Nortek P7RE Series Installation Instructions Manual Download Page 6

6

Figure 4. return air box

Return Duct

1. Assemble the collar by overlapping the two ends.  

note:

 One end of the collar is slotted and the opposite 

end has two small holes. Position the end with small 

screw holes underneath the slotted end.

2. Fasten the collar ends with two self drilling sheet metal 

screws.

3. Position the collar over the unit opening. Align the 

four holes in the collar with the four dimples or holes 

(depending on unit model) in the panel.

4. Secure the collar to the rear panel using self drilling 

screws (10-16x.5).

locating & installing the return air assembly

To simplify installation, locate and install the return air 

assembly first. If desired, the return opening can be 

located inside a closet with louvered doors that has an 

open area equal to or greater than a 12” x 20” grille. The 

return air grille can be placed in the wall of a closet and 

the air ducted into the filter box through a boxed-in area 
at the closet floor level (

Figure 4

). 

Verify  the  filter  is 

readily accessible.
note:

 The return air box with grille and filter should not 

be located in heavy traffic areas like hallways or center 

of rooms. A good spot is in a corner or under a table, if a 

minimum two inch clearance is available.

1. Start the installation from under the home by cutting a 

small hole in the subfloor. Determine how the floor joist 

location will affect cutting the opening needed for the 

return air box. 

note: 

Floor joists are generally located 

on 16” centers, leaving 14-3/8” between joists.

2. After measuring the return air box (approximately 12-

1/4” x 20-1/4”), cut the hole through the floor so that 

the box will fit between the floor joists. Care should be 

taken when cutting through carpeting to avoid snags. 

note:

 In most installations it will be necessary to cut a 

similar hole in the fiberboard directly under the hole in 

the floor. However, if the floor is more than ten inches 

deep, it will only be necessary to cut a hole for the collar 

on the return air box or for the insulated duct.

3. Set the box into the opening and fasten with screws or 

nails.

4. Install the filter and return air grille in the air box.

connecting the return & Supply air Flexible ducts

•  Flexible ducts can be connected to the corresponding 

fittings with the clamps provided with the ducts. See 

Figure 9 

Table 4, (page 12)

note:

 To prevent a 

loss in cooling capacity, make sure all connections are 

tight.

•  The flexible ducts may be cut to the required length, 

see instructions packed with duct. Keep all ducts as 

short and straight as possible. Avoid sharp bends.

•  Ducts  may  be  spliced  with  sheet  metal  sleeves  and 

clamps.

•  After the inner duct is connected to the proper fitting, 

the insulation and plastic sleeve should be pulled over 

the connection and clamped.

•  Homes  with  multiple  supply  ducts  (or  special 

applications), a Y fitting is available to divide the 

supply air so it can be ducted to different areas of the 

home for more efficient cooling. 

note: 

For maximum 

performance, insulate the Y fitting.

locating & installing the Supply damper(s)

 caution:

if installing this air conditioning system in 

conjunction with a furnace, a damper must be 

installed in the furnace base assembly to prevent 

cold air from being discharged around the heat 

exchanger. damage to the heat exchanger and 

asphyxiation may occur if a damper is not 

installed.
check with the furnace manufacturer for damper 

requirements. Failure to install the required 

furnace damper may invalidate code agency 

listing and limited warranty on the furnace.

When locating the supply damper(s), carefully check 

floor joists and frame members that could interfere with 

the installation of the damper or flexible duct. Ideally, the 

damper should be located in the bottom of the main duct, 

forward of center of the home, at least three feet from the 
nearest register. See 

Figure 5 (page 7)

. The round 

supply opening in the slanted side of the damper should 

face the side of the home where the air conditioner is 

located.

1. Locate the center of the heat duct by cutting a small hole 

in the fiberboard below the duct at the desired location.

2. Cut a hole approximately 3/4” larger than the damper 

opening in the fiberboard.

3. Cut a 9-1/8” x 13-1/8” hole in the duct and bend over 

all tabs flat on the inside of the heat duct.

4. Insert the damper into the duct and bend over all tabs 

flat on the inside of the heat duct.

5. Seal the opening between the fiberboard and damper 

or flexible duct.

Summary of Contents for P7RE Series

Page 1: ...e plays an important role as well Pay attention to all safety warnings and any other special notes highlighted in the manual Improper installation of the furnace or failure to follow safety warnings c...

Page 2: ...tions 8 Cooling Only Thermostat 8 Heat Cool Thermostat 10 Blower Speed ECM Motor 10 START UP ADJUSTMENTS 10 Pre Start Checklist 10 Start Up Procedure 10 System Cooling 10 System Heating 10 Refrigerant...

Page 3: ...he information listed below must be followed during the installation service and operation of this unit Unqualified individuals should not attempt to interpret these instructions or install this equip...

Page 4: ...ly and return ducts If practical place the air conditioner and its ducts in an area where they will be shaded from the afternoon sun when the heat load is greatest The length of the supply and return...

Page 5: ...ollar so the edge of the unit opening fits between the flange and the bead 2 Overlap the collar ends keeping the small screw holes underneath 3 Align the holes in the crimped area and install one scre...

Page 6: ...n the air box Connecting the Return Supply Air Flexible Ducts Flexible ducts can be connected to the corresponding fittings with the clamps provided with the ducts See Figure 9 Table 4 page 12 NOTE To...

Page 7: ...installer should become familiar with the wiring diagram before making any electrical connections to the unit Anelectricaldisconnectmustbelocatedwithinsight of and readily accessible to the unit This...

Page 8: ...reaker and do not in any case exceed the maximum size listed on the data label of the unit Thermostat Low Voltage Connections The unit is designed to operate from a 24 VAC Class II control circuit The...

Page 9: ...27 1104 29 1051 30 992 32 Tap T3 1460 22 1415 22 1385 23 1335 24 1275 25 1225 26 1170 27 1120 28 Tap T4 1502 21 1466 22 1437 22 1388 23 1345 23 1305 24 1251 25 1204 26 Tap T5 1565 20 1525 21 1490 21 1...

Page 10: ...Cool Thermostat For the highest efficiency the use of a 2 stage Heating Cooling thermostat is recommended The heat cool thermostatpreventssimultaneousoperationoftheheating and cooling units and is eq...

Page 11: ...valve 2 Measure the liquid refrigerant temperature F at the service valve 3 For the temperature measured determine the required liquid refrigerant pressure from Table 5 page 15 Table 6 page 15 Table 7...

Page 12: ...12 13 1 38 3 2 3 2 5 29 Side View Figure 9 Unit Dimensions A 3 Opening for 12 Diameter Supply Duct 9 15 17 50 9 0 Opening for 14 Diameter Return Duct 10 15 5 5 B 1 3 15 Rear View 3 5 4 5 Ton Model Nu...

Page 13: ...ment des conducteurs en cuivre 3 Ne convient pas aux installations de plus de 150 V a la terre FIELD WIRING LEGEND LOW VOLTAGE HIGH VOLTAGE WIRING DIAGRAM Packaged Air Conditioner Single Phase NOTES 1...

Page 14: ...vant de faire letretien 2 Employez uniquement des conducteurs en cuivre 3 Ne convient pas aux installations de plus de 150 V a la terre FIELD WIRING LEGEND LOW VOLTAGE HIGH VOLTAGE WIRING DIAGRAM Pack...

Page 15: ...358 150 146 294 137 316 141 338 145 359 150 381 154 148 317 141 338 145 360 149 381 154 404 158 150 317 141 339 145 361 149 382 153 404 158 152 340 145 362 149 383 153 405 157 154 363 149 384 153 406...

Page 16: ...55 146 357 182 378 171 398 162 415 160 148 380 181 401 172 421 164 150 403 181 423 173 152 426 182 154 Suct Press OUTDOOR TEMPERATURE F 70 75 80 85 90 95 100 105 Liq Press Dis Temp Liq Press Dis Temp...

Page 17: ...147 378 172 399 172 421 172 443 172 149 403 176 424 177 446 177 151 428 181 449 181 153 453 185 155 Suct Press OUTDOOR TEMPERATURE F 70 75 80 85 90 95 100 105 Liq Press Dis Temp Liq Press Dis Temp Li...

Page 18: ...40 360 380 400 420 440 460 480 500 520 540 560 580 600 75 80 85 90 95 100 105 110 115 120 125 130 135 Liquid Pressure psig Liquid Temperature F Remove refrigerant when above curve Add refrigerant when...

Page 19: ...19...

Page 20: ...uid Pressure high side _________________________ Stage 1 Suction Pressure low side _________________________ ELECTRICAL SYSTEM Electrical connections tight YES NO Line voltage polarity correct YES NO...

Reviews: