ONL753W2 10/09
8
BREAK-IN PERIOD
1. The
fi rst 100 hours on a new or reconditioned
engine are critical to its life and performance.
2. Constantly check the engine temperature and oil
pressure.
3. Oil consumption is greater during break-in as
piston rings take time to seat.
4. Break-In Oil Changes: Change engine oil and
fi lter at 50 hours. Change oil and fi lter again at
250 hours (consult Lubricants section for oil
recommendation).
Operating Instructions:
Maintain at least a 75% load on your generator
set for the fi rst 100 hours. If this is not possible,
maintain no less than a 50% load to ensure proper
seating of the piston rings. Vary the load to help
seat the rings.
BEFORE STARTING
1. Check the coolant level by removing the pressure
cap from the expansion tank or radiator. In order to
give the cooling water an opportunity to expand, the
level should be about 1 in. (2.5 cm) below the fi ller
cap sealing surface when the engine is cold.
CAUTION: Use protective clothing and open the
fi ller cap carefully when the engine is warm to
prevent burns.
2. Check the oil level in the crankcase with the dip-
stick. The oil level must be in the waffl ed area on the
stick. Never allow the level to go below this area.
Always add the same viscosity of oil as is already in
the crankcase.
3. Check the fuel tank level and open any fuel valves.
NOTE: The battery switch must always be kept
ON while the engine is running. If the switch is
turned OFF while the engine is running, the
battery charging regulator could be ruined.
STARTING
1. Hold the Shutdown Bypass-Preheat switch in the ON
position for 10 to 20 seconds before starting a cold
engine. Holding the switch too long can burn out the
glow plugs. This step is not necessary if the engine is
already warm.
2. While holding the Shutdown Bypass-Preheat switch
in the ON position, push the Engine Control switch
to the START position.
3. As soon as the engine starts, release both switches. Do
not crank the starter for more than 20 seconds
consecutively. If the engine fails to start with the fi rst
attempt, be sure that it has stopped completely before
re-engaging.
OPERATING
1. Check oil pressure often. Oil pressure must be
above 15 PSI. The water temperature must be
below 225°F (107°C). Check the AC voltage and
frequency. If these deviate from normal levels, shut
down the generator set and investigate.
1. Let the unit run unloaded for a three to fi ve minute
warm-up period.
2. Add electrical load.
STOPPING
1. Remove electrical load from the generator set.
2. Move the Engine Control switch to the STOP
position
momentarily.
Operating Procedures