Wired Controller WRC2
23
While setting Filter function, a two digit number will be shown in the timer area. The
first number represents the pollution level. The second number indicates the
accumulated operating hours of the indoor fan.
The first digit setting can be a “1” (light pollution level), “2” (medium pollution level),
or “3” (serious pollution level). The second digit will be 0~9 and will represent different
operation hours based on the pollution level. The default setting is for no Filter function.
In this instance “00” will be displayed in the timer area.
Notes:
①
.
A Filter function timer setting of “10” indicates a light pollution level and 5500
operation hours. Each incremental increase in the second digit will add 500
hours to the Filter function timer setting. See Table 3.
②
.
A Filter function timer setting of “20” indicates medium pollution level and 1400
operation hours. Each incremental increase in the second digit will add 400
hours to the Filer function timer setting. See Table 3.
③
.
A Filter function timer setting of “30” indicates a serious pollution level and 100
operation hours. Each incremental increase in the second digit will add 100
hours to the Filter function timer setting. See Table 3.
Table 3
④
.
Filter
Function
Indicator
Fan Operation Hours
Filter
Function
Indicator
Fan Operation Hours
Filter
Function
Indicator
Fan Operation Hours
10
5500
20
1400
30
100
11
6000
21
1800
31
200
12
6500
22
2200
32
300
13
7000
23
2600
33
400
14
7500
24
3000
34
500
15
8000
25
3400
35
600
16
8500
26
3800
36
700
17
9000
27
4200
37
800
18
9500
28
4600
38
900
19
10000
29
5000
39
1000
To set the Filter function, under ON status, press the Function button. With the
FILTER icon flashing, the pollution setting level will be shown in the Timer area. Press
▲ and ▼ to adjust pollution level. Press the Enter/Cancel button to activate.
To cancel the Filter function, press the Function button to select. With the FILTER