Nortek Reznor VRA-4E Series Installation, Commissioning, Servicing Download Page 16

1712VRA

4EGBEN,

 

pag..

 

16/25

 

 

8.3 Ignition system 

To access the ignition system, follow steps 1 to 3 in 
§ 8.1. 

ATTENTION

 : 

Due to high voltage on the spark 

wire and electrode, do not touch when energized. 
See hazard levels.

 

 

Ignitor

-

 

refer to figure 9 and locate the ignitor (on 

the side of the burner rack). Disconnect the wire, 
remove the screw and the ignitor. Clean with an 
emery cloth. 
Note: Spark gap must be maintained to 3.0 mm (see 
figure 10a). Re-fit the ignitor as per figure 10b. 

Flame sensor - 

Refer to figure 9 and locate the 

flame sensor. Disconnect the wire, remove the screw 
and the flame sensor. Clean with an emery cloth. 

 
Ignition controller - 

The enclosed integrated circuit 

monitors the operation of the burner including 
ignition. Do not attempt to dismantle the ignition 
controller. Each heating season ignition cables 
should be checked for insulation deterioration and 
good connections. 

Proper operation of the direct spark ignition 
system requires a minimum flame current of 1,0 

μ

A when measured with a micro-ammeter. 

 

Fig. 10a - Ignitor assembly 

 

For further information and checkout procedure of the direct 
spark ignition system, refer to the manufacturers control 
operating instructions a copy of which is supplied with the air 
heater. 

 

      Fig. 10b -: Fitting the ignitor 

 

 

 
 
8.4 Multi-functional gas control valve 

1.  Ensure gas supply to the air heater is turned 

OFF. 

2.  After the air circulation fan has stopped, switch 

OFF the electricity supply to the air heater. 

3.  Mark for future identification and disconnect the 

wires connected to the valve. 

4.  Disconnect the gas service union between the 

control valve and the gas service tap. Remove 
the gas control valve. 

5.  Re-fit a replacement valve making all of the 

required connections.

 

6  Carry out complete commissioning procedure 

prior to placing the appliance back into service 
as outlined in section 6.0. 

ATTENTION :

 

The gas control operating valve is the 

prime safety shut-off.  All gas supply lines must be free of 
dirt, scale,  
etc. before connecting to the air heater thus ensuring 
positive closure of the control valve. 
 

 
8.5 Combustion air control/switch 

If it is determined that the air differential pressure 
switch needs replacing, use only authorized 
replacements that are designed for the air heater 
being serviced. These switches are calibrated to 
operate at the designed combustion air flow duty for 
each appliance size in the product range. 
 

8.6 Combustion air fan (venter)  
(The combustion air fan motor is lubricated for life. 
Do not oil or grease.) 

1.  Ensure gas supply to the air heater is turned OFF 
2.  After the air circulation fan has stopped, switch 

OFF the electricity supply to the air heater.

 

3.  To gain access to the fan open the hinged controls 
compartment access door. Refer to figure 9 for 
location 
4.  Mark for future identification and disconnect the 

wires connecting the fan motor at the terminals on 
the main wiring junction. 

5.  Remove combustion air fan and clean as 

necessary using a wire brush and solvent to 
remove sticky residues. 

6.  Re-assemble and check for free rotation before 

proceeding to test the appliance. 

 
 
8.7 Thermal overheat (limit) controls 

If it is determined that the thermal overheat control 
needs replacing, use only authorized replacements 
that are designed for this appliance. To gain access 
to the control, open the controls compartment access 
door. Refer to figure 9 for control locations. The 
control near the top of the air heater is a disc type 
control. Both controls are capillary types with a 
capillary tube that extends into the heat exchanger 
area. To remove the controls, disconnect the wires 
leading to them, remove the fixing screws and lift 
clear of the inner casing panel. When replacing a 
capillary control be careful not to damage the 
capillary tube by kinking. Make bends with a generous 
radius (approx 25 mm).   

Note: 

The capillary control is fitted to a bracket. With 

the bracket removed from the heater, remove the 
control from the bracket.

Summary of Contents for Reznor VRA-4E Series

Page 1: ...ng Leave it with the user or attached to the appliance or gas service meter after installation WARNING Improper installation adjustment alteration service or maintenance can cause property damage inju...

Page 2: ...ir Pressure Switch 8 7 Combustion Air Fan 9 0 FAULT FINDING p 17 10 0 PARTS LIST p 20 11 0 GAS CONVERSION p 20 12 0 USERS INSTRUCTIONS p 21 13 0 HEALTH SAFETY STATEMENT p 22 HAZARD INTENSITY LEVELS DA...

Page 3: ...odels have an axial fan for air delivery These heaters are designed for overhead suspension and are suitable for indoor installation only installed at an operation ambient temperature between 15 C and...

Page 4: ...pressure G20 natural gas Inlet pressure 20 0 mbar Table 2 Injector size and burner pressure G20 natural gas Inlet pressure 20mbar Table 3 Injector size and burner pressure G30 G31 butane propane Inle...

Page 5: ...0 151 759 73 808 301 1022 479 477 82 180 608 833 212 212 123 942 550 3 4 G 120 1750 980 846 130 67 1100 164 602 177 1057 348 490 90 175 595 795 160 256 20 1365 770 3 4 G 145 1750 1150 846 130 67 1100...

Page 6: ...r for the appropriate protection grill IP20 dia130 PN 02 25094 Each heater installed as a type C appliance must be fitted with an individual combustion air flue pipe system Only systems specified by t...

Page 7: ...outlet socket for flue pipe 2 Combustion air inlet opening Follow any flue pipe manufacturers installation instructions for making joints including connections to the air heater for passing through a...

Page 8: ...l modify the air throw pattern achieved In building having low heat loss where single heaters are required to cover a large floor area and in buildings with high ceiling heights air re circulation fan...

Page 9: ...ir heater See hazard levels page 2 The heater must be installed in a level plane to ensure proper operation Figure 3 Suspension detail Add a nut to lock the M10x1 5 hanger rod to the heater 4 3 Fittin...

Page 10: ...he appliance for long enough to ensure that lock out does not reoccur suggest 5 minutes Fix all electric cables and installer s wiring to the control panel and ensure they do not touch the combustion...

Page 11: ...ed adjacent to the air heater 6 2 Gas connection ATTENTION NEVER USE A FLAME FOR CHECKING GAS SOUNDNESS Only persons formally qualified to work on gas fired apparatus may carry out commissioning and t...

Page 12: ...rried out Ascertain from section 1 of this document and the appliance data plate the correct operating gas pressure for the air heater Turn the room thermostat control to its lowest setting Remove the...

Page 13: ...onds after the burner has lit the time delay relay will activate the thermal fan control which will energize the fan motor Continue to operate the air heater for several minutes to ensure correct oper...

Page 14: ...soot deposits from the burner with a wire brush Clean the ports with a degreaser or acetone A vacuum cleaner or compressed air may assist in this cleaning operation Wipe the inside of the burner tube...

Page 15: ...valve 6 At the burner rack assembly remove the nuts that secure the burner manifold to the burner rack Lift the burner rack manifold assembly upward and pull the assembly out of the air heater Instru...

Page 16: ...ontrol operating valve is the prime safety shut off All gas supply lines must be free of dirt scale etc before connecting to the air heater thus ensuring positive closure of the control valve 8 5 Comb...

Page 17: ...7 25 FAULT FINDING Fault finding may only be carried out by appropriately qualified persons Air heater does not operate and lock out indicator light is off Air heater does not operate and lock out ind...

Page 18: ...1712VRA 4EGBEN pag 18 25...

Page 19: ...1712VRA 4EGBEN pag 19 25...

Page 20: ...Gas valve modureg 120 145M 03 25144M Burner relay E 03 25321 Ignition electrode ER 03 400US 42 Ignition electrode ER 120 145 05 25186 Flame sensor electrode IS 03 401US 195292 ERP fan 12 01 27003 ERP...

Page 21: ...lly when the room thermostat calls for heat after about 30 sec 6 If the appliance does not light a check that the burner control does not require resetting An indicator light glows at the inside panel...

Page 22: ...suffer reddening and itching of the skin Fiber entry into the eyes will cause foreign body irritation Inhalation will cause irritation to the respiratory tract Precautions Wear protective gloves when...

Page 23: ...tive Complies with the requirements of further directives namely GAD 2009 142 EC EMC 2014 30 EC LVD 2014 35 EC the following harmonized standards have been applied EN 1020 Non domestic gas fired force...

Page 24: ...mum capacity pl 80 9 77 7 76 2 76 2 77 6 79 0 76 2 77 8 77 7 78 6 79 6 Envelope loss factor Fenv 0 0 0 0 0 0 0 0 0 0 0 Ignition burner power consumption Pign kW 0 02 0 02 0 02 0 02 0 02 0 02 0 02 0 02...

Page 25: ...A United Kingdom Tel 01384 489 250 Fax 01384 487 707 reznorsales nortek com www reznor co uk Nortek Global HVAC is a registered trademark of the Nortek Global HVAC Limited Because of continuous produc...

Reviews: