background image

N500-53-00                                                                                                     2                                                                                                  I56-1230-06R

© 2001 Notifier 

A.  Functional: Magnet Test (P/N M02-04-01 or M02-09-00)

 

      This sensor can be functionally tested with a test magnet. The test magnet electronically simulates smoke in the sensing chamber, testing the sensor elec-

tronics and connections to the control panel.

      1. Hold the test magnet in the magnet test area as shown.
      2. The sensor should alarm the panel.
      Two LEDs on the sensor are controlled by the panel to indicate sensor status. Coded signals, transmitted from the panel, can cause the LEDs to blink, latch 

on, or latch off. Refer to the control panel technical documentation for sensor LED status operation and expected delay to alarm.

B.  Smoke Entry: Aerosol Generator (Gemini 501) 

      The GEMINI model 501 aerosol generator can be used for smoke entry testing. Set the generator to represent 4%/ft to 5%/ft obscuration as described in 

the GEMINI 501 manual. Using the bowl shaped applicator, apply aerosol until the panel alarms.

C.  Direct Heat Method (Hair dryer of 1000-1500 watts). FSP-751T only.

      Direct the heat toward either of the side thermistors. Hold the heat source about 12 inches from the detector in order to avoid damage to the plastic. The 

detector will reset only after it has had sufficient time to cool.

Both smoke and heat detection testing are recommended for verifying system protection capability.

A sensor that fails any of these tests should be cleaned as described under 

CLEANING

, and retested. If the sensor fails after cleaning, it must be replaced and 

returned for repair.

When testing is complete, restore the system to normal operation and notify the proper authorities that the system is back in operation.

HIGH SENSITIVITY SETTING

The use of the 0.2% to 0.5% per foot sensitivity setting requires a 90-day test period to ensure that the detector’s environment is suitable for this setting. The 
following steps must be followed to meet Notifier and UL requirements for this high sensitivity application:
1.   Each detector intended for 0.2% to 0.5% per foot alarm application shall have its initial alarm setting set for 0.5% obscuration per foot alarm level. The initial 

prealarm setting for the detector shall be set to the intended alarm setting of the system. Prealarm shall be set for nonlatching operation.

2.   Detectors set at 0.2% to 0.5% per foot are intended for use in smoke-free, environmentally controlled applications, such as computer rooms and clean rooms. 

In order to determine if an environment is suitable for installation, the detectors shall be operated continuously for 90 days with all environmental factors, 
including temperature, humidity, air flow, occupancy, etc., similar to the intended application for these detectors. An electronic history file or printer shall be 
used to record all events associated with the detectors under testing.

3.   At the end of 90 days, the results of the test shall be inspected by an authorized Notifier representative or the end user, if trained by an authorized Notifier 

representative. If no alarms or prealarms are recorded for the detectors under testing, the system may be set to the tested prealarm level in the 0.2% to 
0.5% per foot range.

CLEANING

It is recommended that the detector be removed from its mounting base to facilitate cleaning. The detector is cleaned as follows:

NOTE:

     Before removing the detector, notify the proper authorities that the smoke detector system is undergoing maintenance and will be temporarily out of 

service. Disable the zone or system undergoing maintenance to prevent unwanted alarms.

1.   Remove the detector cover by prying away the four side tabs with a small-bladed screwdriver, and then
      pulling the cover from the base.
2.   Vacuum the screen carefully without removing it. If further cleaning is required continue with Step 3,
      otherwise skip to Step 8.
3.   Remove the screen assembly by pulling it straight out (see Figure 4).
4.   Remove the sensing chamber cover by pulling it straight out.
5.   Clean the vaned chamber piece by vacuuming or blowing out dust and particles.
6.   Replace the sensing chamber cover, aligning the arrow on the top with arrow on the printed circuit board.
7.   To replace the screen, place it over the chamber assembly, turning it until it snaps into place.
8.   Replace the cover using the LEDs to align the cover and then gently pushing it until it locks into place.
9.   Reinstall the detector.
10. Test the detector as described in TESTING.
11. Reconnect disabled circuits.
12. Notify the proper authorities that the system is back on line.

A78-2463-18

Figure 4.

SENSOR

COVER

SENSING

CHAMBER

SENSING

CHAMBER

COVER

SENSOR

SCREEN

COVER REMOVAL

TABS

FCC Statement

This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and (2) this 

device must accept any interference received, including interference that may cause undesired operation.
Note:   This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to Part 15 of the FCC Rules. These limits are designed 

to provide reasonable  protection against harmful interference in a residential installation. This equipment generates, uses and can radiate radio frequency energy and, if 

not installed and used in accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference will 

not occur in a particular installation.  If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment 

off and on, the user is encouraged to try to correct the interference by one or more of the following measures:
             

– Reorient or relocate the receiving antenna.

             

– Increase the separation between the equipment and receiver.

             

– Connect the equipment into an outlet on a circuit different from that to which the receiver is connected.

             

– Consult the dealer or an experienced radio/TV technician for help.

Please refer to insert for the Limitations of Fire Alarm Systems

www.PDF-Zoo.com

Reviews: