background image

11

3. Allow the cooling system to operate for several minutes 

and then set the temperature selector above room 

temperature. Verify the fan and compressor cycle off 

with the thermostat. 

NOTE:

 The blower should also 

stop unless fan mode is set to ON.

System Heating - Heat Pump Mode

1. Set the thermostat’s system mode to HEAT and the 

fan mode to AUTO. Gradually raise the thermostat 
temperature setpoint above room temperature and 
verify the compressor, outdoor fan, and indoor blower 
energize. 

2. Feel the air being circulated by the indoor blower and 

verify it is warmer than ambient temperature. Listen for 
any unusual noises. If unusual sounds occur, determine 
the source of the noise and correct as necessary

System Heating - Electric Heat Mode (If 
Equipped-Optional)

1. Set the thermostat's system mode to EMER. HEAT and 

the fan mode to AUTO.  Gradually raise the thermostat 

temperature setpoint above room temperature and 

verify the compressor and outdoor fan remain off, but 

that the blower and heaters are energized. 

2. Feel the air being circulated by the indoor blower and 

verify that it is warmer than ambient temperature. 

Listen for any unusual noises. If unusual sounds 

occur, determine the source of the noise and correct 

as necessary.

REFRIGERANT CHARGING

 WARNING:

Single Packaged Heat Pumps are shipped fully 

charged with R-410A refrigerant and ready 

for installation. When a system is installed 

according to these instructions, no refrigerant 

charging is required. If repairs make it necessary 

for evacuation and charging, it should only be 

done by qualified, trained personnel thoroughly 

familiar with this equipment. Some local codes 

require licensed installation/service personnel 

to service this type of equipment. Under no 

circumstances should the owner attempt to 

install and/or service this equipment. Failure to 

comply with this warning could result in property 

damage, personal injury, or death.

The system refrigerant charge can be checked and 

adjusted through the service ports provided at the front 

panel. Use only gauge lines which have a Schrader 

depression device present to actuate the valve. Draw a 

vacuum on gauge lines to remove air before attaching 

them to the service ports on the unit.

START UP & ADJUSTMENTS

Pre-Start Check List

 Verify the unit is level and allows condensate to drain.

 Verify the outdoor coil and top of the unit are free from 

obstructions and debris, and all equipment access/

control panels are in place.

  Verify that the duct work is sealed to prevent air leakage. 

 Verify that the line voltage power leads are securely 

connected and the unit is properly grounded.

   Verify that the low voltage wires are securely connected 

to the correct leads on the low voltage terminal strip.

 Verify that the outdoor fan turns freely.

 Verify that the power supply branch circuit overcurrent 

protection is sized properly.

 Verify that the thermostat is wired correctly. The 

thermostat system mode should be set to OFF and the 

thermostat fan mode should be set to AUTO.

Start-Up Procedure

Close all electrical disconnects to energize the system.

 CAUTION:

If the unit is equipped with a crankcase heater, 

allow 24 hours prior to continuing the start up 

procedures to allow for heating of the refrigerant 

compressor crankcase. Failure to comply may 

result in damage and could cause premature 

failure of the system. This warning should be 

followed at initial start up and any time the power 

has been removed for 12 hours or longer.

Air Circulation

Leave the thermostat system mode on OFF, and set the 

fan mode to ON. Blower should run continuously. Check 

the air delivery at the supply registers and adjust register 

openings for balanced air distribution. Examine ductwork 

for leaks or obstruction if insufficient air is detected. Set 

the thermostat fan mode to AUTO. The blower should 

stop running.

Short Cycle Protection

1. With the system operating in cooling mode, note the 

temperature setting of the thermostat and gradually raise 

the set-point temperature until the unit de-energizes.

2. Immediately lower the set point temperature of the 

thermostat to its original setting and verify that the 

indoor blower is energized.

3. After approximately 5 minutes, verify the compressor 

and fan energize and the temperature of the discharge 
air is cooler than the room temperature.

System Cooling

1. Set the thermostat’s system mode to COOL and the 

fan mode to AUTO. Gradually lower the thermostat 

temperature setpoint below room temperature and 

verify the outdoor unit and indoor blower energize.

2. Feel the air being circulated by the indoor blower and 

verify that it is cooler than ambient temperature. Listen for 

any unusual noises. If unusual sounds occur, determine 

the source of the noise and correct as necessary.

Summary of Contents for Q104SD Series

Page 1: ...mon sense plays an important role as well Pay attention to all safety warnings and any other special notes highlighted in the manual Improper installation of the furnace or failure to follow safety wa...

Page 2: ...ing an R 410A Unit in AC Mode 12 Charging an R 410A Unit in Heating Mode 12 Verification of charge in Heat Mode 12 HEAT PUMP MAINTENANCE 12 FIGURES TABLES 13 Figure 7 Q104SD Heat pump Dimensions 13 Ta...

Page 3: ...oorfan compressor andblowermotorwill all cycle on and off to maintain the indoor temperature at the desired cooling level NOTE If the temperature level is re adjusted or the system mode is reset the f...

Page 4: ...selector setting HEAT PUMP MAINTENANCE CAUTION Shut off all electrical power to the unit before performing any maintenance or service on the system Failure to comply may result in personal injury or d...

Page 5: ...asoline and any other flammable vapors and liquids in the vicinity of the unit WARNING The safety information listed below must be followed during the installation service and operation of this unit U...

Page 6: ...ng load of the area to be conditioned must be calculatedandasystemofthepropercapacityselected It is recommended that the area to be conditioned be completely insulated and vapor sealed Check the elect...

Page 7: ...beneath the unit Rigging Hoisting WARNING To avoid the risk of property damage personal injury or death it is the rigger s responsibility to ensure that whatever means are used to hoist the unit are s...

Page 8: ...ning the correct fuse or circuit breaker for the unit Incoming field wiring and minimum size of electrical conductors and circuit Units require horizontal roof curb and return air kit for horizontal i...

Page 9: ...the system when very high pressures occur during abnormal conditions Under normal conditions the switch is closed If the discharge pressure rises above 650 psig then the switch will open and de energi...

Page 10: ...seconds regardless of whether short is removed or not Qualifying conditions of minimum ambient or coil temperature do not need to be met when the unit is forced into defrost If the short across the TE...

Page 11: ...ify the unit is level and allows condensate to drain Verify the outdoor coil and top of the unit are free from obstructions and debris and all equipment access control panels are in place Verifythatth...

Page 12: ...he unit rating plate Return to the system when the outdoor temperature is 60 degrees F or higher and follow the steps defined in Charging an R410A Unit in AC Mode NOTE Unit charge MUST be verified in...

Page 13: ...2 29 5 26 0 43 0 39 3 X60K 530 29 5 26 0 43 0 39 3 FIGURES TABLES Top View 24 9 13 5 16 12 13 3 13 5 16 12 CG A 47 5 75 NPT Female Drain Connector B DOWNFLOW SUPPLY DUCT OPENING DOWNFLOW RETURN DUCT O...

Page 14: ...t Defrost Board L 24V Output Fault Monitor See thermostat manual for compatibility Brown Orange Accesory Heat Plug Indoor Thermostat Sub Base Unit Terminal Block 1 2 3 4 5 6 7 8 9 to Blower Relay Cool...

Page 15: ...See installation instructions in the branding kit 1 Couper le courant avant de faire letretien 2 Employez uniquement des conducteurs en cuivre 3 Ne convient pas aux installations de plus de 150 V a la...

Page 16: ...16 Figure 10 Charging Chart for 2 Ton Units Figure 11 Charging Chart for 2 5 Ton Units Charging Charts Cooling...

Page 17: ...17 Figure 13 Charging Chart for 3 5 Ton Units Figure 12 Charging Chart for 3 Ton Units...

Page 18: ...18 Figure 14 Charging Chart for 4 Ton Units Figure 15 Charging Chart for 5 Ton Units...

Page 19: ...9 1380 22 9 1315 24 0 1215 26 0 Tap T5 1850 17 1 1795 17 6 1740 18 2 1710 18 5 1640 19 3 1595 19 8 1540 20 5 1475 21 4 X48K Tap T1 950 33 2 900 35 1 865 36 6 730 43 4 670 47 0 585 54 2 510 62 2 Tap T...

Page 20: ...VOLTS Has the thermostat been calibrated YES NO Is the thermostat level YES NO Is the heat anticipator setting correct YES NO REPLACEMENT PARTS Replacement parts are available through your distributor...

Reviews: