background image

7

protection must be in compliance with information listed 
on the outdoor unit data label. Any other wiring methods 
must be acceptable to authority having jurisdiction.

•  The outdoor unit requires both power and control circuit 

electrical connections. Refer to the wiring diagram / 
schematic for identifi cation and location of outdoor 
unit fi eld wiring interfaces (Figure 4, page 10). Make all 
electrical connections in accordance with all applicable 
codes and ordinances.

•  Overcurrent protection must be provided at the branch 

circuit distribution panel and sized as shown on the unit 
rating label and according to applicable local codes. 
See the unit rating plate for minimum circuit ampacity 
and maximum overcurrent protection limits.

•  Provide power supply for the unit in accordance with the 

unit wiring diagram, and the unit rating plate. Connect 
the line-voltage leads to the terminals on the contactor 
inside the control compartment.

•  Use only copper wire for the line voltage power supply 

to this unit as listed in Table 1. Use proper code agency 
listed conduit and a conduit connector for connecting 
the supply wires to the unit. Use of rain tight conduit 
is recommended.

•  208/230 Volt units are shipped from the factory wired 

for 230 volt operation. For 208V operation, remove the 
lead from the transformer terminal marked 240V and 
connect it to the terminal marked 208V.

•  Optional equipment requiring connection to the power 

or control circuits must be wired in strict accordance 
of the NEC (ANSI/NFPA 70), applicable local codes, 
and the instructions provided with the equipment.

Grounding

 WARNING:

The unit cabinet must have an uninterrupted or 
unbroken electrical ground to minimize personal 
injury if an electrical fault should occur. Do not 
use gas piping as an electrical ground

!

This unit must be electrically grounded in accordance 
with local codes or, in the absence of local codes, with 
the National Electrical Code (ANSI/NFPA 70) or the CSA 
C22.1 Electrical Code. Use the grounding lug provided in 
the control box for grounding the unit.

Thermostat Connections

•  Thermostat connections should be made in accordance 

with the instructions supplied with the thermostat and 
the indoor equipment.

•  The outdoor unit is designed to operate from a 24 VAC 

Class II control circuit. The control circuit wiring must 
comply with the current provisions of the NEC (ANSI/
NFPA 70) and with applicable local codes having 
jurisdiction.

•  The low voltage wires must be properly connected to 

the units low voltage terminal block. Recommended 

Table 2. Thermostat Wire Gauge

Thermostat

Wire Gauge

Recommended T-Stat Wire

Unit to T-Stat (Length in FT)

2-Wire

(Heating)

5-Wire

(Heating/Cooling)

24

55

25

22

90

45

20

140

70

18

225

110

wire gauge and wire lengths for typical thermostat 
connections are listed in Table 2.

• The

 

thermostat should be mounted about 5 feet 

above the fl oor on an inside wall. DO NOT install the 
thermostat on an outside wall or any other location 
where its operation may be adversely affected by radiant 
heat from fi replaces, sunlight, or lighting fi xtures, and 
convective heat from warm air registers or electrical 
appliances. Refer to the thermostat manufacturer’s 
instruction sheet for detailed mounting and installation 
information.

Positive Temperature  Coeffi cient Resistor (PTCR)

(Select models only)
The PTCR is factory installed and located on the control 
panel of the outdoor unit.This soft start device is for use 
with reciprocating compressors. If a hard start kit is needed 
on this unit, the soft start (PTCR) must be removed fi rst.

JS5BD-24K

Electrical

Data

Volts-Cycles-Phase

208/230-60-1

Total Amps

11.5

Delay Fuse Max.

20

Min. Circuit Ampacity

14.1

Component

Data

Coil

Area

8.3

Rows-FPI

1-22

Tube Dia.

MC

Fan Motor

Type

PSC

Amps

0.7

Watts-HP

0.1

Fan Blade

Dia.

18”

# Blades

3

SCFM

2800

Compressor
Data

RLA

10.8

LRA

40.3

Refrigerant Suction Line:

Length/O.D.

Liquid Line:

 All Lengths - 3/8”O.D.

15 - 24 ft.

3/4”

25 - 39 ft.

3/4”

40 - 75 ft.

3/4”

R-22 Refrigerant Charge (in Ounces):

(Outdoor unit, Indoor Unit - 15’ Line Set)

53

Approximate Weight (lbs.)

Net

113

Ship

118

Table 3. Electrical Specifi cations & Physical Data

Summary of Contents for JS5BD

Page 1: ...minate the problem call your servicing contractor The Installation Instructions are primarily intended to assist qualified individuals experiencedintheproperinstallationofthisappliance Somelocalcodesr...

Page 2: ...nits 13 Figure 6 JS5BD 024KB 2 Ton Units 14 Figure 7 JS5BD 030KB 2 5 Ton Units 14 Figure 8 JS5BD 036KB 3 Ton Units 15 Figure 9 JS5BD 042 3 5 Ton Units 15 Figure 10 JS5BD 048 4 Ton Units 16 Figure 11 J...

Page 3: ...tem will not operate regardless of the temperature selector setting Figure 1 Digital Thermostat Fan Mode Temperature Selector System Mode AIR CONDITIONER MAINTENANCE Propermaintenanceismostimportantto...

Page 4: ...s unit uses refrigerant R 22 DO NOT use any other refrigerant in this unit Use of another refrigerant will damage the unit WARNING The information listed below must be followed during the installation...

Page 5: ...be carefully inspected for damage prior to installing the equipment at the job site Verify coil fins are straight If necessary comb fins to remove flattened or bent fins Claims for damage apparent or...

Page 6: ...able local codes and ordinances and with the current revision of the National Electric Code ANSI NFPA 70 For Canadian installations the electrical connections and grounding shall comply with the curre...

Page 7: ...ical Code Use the grounding lug provided in the control box for grounding the unit Thermostat Connections Thermostatconnectionsshouldbemadeinaccordance with the instructions supplied with the thermost...

Page 8: ...thermostat s system mode to HEAT and the temperature mode above room temperature 2 Verify the optional heating equipment furnace or electric heat and indoor blower energize Feel the air being circula...

Page 9: ...s greater than therequiredliquidrefrigerantpressuredeterminedin Step 3 then there is too much charge in the system Remove refrigerant and repeat Steps 1 through 3 until the system is correctly charged...

Page 10: ...42 208 144 223 145 84 182 146 195 148 211 148 225 150 239 151 86 199 151 213 153 227 154 241 156 256 157 88 216 157 230 158 243 160 258 161 272 163 90 220 160 233 162 247 164 260 165 274 166 92 237 16...

Page 11: ...180 130 196 137 212 144 78 165 130 180 137 198 142 214 149 230 156 80 184 140 199 147 216 153 232 160 248 167 82 203 151 218 158 234 164 250 171 266 178 84 206 154 222 161 237 168 252 175 268 182 86 2...

Page 12: ...202 156 212 155 222 154 83 197 159 205 160 214 159 224 158 234 158 85 209 163 217 163 226 163 236 162 246 162 87 221 167 229 167 238 166 248 166 258 165 89 224 170 233 171 242 170 250 170 260 169 91 2...

Page 13: ...160 217 160 78 175 166 189 166 204 165 219 165 234 165 80 193 169 207 170 221 169 236 169 251 169 82 210 173 224 173 238 173 253 173 267 173 84 213 177 227 177 241 177 255 177 269 177 86 231 181 245 1...

Page 14: ...d refrigerant when below curve JS5BD 024KB SERIES CHARGING CHART Remove refrigerant when above curve Figure 7 Charging Chart for 2 5 Ton Units with Microchannel Coil 140 160 180 200 220 240 260 280 30...

Page 15: ...sure psig Add refrigerant when below curve JS5BD 036KB SERIES CHARGING CHART Remove refrigerant when above curve Figure 9 Charging Chart for 3 5 Ton Units 140 160 180 200 220 240 260 280 300 320 340 3...

Page 16: ...Add refrigerant when below curve JS5BD 048 SERIES CHARGING CHART Remove refrigerant when above curve Figure 11 Charging Chart for 5 Ton Units 140 160 180 200 220 240 260 280 300 320 340 360 380 400 7...

Page 17: ...it If desired ASCT is factory installed on select models only or may be field installed as shown using manufacturer s approved kit If not present connect Yellow and Black wires per Note 6 8 DO NOT use...

Page 18: ...18...

Page 19: ...19...

Page 20: ...7092410 Replaces 7092340 Specifications illustrations subject to change without notice or incurring obligations O Fallon MO Printed in U S A 08 10 709241...

Reviews: