2.5 Indicator leds:

 

 

 

ON Led 

 

 

This led is ON when the Control Unit is powered. 

 

 
 

Fault Led 

 

 

Yellow led that is ON in case of a Power Supply Fault. When 
this indication is activated, the C and NC contacts of the fault 
relay will be closed. 

 

 

MAINS SUPPLY FAULT Led  
 

Power Supply is not detected by the Control Unit and it is 
powered by batteries. The internal led BAT-DIS is also 
activated. 
The led is ON immediately after detecting power. However, the 
fault relay signal and the FAULT led do not activate until the 
power supply fault remains for more than 8 minutes.

 

 

 
 

BATTERY FAULT Led

 

 
Battery is not detected by the Control Unit or the battery voltage 
is below 22.4 Vdc, i.e., the 50% of its capacity. 
The FAULT Led and the fault relay signal are also activated.  
 
In case the internal led LOW BAT is flashing it means that the 
battery voltage is close to 22.4 Vdc. 

 

When the battery voltage is lower than 20.4 Vdc, both outputs, 
PSO1 and PSO2, and the Output 1 and 2 leds will indicate a 
fault condition.   
 
The FAULT Led and the fault relay signal are also activated  

 

 

 
 

BATTERY CHARGER FAULT Led 

 

 

This led is on when there is a battery charger fault.

 

 
 

Summary of Contents for HLSPS25-XP

Page 1: ...Power Supply Unit HLS PS Series HLSPS25 XP and HLSPS50 XP User manual Information in this document is subject to change without notice 8 APRIL 2010 MN DT 1305I_B...

Page 2: ...HLS PS25 HLS PS50 User Manual MN DT 1305I_B 2...

Page 3: ...HLS PS for damage 4 1 2 Pre installation check list 5 1 3 Transient protection 5 1 4 Cleaning 5 1 5 Back Box HLS PS fixing 6 2 Functions and indicators 7 2 1 HLS PS25 and HLS PS50 characteristics 8 2...

Page 4: ...lity of any supplied order items follow the procedure bellow 1 If after removing the HLS PS Series a visual inspection reveals that it has been damaged you MUST NOT continue with the installation but...

Page 5: ...may operate erratically or can be damaged if subjected to lightning induced transients This equipment contains transient protection devices Although no system is immune from lightning transients and i...

Page 6: ...y in the required position against the wall and mark the position of the fixing holes while ensuring the panel is level The drawing below shows the position of the fixing holes at the back box Do NOT...

Page 7: ...ions and indicators FRONT PANEL 1 2 FUS BAT FAULT LOW BAT NO BAT BAT TEST BAT CH BAT DIS IN ALARM 321087 CPU MAX LEGEND ON FAULT MAIN SUPPLY FAULT BATTERY FAULT BATTERY CHARGER FAULT OUTPUT 1 FAULT OU...

Page 8: ...tandard module control which supervises the entire power supply HLS PS25 and HLS PS50 power supplies provide 2 5 Amp and 5 Amp respectively and 300mA to 600mA of them are dedicated to charge batteries...

Page 9: ...control unit Any fault has a delay of 30 seconds from the fault signal to fault relay confirmation except when there is a mains AC loss which will be indicated after an 8 minute delay to avoid faults...

Page 10: ...arm input to disable momentarily the battery charger and be able to supply 300 600mA from battery load to the outputs For this it is necessary to link both IN ALARM terminals by means of a jumper or s...

Page 11: ...n case batteries fail a Battery fault will be reported The HLS PS Series will supervise automatically the battery each 3 hours If the battery load is in normal condition the fault signal will disappea...

Page 12: ...e fault relay signal and the FAULT led do not activate until the power supply fault remains for more than 8 minutes BATTERY FAULT Led Battery is not detected by the Control Unit or the battery voltage...

Page 13: ...will not be earth fault supervision Earth fault solution Make sure that there are no links between Earth and Output 1 and 2 y OVERLOAD Led Indicates that the equipment exceeds the maximum current 5 A...

Page 14: ...g both terminals with a jumper or short circuit this input allows the battery charger momentary disablement in order to provide extra 300 600 mA to the outputs Battery load current 300 mA 7 Amp hour 6...

Page 15: ...HLS PS25 HLS PS50 User Manual MN DT 1305I_B 15...

Page 16: ...www honeywelllifesafety es Honeywell Life Safety Charles Avenue Burgess Hill RH15 9UF West Sussex Tel 44 0 1444 230 300 England Avenue de L Expansion 16 D B 4432 Alleur Tel 32 0 4 247 03 00 Belgium w...

Reviews: