background image

- 4 -

2. G

ENERAL

 R

EQUIREMENTS

 

AND

 S

PECIFICATIONS

This unit must be installed in a dry place, in a non-corrosive, well-ventilated environment, without excessive dust. The 
ambient temperatue must be over 10°C and under 27°C. If the ambient temperatue is 10°C or less, the plenum must be 
insulated on 10 ft linear minimum length.

CAUTION

1.  LOCATION - The furnace should be centrally located to the heating area.

2.  POSITIONS - It can be installed for vertical, horizontal or downflow operation. When installed horizontally, the furnace should be positioned such as the 
 

door will not end up being on the top. The door should be on the side of the furnace, to ensure that the motor bearings are in their designed position. In 

 

vertical downflow installations, use only “L”- or “T”-shaped plenum with no openings or registers directly below furnace.

3.  INSTALLATION CLEARANCES - As shipped from the factory, each unit is approved for “zero inch” clearance. If additional clearance is required, it will be 
 

indicated on the data label attached to the furnace.

4. TEMPERATURE RISE - Furnaces are shipped to operate at 0.20” W.C. (50 Pa) external static pressure. They are certified for operation up to 
 

0.50” W.C. (125 Pa). Check below for temperature rise table on specification chart and, if necessary, adjust the unit to match.

5.  SERVICE CLEARANCE - Units are serviced from the FRONT. Leave at least 24” (610 mm) clearance in front of the door.

240 VOLTS - SINGLE PHASE

TEMPERATURE RISE @ 0.20” W. C.

 MODEL NO.

KW

BTHU

AMPS INCL. MOTOR

HP

BLOWER

°C

°F

*SPEED

RPM

21B10M

10

34152

46

1/3

10” x 8”

(254 mm x 203 mm)

23

41

LOW

663

21B15M

15

51228

67

1/3

24

43

MED-LOW

814

21B18M**

18

61473

77

1/3

27

49

MED-LOW

814

21B20M**

20

68304

86

1/3

33

59

MED-LOW

814

21B25M**

25

85379

107

1/3

37

67

MED-LOW

814

21B27MS***†

27

92210

116

3/4

12” x 8”

(304 mm x 203 mm)

36

65

MED-HIGH

707

208 VOLTS - THREE-PHASE

83B13

13.5

46105

42

1/3

10” x 8”

(254 mm x 203 mm)

21

38

MED

960

83B24

24

81964

70

1/3

35

63

MED

960

83B27

27

92210

78

1/3

39

70

MED

960

10” x 8” (254 mm x 203 mm) BLOWER

SPEED

FLOW 

RATE

STATIC PRESSURE

(INCHES OF WATER COLUMN)

0.2

0.3

0.4

0.5

0.6

LOW

CFM

L/s

756
357

749

353

740

349

729
344

713
337

MED-LOW

CFM

L/s

1035

488

1018

480

997
470

971
458

935
441

MED-HIGH

CFM

L/s

1177

556

1157

546

1132

534

1102

520

1063

502

HIGH

CFM

L/s

1301

614

1276

602

1247

588

1207

569

1145

540

12” x 8” (304 mm x 203 mm) BLOWER

SPEED

FLOW 

RATE

STATIC PRESSURE

(INCHES OF WATER COLUMN)

0.2

0.3

0.4

0.5

0.6

LOW****

CFM

L/s

727
343

699
330

667
315

636
300

606
286

MED-LOW****

CFM

L/s

912
431

897
423

878
414

853
402

823
388

MED-HIGH

CFM

L/s

1216

574

1200

566

1181

557

1157

546

1129

533

HIGH

CFM

L/s

1640

774

1601

755

1558

735

1513

714

1466

692

WARNING:

*FACTORY SETTINGS.

** 21B18M, 21B20M and 21B25M must NOT be setup to run continuously at LOW speed as it will cause overheating conditions. These models are 
   certified to run only at HIGH, MED-HIGH and MED-LOW speeds.

*** 21B27MS must NOT be setup to run continuously at LOW or MED-LOW speeds, as it will cause overheating conditions. This model is certified to run 
     only at HIGH and MED-HIGH speeds.

****These speeds can only be run with heater off, for cooling/ventilation purposes only.

†21B27MS has built-in additional noise-absorption components to run quietly during continuous or regular cycle modes.

SPECIFICATIONS SUBJECT TO CHANGE WITHOUT NOTICE

Summary of Contents for 21B10M

Page 1: ...N AND USER MANUAL IMPORTANT READ AND SAVE THESE INSTRUCTIONS MODELS 21B10M 21B15M 21B18M 21B20M 21B25M 21B27MS 83B13 83B24 AND 83B27 M A DE IN CANA D A F A B R I Q U AU CA N A D A NORTRON Sherbrooke Q...

Page 2: ...ture furnace failure thus voiding the warranty Do not block the combustion air openings in the furnace Any blockage will result in improper overheat situation and may result in a fire hazard and or ca...

Page 3: ...ERED FURNACE HUMIDIFIERS 7 7 4 INTERLOCK CONNECTION 7 8 WIRING DIAGRAMS 8 11 9 SERVICE PARTS 12 10 MAINTENANCE 13 11 TROUBLESHOOTING 13 12 WARRANTY 14 1 DIMENSIONS FK0004A FRONT VIEW RIGHT SIDE VIEW R...

Page 4: ...x 203 mm 23 41 LOW 663 21B15M 15 51228 67 1 3 24 43 MED LOW 814 21B18M 18 61473 77 1 3 27 49 MED LOW 814 21B20M 20 68304 86 1 3 33 59 MED LOW 814 21B25M 25 85379 107 1 3 37 67 MED LOW 814 21B27MS 27...

Page 5: ...s are turned on by the thermostat OFF The blower motor will operate in the standard heating mode controlled by the thermostat MILD During spring and fall you may not require full heating capacity to m...

Page 6: ...of a floor opening 14 x 14 362 mm x 362 mm The duct system must be designed so that the external static pressure of the system does not exceed the maximum external static pressure of 0 50 W C 125 Pa S...

Page 7: ...ummer directing all air flow through the coil In winter the damper would be open to allow air to bypass the coil Typical air conditioning field wiring connections are shown in the diagram at right FUR...

Page 8: ...ing same ratings as high voltage except 18 AWG HI MED HIGH MED LOW LOW FAN MOTOR SPEED BLACK BLUE YELLOW RED COLOR LEGEND C E R K MRTP HEAT L1 L2 Capacitor Heating Element Time Delay Relay Fan Relay A...

Page 9: ...he original wire as supplied must be replaced use the same equivalent wire Wiring must comply with applicable codes ordinances and regulations 2 Field wiring must comply with applicable codes ordinanc...

Page 10: ...rdinances and regulations Use only Class 1 wiring inside furnace compartments Critical characteristic Line voltage wiring UL AWM 1015 600V 105 C VW 1 8 AWG CSA TEW 600V 105 C FT1 8 AWG and 12 AWG Low...

Page 11: ...use the same equivalent wire Wiring must comply with applicable codes ordinances and regulations 2 Field wiring must comply with applicable codes ordinances and regulations Use only Class 1 wiring ins...

Page 12: ...57 12 6 5 37 21 9 DQ 5HOD QRW LQ 0 9 DQ 5HOD 7UDQVIRUPHU 9 ORZHU KHHO PP PP IRU ORZHU 0RWRU 3 9 IRU 06 0RWRU 3 9 IRU 0 0 0 0 DQG 0 0RWRU 3 9 IRU 6HULHV OHPHQW VVHPEO 9 OHPHQW VVHPEO 9 OHPHQW VVHPEO 9...

Page 13: ...N MODE switch open contact Bottom sequencer 4 Motor going on and off in short cycles or in too long cycles Heat anticipator in thermostat incorrectly set or may be defective 5 The thermostat must be s...

Reviews: