AFP-3030 Operations Manual —
P/N DOC-01-033:C 05/12/2018
53
Appendix A: Software Type ID Codes
A.1 Alphabetical List
The following chart lists AFP-3030 Type ID codes in alphabetical order. These codes are assigned during programming based on the
types and functions of the devices they are assigned. The codes appear in point message formats.
Software Type ID Code
Device
AAM SILENCE
Silences all the outputs mapped to the associated AAM zone.
ABORT SWITCH
Monitor that provides an abort function for a releasing zone through connection to an abort station
ACK SWITCH
Monitor used to silence panel sounder, and to give an acknowledge message on the panel display
AIR REF
FSL-751 detector used to monitor air quality entering a protected area
ALARM DEV
Supervised NAC for speaker circuits.
ALARM DEV FLT
Monitoring audio equipment.
ALARMS PEND
Control module or NAC for output that will activate upon receipt of an alarm condition, and remain in the alarm
state until all alarms have been acknowledged. Programmed for switch inhibit
ALARM TRACK
Supervise protected premises for all notification and evacuation.
ASPIR. (NON)
For use with an aspiration detector, reports to the fire panel as a non-fire event when its threshold is reached
ASPIR. (PRE)
For use with an aspiration detector, reports to the fire panel as a prealarm condition when its threshold is
reached
ASPIR. (REF)
For use with an aspiration detector, reports to the fire panel as a non-fire activation, used as a reference for
other aspiration detectors on the loop
ASPIR. (SUP)
For use with an aspiration detector, reports to the fire panel as a supervisory when its threshold is reached
ASPIRATION
For use with an aspiration detector, reports to the fire panel as a fire alarm when threshold is reached
AUDIO SYSTEM
Monitor for audio equipment
BELL CIRCUIT
Control module used with NAC with bells
blank
Operates as CONTROL with no Type ID label
CO MONITOR
Monitor Module for use with conventional CO detectors. Activation will generate a CO Alarm on the FACP.
CONTROL
Control module used with NAC
CONTROL NAC
Control module or NAC
ECS/MN MON
Monitor for mass notification alarms, latching
ECS/MN SUPL
Monitor for mass notification supervisory inputs, latching
ECS/MN SUPT
Monitor for mass notification supervisory inputs, tracking
ECS/MN TMON
Monitor used for mass notification fault inputs, tracking
FIRE CONTROL
Monitors non-fire activations
FMM-420
Monitors 4-20 mA industrial sensors
FORM C RESET
Control module used to interrupt 24 V power to four-wire conventional detectors for 30 seconds upon reset.
Used in conjunction with a monitor module with a conventional detector Type ID
GEN ALARM
Control module, XPC-8 circuit, or XP5-C (NAC mode) configured as a Municipal Box Transmitter (MBT-1
required). This Type ID can also be used for general alarm activation. It is programmed as “switch inhibit”.
GEN PEND
Control module, XPC-8 circuit, or XP5-C (NAC mode) that will activate upon receipt of an alarm and/or fault
condition, and remain in the ON state until all events have been acknowledged
GEN SUPERVIS
Control module, XPC-8, or XP5-C (NAC mode) activated under any supervisory condition (includes sprinkler
type). It is programmed as “switch inhibit”
GEN FAULT
Control module, XPC-8, or XP5-C (NAC mode) activated under any System Fault condition. It is programmed
as “switch inhibit”
HAZARD ALERT
Indicated a hazard condition, tracking
HEAT
Adjustable threshold heat detector
HEAT+
Adjustable threshold heat detector with a low temperature warning.
HEAT(FIXED)
Intelligent 135ºF thermal sensor detector
HEAT(ROR)
15ºF per minute rate-of-rise detector
HEAT DETECT
Monitor for conventional heat detector
INST RELEASE
Control module used with NAC. Always non-silenceable and switch-inhibited
ISOLATED NAC
Supervised NAC for notification appliance, used with audio isolators. Activates even if there is a short on its
NAC circuit. Canada installations only.
ISOLATED SPK
Supervised NAC for speaker circuit, used with audio isolators. Activates even if there is a short on its audio
circuit. Canada installations only.
LATCH SUPERV
Indicates latching supervisory condition
LP PWR SOUND
Used to support intelligent powered AV devices.
MAN RELEASE
Monitor module that provides manual release for a releasing zone through connection to a pull station
Table A.1 Software Type ID Codes, Alphabetical List (1 of 3)