Page No 40 of 52 Reznor, RHC21 8000 Installation EN May 2021 D301319 Issue 0
8. Check spark gap against dimensions below,
if necessary, adjust using long nose pilers. Be
careful not to crack the ceramic sleeve.
9. To replace the probe, unscrew the 7mm nut
to release the probe from the bracket and
change.
10. Check condition of probe bracket gasket and
replace if necessary.
11. Refit all parts in reverse order.
12. Follow start up and commissioning
procedure.
7.7 Replacement of LC3 safety
thermostats
1. Disconnect LC3 electrical connectors.
2. Remove LC3 protective cap and lock nut.
3. Unscrew the 2 fixings from the mounting
bracket.
4. Withdraw mounting bracket from heater.
Thermostat mounting bracket
Spark probe
Length of probe =
78.5mm long probe
42.3mm short probe
3.5±0.5 mm gap between
probes
Angle of probe = 20°
7mm nut x2
Probe mounting
bracket gasket x2
Fixing screws
x2
Location of
LC3 connectors
Location of
LC3 protective
cap and lock
nut