menu This option will not be visible if any unacknowledged fire alarms exist or if the programming sw...

Page 39: ...eding the prealarm level by 45 Line 12 ALARM 6 1 66 Six is the preprogrammed alarm level value for this detector its value is 1 66 indicating the percent per foot obscuration value assigned to level 6...

Page 40: ...e address es of any detector s linked with the detector that is in alarm for Co operative Multi alarm Sensing This field does not display for Acclimate detectors Line 15 The line displays the current...

Page 41: ...g one of the Scroll Display fixed function keys will cause the first event of that type e g alarm trouble etc to display at the top and subsequent events of that type to display in sequence below it I...

Page 42: ...n event list This option will change to MAIN MENU when the FIRST EVENT key is pressed ACKNOWLEDGED FIRE ALARM ELEVATOR LOBBY EAST WING FIFTH FLOOR Z005 SMOKE PHOTO 11 57 45A WED JUN 26 2003 N112L03D05...

Page 43: ...e screen as they are completed Failure of a test may prevent the LCD 160 from performing its functions Holding the DRILL key during the power up will reset all settings including address information t...

Page 44: ...may use the TROUBLE scroll display key to list individual troubles Download Application Screen This screen is displayed during application downloads Downloading is initiated at the FACP The progress...

Page 45: ...der Screen Download Strings Screen This screen is displayed during strings downloads Downloading strings is initiated at the FACP The progress meter shows the progress of the current download Figure 3...

Page 46: ...cation code Usually this screen results from a power interrupt during a critical period of application download The Trouble LED will flash and the piezo if enabled will sound while this screen is in e...

Page 47: ...l Ratings Input Voltage 24 VDC must be non resettable Data Communications Port RDP interface power limited Table 9 1 LCD 160 Current Draw Non Fire Alarm Status A Power LED is on backlight is off Numbe...

Page 48: ...48 LCD 160 P N 51850 A 09 26 2003 Screen Displays Service Screens...

Page 49: ...t Scroll Display key 24 Display and Control Center 24 29 30 Display intensity 35 Download screens 44 45 DP DISP 15 Dress Panels 15 16 Drill and Power up screen 43 fixed function key 24 E Earth Ground...

Page 50: ...LED indicator 11 Remote Data Port see RDP S Scroll Back 42 SCROLL DISPLAY keys 24 Security events 31 event format 27 LED indicator 25 SCROLL DISPLAY key 24 Self Test Screen see Power Up Screen Servic...

Page 51: ...nville Road Northford Connecticut 06472 1653 This writing constitutes the only warranty made by NOTIFIER with respect to its products NOTIFIER does not represent that its products will prevent any los...

Page 52: ...World Headquarters 12 Clintonville Road Northford CT 06472 1653 USA 203 484 7161 fax 203 484 7118 www notifier com NOTIFIER is a company...

Reviews: