44
IQ-318/E/C Installation Manual —
P/N 52864:J3 9/29/15
Applications
Releasing Applications
Figure 4.10 Releasing Circuits (Option 3)
)
Figure 4.11 Release Circuits (Mechanical Disconnect Switch)
4.7.5 Connecting a Releasing Device to the FCM-1 Module
The module can control 1 A of current. Make sure to keep total system current within the limits of
the power supply. You can power the module from the power supply of the Control Panel or any
UL/ULC listed 24 VDC regulated power-limited power supply for Fire Protective Signaling. For
more information, refer to the
Device Compatibility Document
.
Circuit Requirements
When connecting a releasing device to the FCM-1 module, note the
following:
1. Refer to the Releasing Applications appendix in the
IQ-318/E Programming Manual
for
configuration details (such as setting the Soak Timer).
IQAct
uat
o
rs
b.
w
m
f
Ga
sDi
sco
nn
ect.
w
m
f
–
+
–
Compatible UL-listed
24 VDC releasing device
REL-47K
(Use with Type Code
Rel Ckt ULC,
or see Circuit
Requirement 3.)
Brown
Red
Non-resettable
24 VDC Power
Power Supervision
Relay (EOLR-1)
Re
lco
nn
-fcmtpH
.w
m
f
+ –
FCM-1
–
+
SLC from FACP
Note: See text for circuit requirements.
N.C. Supervision
Relay Contact
Part of EOLR-1
*If the SLC device does
not match the one in this
figure, refer to the SLC
manual appendix, which
contains wiring conversion
charts for type V and type
H modules.
Figure 4.12 Typical Connection of a 24 VDC Releasing Device to the FCM-1 Module