C-Rate: Current normalized to the rated capacity of a 
battery. 
Cut-off temperature: Temperature where the BMS will 
terminate the usage of the Battery Unit 
Cut-off voltage: Voltage where the BMS will no longer 
allow usage of the Battery Unit. 
EOL: End-of-Life, as definition it states when less than  
80 % of the initial capacity remain. Li-ion can be used for 
lower remaining capacity. 
LFP: Lithium iron phosphate, electrode material used in the 
LITE Battery Unit.  
SoC: State-of-charge, fraction of rated capacity, 0-100 %. 
 
1.3

 

Unstable Mains Service 

 
Where the main electrical supply is of poor quality, the 
batteries are used to provide service when the mains is off. 
Common to the poor grid operation are frequent 
interruptions. Often the time between the interruptions is 
short which means that the battery will not be fully 
charged. This is not a problem for lithium-ion batteries, as 
they have a stable performance, independent of SoC. The 
figure below shows the voltage of battery units in unstable 
mains. 

 

Operation  

 

2.1 

GENERAL PRECAUTIONS 

 
Only operate within specified temperature, current and 
voltage. All data from battery shall be stored in an upper 
host computer for future reference. 
 
2.2 

BMS 

 
The NorthStar LITE Battery Unit is equipped with an 
internal BMS in every unit. The BMS will protect the 
battery from operating outside of its safe operating 
window by monitoring cell voltages, currents, SoC, capacity 
and temperatures. The BMS also include cell balancing 

functionality, reverse polarity protection, charge control, 
high/low temperature cut off, regulated slow charge, and 
the optional heater on/off.  
 
2.2.1  Protection functions 
 
Overvoltage 

Overvoltage 

System 

Cell 

Rated charging voltage 

52.5V 

 

Overcharge alarm 

54.0±0.5V 

3.6±0.02V 

Overcharge protection 

54.6±0.5V 

3.65±0.02V 

Overcharge recovery 

50.2±0.5V 

3.4±0.02V 

 
If the system voltage or cell voltage becomes higher than 
the overcharge protection voltage for more than 2 seconds, 
the BMS enters overcharge protection state and inhibits 
charging. 
The overcharge protection delay is 1 ± 0.5 s and the 
overcharge protection release conditions are one of the 
following:  

 

The voltage is below the recovery voltage or 

 

Switch to discharge mode. 

 
Undervoltage 

Undervoltage 

System 

Cell 

Overdischarge alarm 

39.0±0.5V 

2.6±0.02V 

Overdischarge protection 

37.5±0.5V 

2.5±0.02V 

Overdischarge recovery 

43.5±0.5V 

2.9±0.02V 

 

If the system or cell voltage becomes lower than 
overdischarge protection voltage and stays at that voltage 
longer than 2 seconds, the BMS enters overdischarge 
protection state and inhibits discharging.  
The overdischarge protection delay is 1 ± 0.5 s and the 
overdischarge protection release condition is: 

 

Start charge mode. 
 

Sleep mode: If undervoltage protection on system level or 
cell level is detected, the BMS goes into sleep mode. 
Release conditions are one of the following:  

 

Put in charge or 

 

Activated via RS232 communication or 

 

Reset button pressed 

 
Overcurrent 

Overcurrent 

System 

Charging Overcurrent alarm 

102±3A 

Charging Overcurrent protection 

105±4A 

Discharging Overcurrent alarm 

102±3A 

Discharging Overcurrent protection 

105±4A 

Short circuit current protection 

210±10A 

 

Voltage of battery in unstable mains 

 

 

Time [Days] 

Vo

lt

ag

e [

V/

C

ell

Summary of Contents for LITE

Page 1: ...NorthStar LITE Battery Application Manual ...

Page 2: ...Lithium Ion Page Section Title 3 1 Introduction 4 2 Operation 7 3 Useful Life 8 4 Installation and Handling 13 5 Maintenance 13 6 Transport 13 7 Technical Specifications 14 8 Contacts ...

Page 3: ...nce in combination with good safety characteristics The battery cells utilized in the Battery Unit are of prismatic type with laser welded aluminum casings Each cell has a safety vent which enables the release of over pressures in case of a thermal runaway situation 1 1 2 Front Panel 1 Negative terminal 2 Circuit Breaker CB 3 Positive terminal 4 Grounding point 5 Handles 6 Fastening bracket for 19...

Page 4: ...ction charge control high low temperature cut off regulated slow charge and the optional heater on off 2 2 1 Protection functions Overvoltage Overvoltage System Cell Rated charging voltage 52 5V Overcharge alarm 54 0 0 5V 3 6 0 02V Overcharge protection 54 6 0 5V 3 65 0 02V Overcharge recovery 50 2 0 5V 3 4 0 02V If the system voltage or cell voltage becomes higher than the overcharge protection v...

Page 5: ...arge Under temperature alarm 5 2 C 5 2 C Charge Under temperature protection 0 2 C 0 2 C Charge Under temperature recovery 8 2 C 8 2 C Discharge Under temperature alarm 5 2 C 5 2 C Discharge Under temperature protection 20 2 C 20 2 C Discharge Under temperature recovery 10 2 C 10 2 C If the minimum cell temperature becomes lower than cell under temperature protection threshold BMS enters cell unde...

Page 6: ...de the above specified temperature limits as it constitutes a safety risk Mode Temperature range Charge 0 45 C Discharge 20 60 C 2 5 1 Low Temperature Performance At temperatures below 15 C the performance of the Battery Unit starts to become affected See figure in section 2 3 showing the capacity different temperatures To extend the performance range of the system a heater is available as an opti...

Page 7: ...ium ion batteries will gradually self discharge The rate of self discharge increases with increasing temperature and SoC To maximize service life it is optimal to store the batteries at 30 40 SoC in the temperature range from 0 C to 25 C However storage temperatures between 20 C to 60 C are acceptable Storage at temperatures above 60 C should be avoided due to the increased safety risks associated...

Page 8: ...ery to an open flame or other ignition source Battery terminals are always energized and if short circuited cause electricalarcing Always use insulated tools Batteries are heavy objects Useproper handling equipment safety gear during installation Inappropriate lithium ion battery disposal can result in environmental contamination Please dispose of batteries according to regulations Battery may be ...

Page 9: ...s been extinguished the Battery Unit needs to be monitored for an extended period of time 24 hours due to the risk of the fire reigniting 4 3 Receiving the Shipment To avoid injuries to the personnel unpacking and installing the battery it is important to remember that the battery is heavy and could require two persons to lift and install To avoid damages to the battery during unpacking and liftin...

Page 10: ...ge nuts M8 8 Nm Battery cables Cables The allowed cable dimensions are Min 35mm2 Max 50mm2 recommended In order to determine proper dimensioning of the power cables consideration must be made in regards to type and length of cable charging settings environmental conditions physical installation etc Installation Do as follows to install the battery unit in a standard 19 rack 1 Make sure the CB is t...

Page 11: ... Connect the battery cables Use cables dimensions and lengths according to information above Cables shall be fitted with a M8 cable lug The connection shall be in the order as in the picture Cables can be connected going downwards or upwards Tighten the screws using table above for torques 11 Connect the communica tion cable to upper host at on of the RS485 ports The second port is used to connect...

Page 12: ...nt panel which indicate the status of the system as described by the table below See section 2 4 Determining State of Charge for introduction to the capacity indicators Battery Unit Mode Normal Alarm Protection Failure ALM RUN Capacity O O O O O O Shutdown Sleep OFF OFF ALL OFF Standby Normal OFF Flash 1 Capacity display Protection Flash 2 Alarm Flash 3 Failure ON OFF ALL OFF Charge Normal OFF Fla...

Page 13: ...regulations For transportation from warehouse to site the battery unit shall be in its original packaging Before returning any Battery Units to Northstar contact the nearest service center for further instructions 6 1 Disposal or Recycling of Battery Units Transport regulations for disposal or recycling of Battery Units is only applicable for units that are still fully functional but have reached ...

Page 14: ...adalsgatan 8 A SE 164 40 Kista Stockholm Sweden europe northstarsitetel com Tel 46 8 410 102 00 Fax 46 8 638 06 00 NorthStar Middle East Africa NorthStar Battery DMCC Office 702 Saba 1 Tower Jumeirah Lake Towers Dubai United Arab Emirates mea northstarsitetel com Tel 971 4 423 8060 Fax 971 4 423 8061 NorthStar China Northstar Group Unit 513 207 North Wulumuqi Road Shanghai 200040 China china north...

Reviews: