background image

Specifications & illustrations subject to change without notice or incurring obligations (06/20). 
O’Fallon, MO, © Nortek Global HVAC LLC 2020. All Rights Reserved.

1032229A

(Replaces 10322290)

MAINTENANCE ITEMS

FREQUENCY OF MAINTENANCE

BEGINNING OF EACH

HEATING SEASON

END OF EACH

HEATING SEASON

MONTHLY

Verify furnace area is free of combustible materials.

X

X

X

Verify combustion and ventilation air is not restricted.

X

X

X

Verify no signs of physical deterioration of the furnace.

X

X

X

Verify no obstructions or restrictions in vent or chimney.

X

X

Verify no holes or cracks in vent pipe.

X

X

Verify no corrosion in vent pipe.

X

X

Verify the horizontal vent pipes slope upwards away from furnace.

X

X

Verify burner flame.

X

Clean or replace filter(s).

X

Clean blower compartment.

X

Clean burner assembly.

X

Clean condensate collection & disposal system (if applicable).

X

Table 1. Maintenance Table

GAS-FIRED

LISTED

FURNACE AIR DUCTS

•  The furnace should be inspected annually by a licensed HVAC 

technician. Table 1 (page 8) contains suggested inspections 

and frequency of maintenance.

•  Homeowners should perform frequent visual inspections of the 

furnace for obvious signs of deterioration. The furnace should 

be secure without sagging, cracks gaps, etc around the base. 

The return air duct connection(s) is secured and sealed to the 

furnace cabinet and terminates outside the area containing 

the furnace. Any signs of damage or loose connections should 

be repaired by a qualified HVAC technician.

VENTING SYSTEM

• For proper and safe operation, this furnace requires 

unrestricted airflow for combustion and ventilation. Inspect for 

blocked or obstructed air openings on or around the furnace, 

and the space around the furnace.

•  The furnace venting system should be inspected annually by 

a licensed HVAC technician. Vent pipe must slope upwards 

and be physically secured without holes or corrosion. Any 

corroded section of vent pipe must be replaced, and any 

obstruction or blockage must be removed by the technician.

•  Flue passageways, the vent system, and the burners should 

be inspected and cleaned (if required) by a licensed HVAC 

technician annually to ensure continued safe operation.

MAINTENANCE & INSPECTION

BLOWER & FILTER

•  It is recommended that the blower compartment be cleaned 

of dirt or lint that may have accumulated in the compartment 

or on the blower and motor as part of the annual inspection.

•  Keep air filters cleaned. It is recommended that the furnace air 

filter be checked at least once a month. Clean or replace filter 

to maintain proper airflow and achieve maximum efficiency.

•  Furniture and drapery should be arranged so that the supply 

air registers and return grilles are not obstructed.

BURNER OPERATION

Perform the startup instructions on page 10. The igniter should 

ignite the closest burner and the flames should quickly carryover 

to the other burners. The flames should be bright blue, with 

occasional yellow streaks.

NEW CONSTRUCTION

The operation of gas furnaces in a construction environment can 

cause a variety of problems with the furnace. Before occupying 

the residence, homeowners should have these safety inspections 

performed by a licensed technician:
•  Before occupancy, the furnace shall be inspected and approved 

by applicable local authority even if this results in redundant 

inspections.

•  The duct work must be inspected and cleaned if found to 

contain any construction debris.

•  The filter must be replaced or cleaned and the furnace must be 

inspected by a licensed HVAC technician. The furnace must 

be cleaned and/or repaired if found to be dirty, damaged, or 

malfunctioning in any way.

Summary of Contents for MG3P

Page 1: ...IMPORTANT Please read all information in this manual thoroughly and become familiar with the capabilities and use of your appliance before attempting to operate or maintain this unit Pay attention to...

Page 2: ...OD DAMAGE 4 ABOUT THE FURNACE 5 INTRODUCTION 5 CATEGORY IV CONDENSING FURNACES 5 FILTER 5 FURNACE LOCATION 5 TROUBLESHOOTING 5 COMPONENT LOCATIONS 6 STARTUP SHUTDOWN 7 STARTING THE FURNACE 7 SHUTTING...

Page 3: ...ou les sorties de l vent de l appareil de chauffage et la prise d air ne soient enaucunefa on obstru es quellequesoitlasaison Safety markings are used frequently throughout this manual to designate a...

Page 4: ...Never operate the furnace without a filter in place Accumulating dust in the return air can build up on internal components resulting in loss of efficiency equipment damage and possible fire Keep air...

Page 5: ...ace operation The homeowner must make sure the condensate drain lines do not become blocked pinched or crushed If the furnace is installed in an area where temperatures fall below freezing special pre...

Page 6: ...e B C D cabinets only Roll Out Switch Transformer Vent Limit Switch Burner Assembly Flame Sensor Roll Out Switch Finish Flange Blower Assembly behind blower panel Blower Door Switch behind blower pane...

Page 7: ...F YOU NEED TO SHUT DOWN YOUR FURNACE FOR SERVICE OR MAINTENANCE SHUT OFF THE GAS VALVE TO THE FURNACE BEFORE TURNING OFF THE ELECTRICAL SERVICE If your installation has a manual gas shutoff valve on t...

Page 8: ...the furnace The furnace venting system should be inspected annually by a licensed HVAC technician Vent pipe must slope upwards and be physically secured without holes or corrosion Any corroded sectio...

Reviews: