Nortek P7RE Series Installation Instructions Manual Download Page 5

5

Figure 2. Single & Multiple duct applications

MultiPle duct aPPlication

Single duct aPPlication

air conditioner inStallation

unpacking the unit

It is recommended that the unit be unpacked at the 

installation site to minimize damage due to handling.

 caution:

do not tip the unit on its side. oil may enter the 

compressor cylinders and cause starting trouble. 

if unit has been set on its side, restore to upright 

position and do not run for several hours. then 

run unit for a few seconds. do this three or four 

times with five minutes between runs.

1. Remove the bands from around the unit.

2. Unfold the top and bottom cap flanges.

3. Carefully remove the top cap and tube.

installing return & Supply air collars

If the supply and return collars are supplied with the 

unit, they will be located in the supply duct. They can be 
easily positioned over the unit openings (

Figure 3

) and 

secured with sheet metal screws. Return and supply duct 
opening sizes are shown in 

Figure 9 

Table 4, (page 

12)

note:

 Before permanently installing the collars, 

it is recommended you pre-fit them over the openings first 
to determine alignment and best fit.

Supply Duct

1. Position the supply duct collar so the edge of the unit 

opening fits between the flange and the bead.

2. Overlap the collar ends keeping the small screw holes 

underneath.

3. Align the holes in the crimped area and install one 

screw. 

note:

 It may be necessary to loosen the four 

screws that hold the transition duct in order to install the 

supply fitting. Re-tighten when installation is complete.

4. Tap collar (if necessary) to ensure engagement with 

unit opening and install second screw.

5. Tighten first screw and rotate collar clockwise so joint 

is near 3 o’clock position.

•  Duct work should be attached directly to the unit flanges 

for horizontal applications.

•  For highly resistive duct systems it may be necessary 

to add an additional return air duct and or supply to 

achieve maximum performance and prevent coil icing 

and refrigerant flood back.

•  The air conditioning output of the system will not 

cool the home if air is lost to the outside through 
leaks in the duct system. ducts that are collapsed 
or restricted by foreign objects will also prevent 
adequate air flow.

•  All  duct  work  passing  through  unconditioned  space 

must be properly insulated to minimize duct losses 

and prevent condensation. Use insulation with an outer 

vapor barrier. Refer to local codes for insulation material 

requirements.

Transition

Duct Screws

Supply Air

Return Air

Duct

Dimples

Figure 3. return & Supply air collars

Summary of Contents for P7RE Series

Page 1: ...e plays an important role as well Pay attention to all safety warnings and any other special notes highlighted in the manual Improper installation of the furnace or failure to follow safety warnings c...

Page 2: ...tions 8 Cooling Only Thermostat 8 Heat Cool Thermostat 10 Blower Speed ECM Motor 10 START UP ADJUSTMENTS 10 Pre Start Checklist 10 Start Up Procedure 10 System Cooling 10 System Heating 10 Refrigerant...

Page 3: ...he information listed below must be followed during the installation service and operation of this unit Unqualified individuals should not attempt to interpret these instructions or install this equip...

Page 4: ...ly and return ducts If practical place the air conditioner and its ducts in an area where they will be shaded from the afternoon sun when the heat load is greatest The length of the supply and return...

Page 5: ...ollar so the edge of the unit opening fits between the flange and the bead 2 Overlap the collar ends keeping the small screw holes underneath 3 Align the holes in the crimped area and install one scre...

Page 6: ...n the air box Connecting the Return Supply Air Flexible Ducts Flexible ducts can be connected to the corresponding fittings with the clamps provided with the ducts See Figure 9 Table 4 page 12 NOTE To...

Page 7: ...installer should become familiar with the wiring diagram before making any electrical connections to the unit Anelectricaldisconnectmustbelocatedwithinsight of and readily accessible to the unit This...

Page 8: ...reaker and do not in any case exceed the maximum size listed on the data label of the unit Thermostat Low Voltage Connections The unit is designed to operate from a 24 VAC Class II control circuit The...

Page 9: ...27 1104 29 1051 30 992 32 Tap T3 1460 22 1415 22 1385 23 1335 24 1275 25 1225 26 1170 27 1120 28 Tap T4 1502 21 1466 22 1437 22 1388 23 1345 23 1305 24 1251 25 1204 26 Tap T5 1565 20 1525 21 1490 21 1...

Page 10: ...Cool Thermostat For the highest efficiency the use of a 2 stage Heating Cooling thermostat is recommended The heat cool thermostatpreventssimultaneousoperationoftheheating and cooling units and is eq...

Page 11: ...valve 2 Measure the liquid refrigerant temperature F at the service valve 3 For the temperature measured determine the required liquid refrigerant pressure from Table 5 page 15 Table 6 page 15 Table 7...

Page 12: ...12 13 1 38 3 2 3 2 5 29 Side View Figure 9 Unit Dimensions A 3 Opening for 12 Diameter Supply Duct 9 15 17 50 9 0 Opening for 14 Diameter Return Duct 10 15 5 5 B 1 3 15 Rear View 3 5 4 5 Ton Model Nu...

Page 13: ...ment des conducteurs en cuivre 3 Ne convient pas aux installations de plus de 150 V a la terre FIELD WIRING LEGEND LOW VOLTAGE HIGH VOLTAGE WIRING DIAGRAM Packaged Air Conditioner Single Phase NOTES 1...

Page 14: ...vant de faire letretien 2 Employez uniquement des conducteurs en cuivre 3 Ne convient pas aux installations de plus de 150 V a la terre FIELD WIRING LEGEND LOW VOLTAGE HIGH VOLTAGE WIRING DIAGRAM Pack...

Page 15: ...358 150 146 294 137 316 141 338 145 359 150 381 154 148 317 141 338 145 360 149 381 154 404 158 150 317 141 339 145 361 149 382 153 404 158 152 340 145 362 149 383 153 405 157 154 363 149 384 153 406...

Page 16: ...55 146 357 182 378 171 398 162 415 160 148 380 181 401 172 421 164 150 403 181 423 173 152 426 182 154 Suct Press OUTDOOR TEMPERATURE F 70 75 80 85 90 95 100 105 Liq Press Dis Temp Liq Press Dis Temp...

Page 17: ...147 378 172 399 172 421 172 443 172 149 403 176 424 177 446 177 151 428 181 449 181 153 453 185 155 Suct Press OUTDOOR TEMPERATURE F 70 75 80 85 90 95 100 105 Liq Press Dis Temp Liq Press Dis Temp Li...

Page 18: ...40 360 380 400 420 440 460 480 500 520 540 560 580 600 75 80 85 90 95 100 105 110 115 120 125 130 135 Liquid Pressure psig Liquid Temperature F Remove refrigerant when above curve Add refrigerant when...

Page 19: ...19...

Page 20: ...uid Pressure high side _________________________ Stage 1 Suction Pressure low side _________________________ ELECTRICAL SYSTEM Electrical connections tight YES NO Line voltage polarity correct YES NO...

Reviews: