Releasing Applications
Applications
4. Do not loop wiring under the screw terminals. Break the wire run to provide supervision of
connections.
5. All applications using the FCM-1-REL are power-limited:
a.
Program the releasing circuit for Type Code REL CKT ULC or RELEASE CKT.
b. Circuits are supervised against opens and shorts.
6. Refer to the
IQ-318/E Programming Manual
for instructions on setting the Soak Timer.
The FCM-1-REL module must be programmed with the correct releasing type code listed in the
IQ-318/E Programming Manual
.
4.7.7 Connecting an NBG-12LRA Agent Release-Abort Station
NOTE:
If using the on-board NACs, see Circuit Requirements for Section 4.7.4 “Connecting a
Releasing Device to the Control Panel” on page 42. If using FCM-1, see Circuit Requirements for
Section 4.7.5 “Connecting a Releasing Device to the FCM-1 Module” on page 44.
SLC loop to
FACP
FCM-1
FRM-1
FMM-1
FMM-101
Black
Red
Yellow
Violet
Black
Red
Non-rese24 VDC
from main power supply
Manual Abort
Manual Release
Normal
Release
NBG-12LRA
See Document 51369
for installation details.
ELR mode R-47K
supervised and
power-limited
Red
Brown
24 VDC UL-listed
releasing device
C.
N.O.
REL-47K
(use with Type Code
Rel Ckt ULC)
NF
S
6
40
-NB
G
12
LR
At
p
H
.w
mf
System
Common (–)
24 VDC power
from FACP’s
main power supply
N.C.
Power Supervision
Relay (EOLR-1)
N.C. Supervision
Relay Contact
Figure 4.14 Typical Connections for an NBG-12LRA Agent Release-Abort Station
Polarity shown in
an energized
state.
*If the SLC device does
not match the one in this
figure, refer to the SLC
manual appendix, which
contains wiring conver-
sion charts for type V and
type H modules.